|
SPLIT-PHASE MOTORS
Two general classifications of split-phase motors are used in the industry.
The resistance-start—induction-run motor and the capacitor-start— induction-run
motor are types of split-phase motors in common use today. Each of these
motors has different operating characteristics while being similar in construction.
Split-phase motors use some method of splitting the phase of incoming power
to produce a second phase of power, giving the motor enough displacement
to start. The split-phase motor uses two windings to displace the phase
and create the needed displacement between the run and start windings to
produce rotation.
Resistance-Start—Induction-Run Motor
The resistance-start—induction-run motor shown in Figure 9.25 has both
a starting winding to assist the motor in starting and a running winding
to continue rotation after the motor has reached a certain speed. Most
single- phase motors have some method of beginning the rotation; in a split-phase
motor, rotation is started by splitting the phase to make a two-phase cur
rent. The single-phase current is split between the running and the starting
winding, which puts one of the windings out of phase by 45 to 90 degrees.
The starting windings are used to assist the split-phase motor in starting.
They are also used until the motor has reached a speed that is about 75%
of its full-capacity speed. The starting windings then drop out of the
circuit by the use of a centrifugal switch. After that occurs, the motor
operates at full speed on the main or running winding alone.
Fig. 9.25 Split-phase motor
Fig. 9.26 Cutaway view of an electric motor: Bearings; Stator; Squirrel
cage rotor; Bearings; Motor windings
A cutaway view of a split-phase motor is shown in Figure 9.26.
The split-phase motor can be operated on 120 volts—single phase—60 hertz
or 208/240 volts—single phase—60 hertz. Some split-phase motors can operate
on either voltage by making simple changes in their wiring if so desired.
Thus, they are dual-voltage motors. Split-phase motors can be reversed
by reversing the leads of the starting winding at the terminals in the
motor.
Split-phase motors are used when a high starting torque is not required.
They are used in such equipment as belt-driven evaporator fan motors, hot-
water pumps, small hermetic compressors, grinders, washing machines, dryers,
and exhaust fans.
Operation
The phases in a split-phase motor are split by the makeup of the starting
windings. The starting winding is designed with smaller wire and more turns
than is the running winding, which has a greater inductance. Therefore,
the running winding is displaced from the starting winding because of its
greater inductance. This displacement causes a resistance to current flow
to build up in the running winding. The phase displacement means the current
reaches the two windings at separate times, allowing one winding to lead,
in this case the starting winding. However, some manufacturers allow current
to reach the running winding first by designing an increased resistance
into the starting winding and a decreased induction into the running winding.
Whatever method is used, the motor basically operates on the same principle:
splitting the phase.
Fig. 9.27 Layout of a split-phase motor: Running windings, Starting windings
Legend:
A: Running windings
B: Starting windings
C: Rotor
The operation of a split-phase motor, referring to Figure 9.27, is as
follows:
1. Power is applied to the running and starting windings in parallel.
The motor itself splits the phase by the counter electromotive force (emf)
in the running winding, which acts as a resistance to hold back the cur
rent flow to the running winding. On the alternation of power, the starting
winding creates a higher magnetic field than the running winding.
2. In half of a cycle the alternations are changed. The running winding
has the stronger magnetic field, moving the rotor a certain distance depending
on the number of poles in the motor. For the motor in Figure 9.27, the
distance is one-fourth of a rotation.
3. As the alternations continue at the rate of 60 cycles per second, the
motor continues to rotate with the magnetic field of the stator. Therefore,
the rotor, with its magnetic field permanent, attempts to keep up with
the rotating magnetic field of the stator.
4. The motor is equipped with a centrifugal switch that drops the starting
winding out of the circuit when the motor has reached 75% of its full speed.
Troubleshooting
Split-phase motors are one of the most reliable types of motors used in
the heating, cooling, and refrigeration industry. They are used on most
types of single-phase equipment. The split-phase motor is easy to troubleshoot
if the service technician has a good understanding of its operation. The
three probable areas of trouble are the bearings, the windings, and the
centrifugal switch.
The bearings of any motor often give trouble because of wear and improper
maintenance. Identification of a motor with bad bearings is simple. The
motor will have trouble turning and in some cases may be locked down completely.
The windings of a split-phase motor can be shorted, open, or grounded.
This is easily diagnosed with an ohmmeter.
