|
OBJECTIVES:
After studying this unit, the learner/learner will be able to:
• state the function of a dc generator.
• list the major components of a generator.
• describe the difference between a separately-excited and a self-excited
generator.
• explain how the output voltage of a generator can be varied.

Ill. 1-1: Compound generator fields, with commutating poles:
commutating pole, armature, main pole, brushes, commutator
A dc generator changes mechanical energy into electrical energy. It furnishes
electrical energy only when driven at a definite speed by some form of
prime mover, such as a diesel engine or a steam turbine.
DC generators are used principally in electrical systems for mobile equipment.
They are also used in power plants supplying dc power for factories and
in certain railway systems. DC power is used extensively in communication
systems and for battery charging and electroplating operations. The generation
of electromotive force is described in detail in our ELECTRICITY 1
Guide.
DC GENERATOR COMPONENTS
The essential parts of a dc generator are shown in figures 1—1 and 1—2.
The member that spins is called the rotor. The rotor is a cylindrical,
laminated iron core that is mechanically coupled to the drive shaft of
the generator. An armature winding is embedded in the slots on the surface
of the rotor. The armature windings have voltage induced into them as it
spins past the field poles. The windings are actually coils of wire in
a series of loops that terminate at the copper segments of the commutator.
A commutator consists of a series of copper segments which are insulated
from one another and the shaft. The commutator turns with the shaft and
the armature windings. The commutator is used to change the ac voltage
induced in the armature windings to dc voltage at the generator output
terminals. Carbon brushes pressing against the commutator segments connect
the current to the external load circuit.

Ill. 1—2 Cutaway view of a direct-current generator:
reaction-type brush holders; field coils; frame yoke; outer bearing cap
inspection plates; armature coils; armature tooth laminations; field poles;
commutator end brackets

Ill. 1—3 “Motor action” opposing generator driving force
The armature windings generate voltage by cutting a magnetic field as
the armature rotates. This magnetic field is established by electromagnets
mounted around the periphery of the generator. The electromagnets, called
field poles, are arranged in a definite sequence of magnetic polarity;
that is, each pole has a magnetic polarity opposite to that of the field
poles adjacent to it. Electrical current for the generator field circuit
is usually obtained from the generator itself.
When a generator feeds a load circuit, current passing through the armature
sets up a magnetic field around the armature. This field reacts with the
main field flux. The result is a force that attempts to turn the armature
in a direction opposite to that in which it is being driven (figure 1—3.)
(This effect is known as the motor effect of generators). The force of
this reaction is proportional to the current in the armature and accounts
for the fact that more mechanical power is needed to drive a generator
when electrical energy is taken from it.
Armature Reaction
The armature field flux also reacts against the main field flux and tends
to distort it. One result of this undesirable condition, known as armature
reaction, is excessive sparking at the brushes on the commutator. To counteract
this effect, commutating poles are often inserted between the main field
poles, as shown in figure 1—1. These commutating poles, also called inter-poles,
are energized by windings placed in series with the output (load) circuit
of the generator. Because of this arrangement, armature reaction, which
tends to increase with load current, is counteracted by the effects of
the load current passing through the interpoles.
Armature reaction, appearing as excessive brush sparking under load, also
can be partially corrected by shifting the brushes from their neutral position
in the direction of rotation. Large dc generators have the brushes assembled
so that they can be shifted to the position of minimum sparking. When the
brushes are not movable, the generator manufacturer inserts other design
features to minimize the effects of armature reaction.
Brush Polarity
The output terminals of a generator, as with other dc power units, have
electrical polarity. In the case of generators, the term brush polarity
is used to distinguish between the electrical polarity of the brushes,
either positive or negative, and the magnetic polarity either North or
South, of the field poles.
Brush polarity markings are often omitted, but the electrician can easily
determine electrical polarity by connecting a voltmeter across the output
leads of the generator. Many automotive and aircraft generators are constructed
with either the positive or negative brushes grounded to the frame of the
generator. It is very important to maintain the polarity as specified by
the manufacturer. Additional information on brush polarity will be given
after the effects of residual magnetism in the field circuit are considered.
Field Supply
The magnetic field of a generator is established by a set of electromagnets
(field poles). The current required by the field circuit may be supplied
from a separate dc sup ply. If this is the case, the generator is said
to have a separately excited field. The majority of generators, however,
are self-excited and the current for the field is supplied by the generator
itself.

Ill. 1—4 Separate excitation; Ill. 1—5 Self-excitation
Figure 1—4 illustrates a separately excited dc generator with the field
circuit supplied from batteries. A self-excited shunt generator is shown
in figure 1—5. Note that the field circuit is connected in parallel with
the armature and that a small part of the generator out put is diverted
to the field circuit, in order to “excite” or energize the field poles.
OUTPUT VOLTAGE CONTROL
Since the induced voltage depends on the rate at which the magnetic lines
of force per second are cut, it is possible to vary the output voltage
by controlling either the speed of the prime mover or the strength of the
magnetic field. In all but a few instances, the output voltage is controlled
by varying the field current with a rheostat in the field circuit.
The flux density in the field poles depends on the field current. As a
result, the volt age output of the generator continues to increase with
an increase of field current to a point where saturation of the field poles
occurs. Any additional increase in voltage output after this point must
be obtained by an increase in speed.
GENERATOR RATINGS
Generator ratings as specified by the manufacturer are usually found on
the name plate of the machine. The manufacturer generally specifies the
kilowatt output, current, terminal voltage, and speed of the generator.
For large generators, the ambient temperature is also given.
ROTATION
A separately-excited generator develops voltage for either direction of
rotation. This is not true, however, for self-excited units; they develop
voltage in one direction only. (See explanation in unit 3.) The standard
direction of rotation for dc generators is clock wise when looking at the
end of the generator opposite the drive shaft (this is usually the commutator
end).
REGULATION
The voltage regulation of a generator is one of its important characteristics.
Different types of generators have different voltage regulation characteristics.
Figure 1—6 shows the action of the voltage at the terminals of a generator
for different values of the load current. The drop in terminal voltage
is caused by the loss in voltage (1) across the internal resistance of
the armature circuit including the brush contacts, and (2) due to armature
reaction. The curve at (a) is the normal curve for a shunt generator. An
ideal condition is shown in (b) where the voltage remains constant with
load current. Curve (c) illustrates a generator with very poor regulation
in that the output voltage drops off considerably as the load current increases.
A rising characteristic, curve (d), is obtained by using a cumulative compound-wound
generator (unit 4).
SUMMARY
DC generators are used to provide direct current to specific loads. The
armature, mounted on the rotor, is driven through the magnetic fields developed
by the electromagnetic poles. AC voltage is actually induced into the armature,
then mechanically rectified …
[restore p. 6-8]
|