|
10.7 SERVICE CALLS
Service Call 1
Application: Commercial refrigeration (walk-in cooler) Type of Equipment:
Air-cooled condensing unit with evaporator
Complaint: No refrigeration
Service Procedure:
1. The technician reviews the work order from the dispatcher for avail
able information. The work order information reveals that the walk-in cooler
of the meat market is hot with rapid deterioration of stored product. The
condensing unit is located outside behind the structure.
2. The technician informs the manager of his or her presence and obtains
any additional information about the problem.
3. The manager has noticed that the compressor is starting and running
only a short time before cutting off. The condenser fan motor is running
normally.
4. The equipment is 240 V—1ø—60 Hz. With the condenser fan motor picking
up power from the terminals of the compressor, the technician assumes that
voltage is being applied to the compressor. The technician measures the
current draw of the compressor while running. The current draw is seven
times that of the normal running amps of the compressor.
5. The compressor overload breaks power to the compressor after only a
few seconds of operation.
6. The technician turns the power off and locks or labels it when working
with live circuits.
7. The technician checks the compressor motor and determines that the
motor is in good condition.
8. The starting capacitor is hot to the touch. The technician checks to
determine if the capacitor is being removed from the circuit by checking
the amp reading of the capacitor; if the capacitor is reading a cur rent
draw, then the capacitor is remaining in the circuit. The potential relay
is checked to determine the condition of the relay contacts and coil. The
technician reads the resistance between terminals 1 and 2 and 2 and 5.
The reading between 1 and 2 reads 0 ohms. Terminals 1 and 2 are the normally
closed contacts of the relay and should read 0 ohms. The reading between
2 and 5 reads infinite ohms. Terminals 2 and 5 are the relay coil terminals
and should have a very high but measurable resistance. The potential relay
coil is open, allowing the starting capacitor to remain in the circuit
and causing the motor to overload.
9. The part number of the faulty relay is an RBM 128-122-1335CA. The relay
must be replaced with a potential relay with the continuous coil voltage
of 256 and a coil calibration of 300 to 320 volts. The technician finds
the correct relay from the available supply on the service truck.
10. The technician replaces the relay and checks to make certain that
the new relay is removing the capacitor from the circuit by observing the
current draw of the capacitor. There should be a current draw through the
capacitor while the motor is starting, but when the motor reaches a certain
speed, the capacitor current draw should be 0 amps.
11. The technician checks the current draw of the compressor to make certain
the compressor is operating properly.
12. The technician informs the manager of the problem and that it has
been corrected.
Service Call 2
Application: Domestic refrigeration
Type of Equipment: Domestic chest-type freezer
Complaint: Freezer defrosting
Service Procedure:
1. The technician reviews the work order from the dispatcher for avail
able information. The work order information reveals that the freezer is
located in the utility room under the carport and will be unlocked. The
customer has commented that the compressor tries to start but does not
run. The freezer has been unplugged.
2. The technician plugs the freezer in and notices that the compressor
tries to start but does not and the overload takes it out of the circuit.
When checking a chest-type freezer the technician knows that only three
or four components will need to be checked when the compressor is attempting
to start: the compressor, relay, overload, and capacitor, if used. The
overload is seldom the problem, so the technician will check that last.
3. The technician unplugs the freezer.
4. The technician reads the resistance of the compressor and determines
that the compressor is electrically good. The relay is a current type relay
and must be checked next. The relay has a normally open set of contacts
and a magnetic coil that closes the contacts when the compressor tries
to start.
5. The technician checks the resistance of the coil and reads infinity.
The technician determines that the current-type relay coil is open and
not energizing the starting winding, thus preventing the compressor from
starting. The freezer motor is a split-phase motor and does not require
a capacitor.
6. The technician obtains the correct relay from the supplier and replaces
the faulty relay.
7. The technician starts the freezer and checks the current draw of the
compressor to make certain the freezer is operating properly.