Fig. 9.28 Centrifugal switch used in a split-phase motor: Wiring
terminals
The centrifugal switch, shown in Figure 9.28, is the hardest section to
diagnose for troubles because it stays in the circuit only a short time.
The centrifugal switch has a tendency to stick in an open or closed position
because of wear and often must be replaced. The centrifugal switch can
usually be heard when it drops in after the motor is cut off. Hence, it
can be checked effectively in this manner. If the centrifugal switch does
not drop out of the circuit, the motor will pull an excessively high ampere
draw and cut off on overload. One sure method of checking the centrifugal
switch is by disassembling the motor and making a visual inspection.
Capacitor-Start-Induction-Run Motor
The capacitor-start motor, shown in Figure 9.29, produces a high starting
torque, which is needed for many applications in the industry. The open
capacitor-start motor operates like a split-phase motor except that a capacitor
is inserted in series with the centrifugal switch and the starting winding.
The centrifugal switch breaks the flow of current to the starting capacitor
and starting winding. The centrifugal switch opens when the motor has reached
a speed that is 75% of its full speed. Figure 9.30 shows a schematic diagram
of the motor.
Capacitor-start motors are used on pumps, small hermetic compressors,
washing machines, and some types of heavy-duty fans.
Fig. 9.29 Capacitor-start motor; Fig. 9.30 Schematic diagram of an open
capacitor-start motor with a centrifugal switch. Relays may be used instead
of centrifugal switch.
Open Type
As we have said, the open capacitor-start motor is similar in design to
the split-phase motor with the exception of the capacitor. Therefore, troubleshooting
the open capacitor-start motor is similar to checking the split- phase
motor except for checking the capacitor. There are four possible areas
of trouble in the open capacitor-start motor: windings, bearings, centrifugal
switch, and capacitor.
The windings can be, easily checked with the use of an ohmmeter by checking
for shorts, opens, and grounds.
The bearings of a motor usually fail because of lack of maintenance or
wear. Motor bearings will usually become tight or lock down completely.
This condition can be determined by trying to turn the motor. If the motor
has a tight place in its rotation or will not turn at all, the bearings
are faulty in the motor.
Due to the constant opening and closing of the centrifugal switch, it
is often the culprit in motor problems. The centrifugal switch may stick
in an open or closed position or its contacts may be defective. A centrifugal
switch, in some cases, can be checked with an ohmmeter to determine its
position, open or closed. In other cases, the motor will have to be disassembled
to check the switch.
The capacitor is easy to check with an ohmmeter. The capacitor is often
mounted in one end bell of the motor rather than on top of the stator.
Enclosed Type
When capacitor-start motors are used in small hermetic compressors, a
centrifugal switch cannot be used because of the oil used to lubricate
the compressor. Instead, an external relay is used to break the power going
to the starting winding and the starting capacitor. In this case, the capacitor-
start motor is an enclosed motor with a starting relay. By inserting a
capacitor in the starting winding, a phase displacement is created between
the running and starting windings, causing the motor to rotate.
The enclosed capacitor-start motor has an external relay to drop the starting
winding and starting capacitor out of the circuit. This capacitor should
be checked to determine its condition.
The condition of the windings of an enclosed motor can easily be checked
with an ohmmeter. The windings have a set of terminals on the outside of
the casing that lead to the windings. Use an ohmmeter to check across these
terminals to determine if the windings are shorted, open, or grounded.
The enclosed motor can also be locked down due to worn bearings or to
internal failure of some component of the motor. This condition can be
detected with an ammeter or by the humming sound of the motor on an attempted
start.
PERMANENT SPLIT-CAPACITOR MOTORS
Permanent split-capacitor motors, also known as PSC motors, are simple
in design and have a moderate starting torque and a good running efficiency,
which makes them a popular motor in the industry. Figure 9.31 shows a PSC
motor used as a fan motor. Figure 9.32 shows a hermetic compressor that
uses a PSC motor to power the compressor.
The starting winding and the running capacitor of the PSC motor are connected
in series, as shown in Figure 9.33(a). The schematic diagram of the hookup
is shown in Figure 9.33(b). The running and starting windings are in parallel,
but the capacitor causes a phase displacement.
