The squirrel-cage induction motor may have 6, 9, or 12
terminal leads from the ends of its coils brought out of the motor frame
for field wiring connections. Field wiring connections are the connections
that a technician will change right on the factory floor with the motor
mounted in place. Fig. 1 shows the diagram of a nine-lead motor. Notice
that the coils are positioned in the shape of the letter Y. This motor
is called a wye-connected motor or star-connected motor.

Above: Fig. 1: Nine-lead, wye-connected motor.
The wye motor terminals are numbered in the clockwise direction. The
two ends of the first coil are numbered Ti and T4, the second coil is
numbered T2 and T5, and the third coil is numbered T3 and T6. The outside
coils are isolated from each other while the inside coils are connected
together at the wye point. The second diagram shows the motor connected
to three-phase line voltage at Ti, T2, and T3. A table is also provided
to show which terminals are connected together and which ones are connected
to line voltage for the motor to operate correctly. The information provided
in this table is similar to data provided on the data plate of the motor.
A technician will need to make these connections in the field when
he or she is installing the motor. Wire nuts or lugs should be used to
make the connections for the coil terminals and supply voltage wires.
The diagram is shown for the motor so it can be connected for high voltage.
The diagram indicates the high voltage is 480 volts AC. Be aware that
in your area of the country the exact amount of high voltage may vary
from 440 volts AC through 480 volts AC. The diagrams will be marked so
that 480 volts AC represents any high voltage (440, 460, or 480 volts
AC), 240 volts AC represents any low voltage (220, 230, or 240 volts
AC) for a delta system, and 208 volts AC represents the low-voltage wye
system. |