8. The technician leaves a note informing the homeowner of the service
performed.
Service Call 3
Application: Residential conditioned air system
Type of Equipment: Packaged heat pump
Complaint: No heat
Service Procedure:
1. The technician reviews the work order from the dispatcher for avail
able information. The work order reveals that the unit is a packaged heat
pump. Someone will be home.
2. Upon entering the residence, the technician makes certain that no dirt
or foreign materials are carried into the structure. The technician also
takes care not to mar interior walls. The customer informs the technician
that the auxiliary heat light has been on when the unit is operating.
3. This heat pump has a capacitor-start—capacitor-run compressor motor.
With the indoor fan motor operating properly, the technician knows that
voltage is available to the unit.
4. The technician removes the compressor access panel. The compressor
is hot to the touch, indicating that it had been attempting to start and
failed, resulting in an open internal overload.
5. The technician must determine why the compressor is not starting. The
compressor and motor are found to be in good electrical condition. The
starting components of the compressor must be checked to determine if they
are good.
6. The technician uses an ohmmeter to check both starting and running
capacitors and finds them good. The potential relay contacts must be checked.
An ohm reading of infinity is read across terminals 1 and 2, indicating
that the normally closed contacts are open and the start capacitor is not
being introduced to the motor starting circuits.
7. The technician turns the power supply off and locks it or labels it.
8. The technician replaces the faulty potential relay with the proper
relay.
9. Power is restored to the unit and the technician checks the operation
of the compressor, making certain that the capacitor is being removed from
the circuit.
10. The technician reads the current of the motor and makes certain the
compressor is operating properly.
11. The technician replaces the compressor access cover.
12. The technician informs the customer of the corrected problems.
Service Call 4
Application: Commercial refrigeration (refrigerator)
Type of Equipment: Air-cooled condensing unit mounted on top with evaporator
Complaint: No refrigeration
Service Procedure:
1. The technician reviews the work order from the dispatcher for avail
able information. The work order information reveals that the temperature
of the refrigerator is above a safe temperature for the product stored.
2. The technician informs the owner of the sandwich shop of his or her
presence and obtains specifics about the operation of the refrigerator.
3. The technician makes every attempt not to disturb the activity of kitchen
personnel.
4. The compressor is hot to the touch and not operating, but the con denser
fan motor is operating, indicating that power is available to the compressor.
5. The technician turns the power supply off and locks or labels it.
6. The technician determines that the compressor and motor are in good
condition.
7. The technician observes that the compressor attempts to start. The
technician measures the current draw of the compressor; the current draw
is extremely high.
8. The technician checks the current-type relay. The resistance reading
for the coil is slightly above 0 ohms, indicating that the coil is good.
The resistance of the relay contacts is infinite when the relay is inverted,
indicating that the relay is bad.
9. The technician replaces the current-type relay.
10. The technician restores power and checks the operation of the compressor.
11. The technician informs the owner of the sandwich shop of the problem
and that it has been corrected.
Service Call 5
Application: Ventilation system
Type of Equipment: Exhaust fan
Complaint: Exhaust fan not running
Service procedure:
1. The technician reviews the work order from the dispatcher for avail
able information. The work order information reveals that the exhaust fan
is not operating, causing a stuffy condition in the room.
2. The technician informs the maintenance supervisor of his or her presence
and obtains additional information about the problem. The supervisor informs
the technician that the motor is operating, but the fan is not.
3. The technician turns the power supply off and locks or labels it.
4. The technician visually inspects the exhaust fan and locates a broken
belt.
5. The technician obtains the correct replacement and installs it, adjusting
the tension.
6. The technician makes certain that the exhaust fan is operating properly.
7. The technician informs maintenance supervisor of the problem and that
it has been corrected.
SUMMARY
Many types of electric motors require special electrical devices to keep
the starting winding or starting component in the circuit until the motor
has reached approximately 75% of full speed. Starting relays are used in
most cases to drop the start windings and/or starting component from the
electrical circuit once the motor has reached operating speed. It is essential
that the starting components and/or starting windings be removed from the
circuit at the correct time to prevent damage to the motor or starting
components.