Permanent split-capacitor motors are used on compressors, where the refrigerant
equalizes on the “off” cycle, on direct-drive fan motors, and in other
applications in the industry. It has a relatively low cost in comparison
with other motors because it does not have a switch to drop the starting
winding out of the circuit. The PSC motor can be used only when a moderate
starting torque is required to begin rotation.
Fig. 9.31 Permanent split-capacitor motor used as a fan motor; Fig. 9.32
Hermetic compressor utilizing a PSC motor
Fig. 9.33 Diagrams of permanent split-capacitor motor: (a) Hookup; (b)
Schematic. Running capacitor; Hermetic compressor,
Legend:
C: Common terminal
R: Running winding terminal
S: Starting winding terminal
RC: Running capacitor
Operation
The permanent split-capacitor motor has two windings: a running (main)
winding and a starting (phase) winding. Both windings are wound with almost
the same size and length of wire. A running capacitor is put in series
with the starting winding. The capacitor causes the electron flow through
the starting winding to shift it out of phase with the running winding.
Therefore, a rotating magnetic field is set up, causing the rotor to turn.
Multispeed PSC motors contain additional running windings. The starting
winding is in series with the running capacitor and in parallel with the
running winding. Figure 9.34 shows a schematic diagram of a three-speed
PSC motor. For high-speed operation, the starting and main windings are
energized. Medium-speed operation is accomplished by energizing the starting
winding with the main and medium-speed windings connected in series. For
low-speed operation, the main, medium, and low windings are connected in
series with each other, and all are connected in parallel to the starting
winding.
Fig. 9.34 Schematic diagram of a three-speed PSC motor
Troubleshooting
The PSC motor usually gives trouble-free operation for long periods. The
three most common failures in a PSC motor are in the bearings, windings,
or capacitor.
The bearings of a PSC motor often become faulty because of wear or lack
of proper maintenance. Bearings in any motor can be diagnosed with little
trouble by rotating the motor by hand and noticing rough places in the
movement or the shaft being locked in one position.
The windings of a motor become faulty because of overheating, over loading,
or a faulty winding. A bad motor winding can easily be checked with an
ohmmeter. The windings could be shorted, open, or grounded. The service
technician should use care in diagnosing problems with the windings of
PSC motors because they are often built with several speeds.
A bad capacitor can keep a PSC motor from starting or can pull a high
ampere draw when running. Capacitors can be checked by one of the methods
covered in Section 9.5. In most cases, faulty PSC motors will be replaced
with new motors rather than repaired. The PSC motor is easy to troubleshoot
with the right tools and knowledge.
Probably the most difficult aspect of PSC motors is their design. PSC
motors are often built with several speeds. Service technicians must pay
careful attention when replacing a faulty PSC motor because if the motor
is connected incorrectly, permanent damage can occur. Most PSC motors are
furnished with a wiring diagram to ensure correct installation. Motor manufacturers,
however, make only a limited number of motors to replace the many different
motors in the field. Thus, a service technician may have to adapt the replacement
motor to a specific application.
CAPACITOR-START-CAPACITOR-RUN MOTORS
The capacitor-start—capacitor-run motor, or CSR motor produces a high
starting torque and increases the running efficiency. It is actually a
capacitor- start motor with a running capacitor added permanently to the
starting winding. The starting winding is energized all the time the motor
is running. The capacitor-start—capacitor-run motor takes the good running
characteristics of a permanent split-capacitor motor (see Section 9.7)
and adds the capacitor-start feature. This produces one of the best all-around
motors used in the industry.
Capacitor-start—capacitor-run motors are used almost exclusively on hermetic
or semi-hermetic compressors. Rarely will this type of motor be used as
an open-type motor because of the cost of the components necessary to produce
it. Most open-type motors do not use a starting relay but use the centrifugal
switch instead. Open-type motors are usually built as permanent split-capacitor
motors or capacitor-start motors. Occasionally, a CSR motor will be used
in an open-type motor when an extremely high starting torque is required.
Operation
The CSR motor begins operation on a phase displacement between the starting
and running windings, which allows rotation to begin. The running capacitor
lends a small amount of assistance to the starting of the motor, but its
main function is to increase the running efficiency of the motor. Figure
9.35 shows a schematic diagram of this motor with its starting components.
Troubleshooting
The capacitor-start—capacitor-run motor is sometimes difficult to troubleshoot
because of the number of components that must be added to a regular motor
to produce it. The windings, bearings, potential relays, starting capacitor,
and running capacitor must all be checked.
The windings of a CSR motor can be easily checked with an ohmmeter to
determine if the windings are shorted, open, or grounded. In most cases,
the windings will be enclosed in a hermetic casing and the terminals will
be on the outside of the casing. However, the type of motor makes little
difference in checking the winding as long as the technician uses the correct
terminals.
Fig. 9.35 Schematic diagram of a capacitor-start-capacitor-run motor.
Legend:
C: Common terminal
R: Running winding terminal
S: Starting winding terminal
RC: Running capacitor
SC: Starting capacitor
SR: Starting relay (potential)
The bearings of a CSR motor can be worn so badly that the motor will not
turn or will turn only with a great deal of difficulty. The bearings of
hermetically sealed motors are enclosed and therefore harder to check,
but the condition of the bearings can be determined by a whining sound,
or by the motor pulling a larger-than-normal ampere draw. Care should be
taken not to condemn the bearings of a motor because of a high ampere draw
unless you are sure this is the problem.
The starting relay can be checked by diagnosing the condition of the contacts
and the coil. The contacts can be checked with an ohmmeter or by visual
inspection. On an ohmmeter the contacts should show zero resistance. The
visual inspection is easy once the relay is disassembled. Then the condition
of the contacts can be determined: sticking, pitting, or mis alignment.
The coil is checked like the windings of a motor.
The starting and running capacitors are easily checked with an ohmmeter
to determine their condition.
Troubleshooting a CSR motor is done by checking all components of the
motor. These motors must be correctly checked to prevent other components
from being destroyed. For example, a capacitor will be destroyed if the
contacts or coil of a starting relay are bad.
THREE-PHASE MOTORS
Three-phase motors are rugged, reliable, and more dependable than other
types of motors. The most common type and the type often used in heating,
cooling, and refrigeration is the squirrel cage induction type, shown in
Figure 9.36. This motor will be the only three-phase motor discussed in
this section.
Fig. 9.36: Three-phase induction motor
Three-phase motors are considerably stronger than single-phase motors
because of the three phases that are fed to the motor. Three-phase current
actually supplies three hot legs to the device, rather than the two hot
legs supplied by single-phase power. Therefore, instead of having a two-phase
displacement, a three-phase displacement is available without using starting
components. Three-phase motors are common to the industry; thus the technician
should understand their operation.
Operation
Three-phase motors operate on the same principles as the single-phase
with the exception of the three-phase displacement. A rotating magnetic
field is produced in the stator. This interacts and causes a magnetic field
in the rotor. However, the three-phase motors require no starting apparatus,
because none of the phases are together. In the sine wave of the three-phase
motor, none of the phases peaks at the same time. Each phase is approximately
120 electrical degrees out of phase with the others. For this reason, there
is no need to use any device to cause a phase displacement, as is needed
in the starting of single-phase motors.
Three-phase motors can be purchased in any voltage range desired. For
example, a dual-voltage, three-phase motor can be operated on two different
voltages with minor modifications in the wiring.
Three-phase motors have two basic types of windings. They are the star
winding or wye (Y) winding, as shown in Figure 9.37, and the delta winding,
as shown in Figure 9.38. There is no operational difference between the
two types, but it does allow designers more latitude in three-phase motor
design.
Fig. 9.37 Schematic diagram of the star winding of a three-phase motor
Low-voltage hookup:
- L1 to T1 and T7
- L2 to T2 and T8
- L3 to T3 and T9
- Tie T4, T5, and T6 together
High-voltage hookup:
- L1 to T1
- L2 to T2
- L3 to T3
- Tie T4 to T7, T5 to T8, and T6 toT9
Fig. 9.38 Schematic diagram of the delta winding of a three-phase motor
Low-voltage hookup:
- L1 to T1, T6 and T7
- L2 to T2, T4 and T8
- L3 to T3, T5 and T9
High-voltage hookup:
- L1 to T1 L2 to T2 L3 to T3
- Tie T4 to T7, T5 to T8, and T6 to T9
Troubleshooting
A three-phase motor can be checked by reading the resistance of the winding
with an ohmmeter. If a resistance reading of 0 ohm occurs, the motor is
shorted. A reading of infinite resistance indicates an open winding. A
reading of some measurable resistance is usually from 1 ohm to 50 ohms,
depending on the size of the motor. The larger the motor, the smaller the
resistance. The smaller the motor, the larger the resistance of the winding.