There are four types of relays in common use in the industry today. The
current-type relay operates on the principle that amperage flowing through
a wire will produce a magnetic field. At its highest point, this magnetic
field will close a set of contacts, thus putting the necessary starting
components in the circuit and removing them at the correct time. The potential
relay has a normally closed set of contacts that are opened and closed
by the back electromotive force of the motor. This back emf corresponds
to the motor speed, thus dropping out the starting components at the right
time. Electronic relays used as starting relays are becoming increasingly
popular in the industry. They have several advantages over the regular
type of starting relay in that they can be used over a variety of sizes
while incorporating other motor components if needed. The hot-wire relay
is seldom used in the industry because better methods are available for
dropping the starting components out of the circuit.
All rotating heating, cooling, and refrigeration equipment must have bearings
to operate efficiently and smoothly. Ball bearings and sleeve bearings
are commonly used today for this purpose. Correct lubrication is essential
to ensure long life and efficient service from the bearings.
In most cases in the industry, electric motors drive some type of equipment.
Direct-drive applications are common, as are V-belt applications. Direct-drive
applications require very accurate fit with little vibration. The device
being driven must turn at the same revolutions per minute (rpm) as the
motor. V-belt connections have a certain amount of tolerance, but they
must be correctly adjusted. They can be used to alter the revolutions per
minute of the equipment by changing the pulleys.
REVIEW QUESTIONS
1. What is the purpose of a starting relay?
a. to start an electric motor
b. to remove the starting winding or component from the circuit
c. to protect the motor from starting overloads
d. to prevent the motor from starting under heavy loads
2. Explain the operating principle of a potential relay.
3. Explain the operating principle of a current relay.
4. What is the difference between a current and potential relay?
5. The contacts of the current relay are
6. The controlling factor for a potential relay is ____
a. back electromotive force
b. line voltage
c. voltage drop
d. none of the above
7. True or False: The contacts of the potential relay are normally open.
8. What is the approximate speed at which the starting windings or components
should be removed from the motor electrical circuit?
a. 50%
b. 75% c. 90% d. 100%
9. As a single-phase motor’s speed is increased from a stationary position,
the current draw _____
a. increases b. decreases
10. As a single-phase motor’s speed is increased from a stationary position,
the back electromotive force_______
a. increases b. decreases
11. Which of the following statements reflects the correct terminal identification
of a potential relay?
a. 1 & 2 coil, 2 & 4 contacts
b. 2 & 4 coil, 3 & 6 contacts c. 1 & 5 coil, 2 & 5 contacts
d. 2 & 5 coil, 1 & 2 contacts
12. A G.E. potential relay with the number 3ARR3-D4F6 would have a continuous
coil voltage of _____.
a. 214
b. 332
c. 420 d. 502
13. An RBM potential relay with the number 128-122-2324K would have a
continuous coil voltage of:
a. 130
b. 170
c. 256
d. 336
14. A G.E. potential relay with a number 3ARR3-C3A1 could be replaced
with which of the following RBM potential relays?
a. 128-212-1167AB b. 128-112-1161AB c. 128-151-1111CD d. 128-212-1147AB
15. An RBM potential relay with a number 128-122-1161BC could be replaced
with which of the following G.E. potential relays?
a. 3ARR3-C4B2
b. 3ARR3-C9D2 c. 3ARR3-C6B2 d. 3ARR3-C2B2
16. What are the two types of bearings used in the industry?
17. Which of the following is not an advantage of the ball bearing?
a. more efficient than a sleeve bearing
b. requires less maintenance than a sleeve bearing
c. cheaper than a sleeve bearing
d. longer life than a sleeve bearing
18. What is the main reason that sleeve bearings are used in the industry?
a. cost
b. maintenance
c. life
d. efficiency
19. What is a direct-drive application?
20. How is the direct-drive application used in the industry?
21. Why are V-belts popular in the industry?
22. What is the correct tension on a V-belt?
23. True or False: If the starting relay is working properly, there will
be no ampere draw through the starting circuit after the motor reaches
full speed.