Care should be taken because of the chance of a spot burnout in the winding.
Experience should give service technicians the ability to diagnose any
type of electric motor.
ELECTRONICALLY COMMUTATED MOTORS
The refrigeration, heating, and air-conditioning industry has a made a
concentrated effort to increase the efficiency of equipment that is being
placed into operation. This can be accomplished by decreasing the electrical
power consumed by the equipment by decreasing the load on equipment. The
largest electrical loads in refrigeration or air-conditioning systems are
the motors that supply mechanical energy to operate compressors, fans,
pumps, and other devices requiring rotation. Electrical resistance heaters
also require large amounts of electrical power but are seldom used because
of high energy costs. Most other electrical loads in refrigeration and
air- conditioning systems require only minimal electrical power. The major
emphasis for increased efficiency and reduction in system power consumption
has, therefore, been the electric motor.
Equipment typically operates at full-load capacity equipped with some
type of capacity control, which is seldom the case in residential installations.
Most equipment could easily satisfy the heating or cooling load of the
structure while supplying only a fraction of its rated capacity. For example,
if the capacity of an air-conditioning system was 48,000 Btu/hr and the
building’s heat gain was only 24,000 Btu/hr, conventional equipment would
supply 48,000 Btu/hr for the heat load of only 24,000 Btu/hr. This would
result in frequent system starting and stopping, not to mention the increased
chances of high-humidity-related issues. Stopping and starting an electrical
motor requires a great deal more electrical power than normal running conditions.
Recall that the locked rotor amperage, which is the amperage draw of the
motor on initial startup, is about five to seven times greater than the
motor’s normal running amperage. It would, therefore, be advantageous if
the equipment operated for a longer period of time at a reduced capacity.
This would result in using less electrical energy than the frequent stopping
and starting alternative of forcing the equipment to operate at full capacity
for shorter periods of time. In addition, less frequent starting and stopping
reduces the wear and tear on the system’s mechanical components. One method
of accomplishing this goal is to incorporate variable-speed motors into
the system. Variable-speed motors have the ability to vary their speed
to match the load of the structure. As a result, equipment efficiency is
increased and electrical power consumption is reduced as the equipment
capacity will closely match the structure’s heating or cooling load.
There are several methods used to control the speed of electric motors.
The speed of an alternating current electric motor is determined by the
number of motor poles and the frequency of the power supply. Alternating
current is difficult to regulate and control, making motor speed modulation
difficult to accomplish by regulating the frequency of the alternating
cur rent power supply. The speed of AC motors can easily be varied by changing
from one pole arrangement to another, a feature commonly found on many
multispeed alternating current motors. When the speed of an AC motor is
varied by altering the frequency of the power supply, variable frequency
drives (VFDs) are used. These tend to be bulky and very expensive for many
applications, but advances in technology are helping to remedy these setbacks.
A very easy way to produce a variable-speed motor is by converting alternating
current to direct current. Direct current is easier to control and regulate,
enabling a motor to operate at variable speeds. The most common methods
used to vary the speed of electric motors, short of using VFDs, are using
direct current converters and electronically commutated motors (ECM). The
direct current converters convert the alternating current that the power
company supplies to direct current, which can then be regulated to vary
the speed of the motor. The electronically commutated motor actually reverses
one-half of each alternating current cycle to form a single directional
current, which is then utilized to vary the speed of the motor.
The increase of electronically commutated motor usage has been phenomenal
over the past ten years—from 100,000 motors in service in 1995 to over
one million in 2005. ECM-driven appliances are found in residential, commercial,
and industrial markets. Probably the greatest increase in the usage of
the ECM has been the residential market, where motors controlling fans
are usually smaller than 1 horsepower. Electronically com mutated motors
are manufactured for 120-, 240-, and 277-volt inputs and typically range
from 1/3 horsepower to 1 horsepower for primary air movement in residential
air-conditioning systems. Figure 9.39 shows an ECM used as the primary
air mover in a residential gas furnace. ECMs have also become popular in
smaller sizes with 120- and 240-volt inputs that are used in furnace draft
inducers as shown in Figure 9.40. The ECM is utilized in many other applications,
such as fan terminal boxes in variable air volume (VAV) systems and air
movement in refrigeration display cases, vending machines, and walk-in
coolers. Most major air-conditioning manufacturers are using the ECM in
their high-efficiency equipment lines.
Fig. 9.39 ECM used as primary air movement in residential gas furnace
Fig. 9.40 ECM used as furnace draft inducer
Construction
The ECM is a brushless DC, three-phase motor with a permanent magnet rotor
shown broken down in Figure 9.41. The ECM is actually a two-part motor.
One part is the motor and the other part is the control. Both parts are
shown in Figure 9.41. Motor phases are sequentially energized by an electronic
control, energized by a power supply. A control module is attached to one
end of the motor that uses input signals to obtain and maintain the correct
motor speed. The motor control is shown in Figure 9.42.
Fig. 9.41 ECM broken down in sections
Fig. 9.42 The control module of ECM; Fig. 9.43 The stator of ECM
Fig. 9.44 The rotor of ECM
The ECM stator is a laminated interlocked stator wound like a three-phase
motor, as shown in Figure 9.43. The rotor of the ECM turns with the aid
of ball bearings and is equipped with three permanent magnets attached
to it at 120-degree segments, as shown in Figure 9.44. The magnets are
attached to the rotor with heavy-duty glue and are magnetized by the manufacturer.
Operation
The operation of an electronically commutated motor is determined by the
inputs to the motor control. The input signals vary depending on the mode
of system operature. Line voltage alternating current is supplied to the
motor at all times. The alternating current is converted to direct current
and sent to the inverter. The signal from the motor control, also sent
to the inverter, ultimately determines the speed of the motor. The ECM
experiences a soft start when initially energized. This means that the
motor starts at a low speed and gradually ramps up to its final desired
speed, which depends on the system conditions. Since the motor ramps its
speed up and down, the ECM allows for a wide range of blower or fan speeds.
Figure 9.45 shows a block diagram of the ECM and the control. At present
it is almost impossible to cover all of the different inputs of the ECM
because each manufacturer uses a unique signal or interface strategy.
For more information on the manufacturer-specific signals and interfaces,
the technician should consult the equipment manufacturer. Electronically
commutated motors have many advantages over the PSC motor, which has been
used almost exclusively in low-torque applications prior to the introduction
of the ECM. These advantages include quieter operation, higher motor efficiency,
better performance, greater comfort for the consumer, and better humidity
control in the occupied space.
Fig. 9.45 Block diagram of ECM and control:
Troubleshooting
Electronically commutated motors are more difficult to troubleshoot than
most other motors used in the field because of the various interfaces,
motor control strategies, and modules that are used by the various equipment
manufacturers. The technician should always refer to manufacturer’s information
when troubleshooting these motors. Some inherent actions of the ECM, such
as the rocking of the stator or the rumbling sound on startup and shut
down, may lead the technician to condemn the motor. When the motor is rocking,
trying to go both directions, it is determining the location between the
stator and the rotor. The technician should isolate the sound rather than
change ECMs when the noise is objectionable. ECMs should always be tested
under load because motor operation without a load can be erratic. The line
voltage supplies to the ECM should never be disconnected or connected with
the power on as this action could cause damage to the control module.
ECMs must have high and low voltage at the appropriate connections to
operate. This should be the first item that a service technician should
check if the motor is not operating. The motor’s failure to operate could
be caused by the absence of either line or low voltage. The technician
should check each voltage source and verify that the measured voltage is
within accept able ranges. If the motor starts but runs erratically, the
problem could be anything from loose low-voltage connections to moisture
in the control. Common indications of motor/controller problems include
constant ramping of the motor speed, either up or down, and constant motor
speed during periods of varying load. When problems such as these occur,
a troubleshooting chart from the manufacturer could be helpful. The common-sense
method of troubleshooting an ECM is to first check the motor. The motor
must be disconnected from the control module to check it properly. The
resistance readings of the motor should be similar to those of a three-phase
motor. Each winding should have the same resistance. If each winding reads
the same resistance and the motor is not grounded, the problem is probably
elsewhere. Once you have determined that the motor is good and all connections
are good, the next item to check is the control module. Figure 9.46 shows
an electronic module that is available to check the ECM.