24. What is the purpose of a hard-start kit in conjunction with a hermetic
compressor?
25. What electrical components make up a hard-start kit?
26. Name the three ways in which ball bearings may be lubricated.
27. True or False: Over-lubrication of a motor and its bearings is as
damaging as underlubrication.
28. Name three ways in which sleeve bearings may be lubricated.
29. What are the common sizes of V-belts and what are their applications?
30. What is the compressor speed of an open-type compressor if the motor
rpm is 1750, the motor pulley diameter is 4 inches, and the pulley diameter
of the compressor is 16 inches?
a. 438
b. 468
c. 498
d. 528
31. What size motor pulley would be required if the motor turns 1750 rpm,
the fan pulley is 8 inches, and the desired rpm of the fan is 650 rpm?
a. 3
b. 4
c. 5
d. 6
32. What is one situation in which a ball bearing cannot be used?
33. Explain the operation of a solid-state PTC starting relay.
34. What advantages does the solid-state starting relay have over the
conventional current-type relay?
PRACTICE SERVICE CALLS
Determine the problem and recommend a solution for the following ser vice
calls. (Be specific; do not list components as good or bad.)
Practice Service Call 1
Application: Commercial refrigeration
Type of Equipment: Frozen food display with air-cooled condensing unit
(240 V—1Ø— 60 Hz)
Complaint: No refrigeration
Symptoms:
1. Condenser fan motor is operating normally.
2. Evaporator fan motor is operating properly.
3. Internal overload is cycling compressor on and off.
4. All starting components are in good condition.
5. Compressor motor is in good condition.
Practice Service Call 2
Application: Domestic refrigeration
Type of Equipment: Frost-free domestic refrigerator (compressor has split-phase
motor)
Complaint: No refrigeration
Symptoms:
1. Compressor is not operating.
2. Correct voltage is available to compressor.
3. Contacts of current-type relay are good.
4. Compressor is cycled on and off by compressor overload.
5. Compressor draws locked rotor current when start is attempted.
Practice Service Call 3
Application: Residential conditioned air system
Type of Equipment: Air conditioner using air handling unit with air-cooled
condensing unit (240 V—1Ø —60 Hz and CSR motor with internal overload)
Complaint: No cooling
Symptoms:
1. Indoor electrical components are operating normally.
2. Condenser fan motor is operating properly.
3. 240 V—1ø—60 Hz is available to compressor.
4. Compressor starts and runs for a short period of time.
5. Compressor and motor are in good condition.
Practice Service Call 4
Application: Commercial refrigeration
Type of Equipment: Glass door refrigerator (240 V—1Ø --60 Hz and CSR motor
with external overload)
Complaint: No refrigeration
Symptoms:
1. Evaporator fan motor is operating normally.
2. Proper voltage is available to compressor.
3. Compressor tries to start, but does not.
4. Compressor and motor are in good condition.
5. Start and run capacitor are good.
6. Condenser fan motor is operating properly.
Practice Service Call 5
Application: Residential conditioned air system
Type of Equipment: Oil-fired furnace with a belt-drive blower motor
Complaint: No heat
Symptoms:
1. Blower motor is not operating.
2. Correct voltage is available to blower motor.
3. Blower motor is drawing locked rotor current.
4. Blower can’t be turned by hand.
Practice Service Call 6
Application: Commercial refrigeration
Type of Equipment: Ice machine (120V - 1Ø - 60 Hz with CS motor)
Complaint: No ice production
Symptoms:
1. Correct voltage is available to compressor.
2. Compressor attempts to start but is cut off by external overload.
3. Current-type starting relay is good.
4. Compressor and motor are in good condition.
|