Fig. 9.46 Electronic module used to troubleshoot ECM
HERMETIC COMPRESSOR MOTORS
Hermetic compressors are becoming increasingly popular because of their
low cost. Hermetic motors are of the induction type. They are designed
for single- and three-phase current. There are four basic types of single-phase
motors used in hermetic compressors. The split-phase motor is used on small
equipment (fractional horsepower). The capacitor-start motor is also used
on small equipment. The permanent split-capacitor motor is used on most
window units and small residential units. The capacitor-start—capacitor-run
motor is used on any application that requires a good starting and running
torque. Many hermetic compressors are built with three-phase motors; usually
these are used on the larger equipment.
CAUTION: Make sure all compressors are properly grounded.
Operation
Hermetic compressor motors are totally enclosed in a shell with refrigerant
and oil. Hence, they require special considerations. Nothing can be used
inside the shell that is capable of causing a spark or that has to move
on the crankshaft, such as a centrifugal switch. Therefore, no starting
apparatus can be incorporated inside the compressor shell. Starting relays
and capacitors must be mounted and wired outside the motor. It must be
remembered that hermetic motors operate the same as other motors with the
exception of the enclosure.
CAUTION: Oil and refrigerant can spray out of a hermetic compressor
when an electrical terminal of the compressor is vented.
CAUTION: The protective covering of the electrical terminals of a
hermetic compressor should always be in place in the event of terminal
venting.
Terminal Identification
All single-phase motors have a common, a start, and a run terminal. These
terminals are sometimes wired directly into an open-type motor and are
difficult to find. The common is the junction point of the start and run
terminals. The start and run terminals are connected to one end of the
windings while the common is connected to the other end. The schematic
diagram of a single-phase compressor motor is shown in Figure 9.47 with
the terminals identified. Of course, each of the windings of a three-phase
hermetic motor is the same because no starting apparatus is required.
In single-phase motors, it is important for the service technician to
deter mine the common, start, and run terminals. This task can be performed
simply and easily by using an ohmmeter to obtain the resistance of each
winding with respect to common. Figure 9.48 shows the resistance values
of a single-phase motor after the resistance has been measured at each
terminal on the compressor. To find the run, start, and common terminals,
the following procedure should be followed:
1. Find the largest reading between any two terminals. The remaining terminal
is common (in Figure 9.48 the reading between A and B is largest; C is
common).
2. The larger reading between common and the other two terminals identifies
start (C to A is 2 ohms and C to B is 10 ohms; therefore, common to B is
larger and B is start).
3. The remaining terminal is run (A is run).
This procedure is important, especially in installing the external electric
devices, although it is not necessary if a good, readable diagram is available.
In a three-phase motor, the resistances among all three terminals are the
same.
Fig. 9.47 Schematic diagram of a single-phase compressor with the terminals
identified: Compressor terminal box; Fig. 9.48 Terminals of a single-phase
compressor with ohmic values given
Legend:
R: Run terminal
C: Common terminal
S: Start terminal
Troubleshooting
Troubleshooting a hermetic compressor motor is often difficult because
of its physical makeup and because it is totally enclosed in a shell and
cannot be visually inspected. Small hermetic compressors usually have some
type of external overload, as shown in Figure 9.49, whereas large hermetic
compressors usually have internal overloads, as shown in Figure 9.50. The
winding layouts of single-phase hermetic compressors are similar regardless
of motor size. The only difference is the size of the windings, which will
vary the resistance readings of the motor windings. Three-phase hermetic
compressor motors are generally produced in sizes above 3 horsepower. Through
experience, the service technician will be able to determine the approximate
resistance of the motor windings in a hermetic compressor.
Fig. 9.49 Small hermetic compressor with external overload; Fig. 9.50
Large hermetic compressor with internal overload (cutaway)
Electrical troubleshooting of hermetic compressor motors is done by taking
a resistance reading of the windings with a good ohmmeter. Determining
the condition of the windings is easy if the problem with the motor is
open windings, shorted windings, or grounded windings. Figure 9.51 shows
a schematic representation of these three conditions.
CAUTION: If arcing sounds (sizzling, sputtering, or popping) are heard
inside a compressor, immediately move away; this sound indicates a possible
compressor terminal venting situation.
Fig. 9.51 Schematic representation of good, shorted, open, and grounded
compressor windings with internal overload: Good, Shorted, Open, Grounded
Most single- or three-phase hermetic compressor motors have three terminals
on the outside of the casing that connect the motor to the external power
wiring, as shown in Figure 9.52. Some large hermetic compressors have more
than three terminals, such as dual-voltage, part winding motors or two-speed
motors, as shown in Figure 9.53. The resistance readings of single-phase
motor windings are not the same because the compressor has a start winding
and a run winding connected by a common wire, as shown in Figure 9.54.
The physical makeup of a single-phase motor will allow the service technician
to match the resistance readings to determine the condition of the windings.
The sum of the resistance readings of the start to common terminals and
the run to common terminals should equal the resistance reading obtained
between the run and start terminals, as discussed in the terminal identification
section. If the readings do not match, a spot burnout of the winding is
likely. Three-phase motors will have the same resistance in each winding;
if not, the motor is bad because of the spot burnout. The service technician
must be careful, however, before condemning a hermetic motor whose winding
resistance readings vary, because the problem may actually be bad connections,
a faulty meter, or a misreading of the meter. A good service technician
should use every possible diagnostic tool to ensure that no good hermetic
compressor is condemned.
CAUTION: When removing a compressor, make sure that electrical power
supplies have been disconnected and the refrigerant recovered.
Fig. 9.52: Spade-type hermetic push-on terminals ; Several terminal arrangements
on hermetic compressors. Screw terminals: 24-Volt compressor sensors; Line
voltage c’ case heaters; Compressor power; Two-speed motor connections
Fig. 9.53 Terminals on a large hermetic compressor
Fig. 9.54 Schematic of windings of a single-phase compressor with internal
overload (ohm readings for winding shown)
Fig. 9.55 Open compressor winding being checked with an ohmmeter.
Fig. 9.56 Shorted compressor winding being checked with an ohmmeter.
Fig. 9.57 Grounded compressor windings being checked with an ohmmeter.
Diagnosing an open, shorted, or grounded hermetic compressor motor is
easy because the resistance readings obtained are definite and exact. An
open winding in the compressor motor means there is no continuity or no
complete circuit; it gives an infinite resistance reading, as shown in
Figure 9.55. A shorted winding in a compressor motor means the winding
has burned together; it gives a zero ohm reading, as shown in Figure 9.56.
A grounded winding in a compressor motor means that part of the winding
is contacting the compressor body; it gives a resistance reading between
the shell and the terminals of a compressor, as shown in Figure 9.57. Good
contact on the compressor shell must always be maintained if the motor
is grounded; therefore, any paint must be removed from a small section
of the compressor. The open and shorted windings should be read on a low
ohm scale (R x 1), but the grounded winding should be read on the R x 10,000
scale or higher. A grounded compressor can be dangerous because the technician
or customer can receive an electrical shock if he or she touches the casing
of a slightly grounded compressor. A resistance reading as high as 500,000
ohms indicates a grounded compressor that should be changed. Grounded compressors,
if allowed to operate, will often operate at a higher-than-normal temperature;
the warmer the windings, the lower the resistance of the ground in most
cases.
CAUTION: To ensure safety and prevent damage to the motor, restart only
after determining the cause of stoppage.
CAUTION: Before resetting a circuit breaker or fuse, check for a short
circuit to ground.
Before condemning the compressor, service technicians should make certain
that the internal overload of the compressor is not open. This condition
can easily be determined by touching the compressor; if the compressor
is hot, it is a good indication that the overload is open. The internal
overload of a single-phase hermetic compressor is located in the common
conductor that connects the run and start windings, as shown in Figure
9.58. Internal overloads used in three-phase hermetic compressor motors
are connected at the common junction of the windings, as shown in Figure
9.59. There are many reasons for an internal overload to open in a hermetic
compressor: for example, low refrigerant charge, locked-down compressor,
faulty starting components, and high discharge pressure.
CAUTION: When troubleshooting electric motors or hermetic compressor motors
that are extremely hot, make sure they have ample time to cool before condemning
them.
Mechanical failures in hermetic compressors often seem like electrical
problems, especially when the compressor is locked down or when the internal
overload opens because of some mechanical failure. The technician must
make certain the problem is truly electrical before an accurate diagnosis
can be made.
Fig. 9.58 Schematic of a single-phase compressor with internal overload;
Fig. 9.59 Schematic of a three-phase compressor with internal overload.
. |