|
ENGINE-DRIVEN GENERATING SETS OBJECTIVES:
After studying this unit, the learner should be able to:
• describe the purposes of engine-driven generating sets.
• list the advantages of using cogenerating sets.
• describe the operation of an automatic transfer switch.
• connect an automatic transfer switch.
• state National Electrical Code requirements.
ENGINE-DRIVEN GENERATING SETS
Diesel, gasoline, or natural gas engine-driven generators are most commonly
used to provide another source of emergency or standby power when the normal
utility power fails. Turbine power generator sets are also used in this
application.
Sturdy, diesel-engine powered generators may lose some of their popularity
in the remote, area-sites power systems. The use of hybrid systems using
natural energy, such as the wind and the sun, are growing dramatically.
So, although diesel generators will not become obsolete for remote site
electrical power, a need will exist for a back-up source, as the generator
changes its role from a primary energy source to part of a combined source.
Most engine-driven generator sets are rated from a few hundred watts to
several hundred kilowatts, although units rated as high as 3,000 kW have
been successfully applied. Multiple units, with some working in parallel,
are becoming more commonly used to increase generating capacity. Controls
may be manual, remote, or automatic, depending upon their application.
Transfer Switches
Switches are required to transfer, or reconnect, the load from a preferred
or normal electric power supply to the emergency power supply from the
generator set. This is done either manually or automatically. The manual
method uses a double-throw switch, operated by hand, to transfer the load
from the normal to the emergency power after the standby plant is already
running. An automatic transfer switch (fig. 12-1) usually starts and
stops the standby power plant, and transfers the load by relays without
requiring the attention of an operator.

Fig. 12-1 A sophisticated, 600-ampere automatic transfer switch with accessory
group control panel at right. Note the cable terminal Jugs at top and bottom.
(Courtesy of Automatic Switch Co.)
An elementary diagram of a typical automatic transfer switch is
shown in fig. 12-2. (The figure does not include the engine starting controls
and other controls.)

Fig. 12-2 Elementary diagram of an automatic transter switch
When the normal supply on the left side is energized, current
flows from L1 through TD (time-delay coil) and back to L2. After a predetermined
setting of time delay in closing contact, relay R coil becomes energized.
Contact R then closes, and energizes the N coil. Power contacts N then
close, supplying the load from the normal or preferred source. When
R coil is energized, it also opens the normally closed R contact interlock
in the E coil emergency circuit. This safe action insures that each
power supply operates independently of the other.
When the normal power fails, all coils on the left, or normal
supply side, become de-energized. Relay contact R drops to its normally
closed position in the E (emergency coil) circuit. Coil E is then energized,
thereby closing the E power contacts feeding the load from an emergency
electrical supply.
The time delay action helps to insure that the normal service does
not supply the load intermittently with the emergency supply. In other
words, the load will wait a preset time until the normal supply is
firmly established before it is reconnected to it.
EMERGENCY SYSTEMS
Applicable National Electrical Code (NEC) and local code rules are
considered when an on-site generator is selected. These differ, depending
on whether the generating set is to function as a power source in a
health care facility, such as a hospital, a standby power system, or
as an emergency system.
On site generator systems generally are installed wherever great
numbers of people gather, and where artificial lighting is required, such
as in hotels, theatres, sports arenas, hospitals, and similar institutions.
In addition to lighting, emergency systems supply loads which are essential
to life and safety. Such installations include fire pumps, ventilation,
refrigeration, and signaling systems when essential to maintain life.
[ Refer to Article 700 of the National Electrical Code (NEC).]
Standby Power Generation Systems
Standby power generation systems include alternate power systems for
applications such as heating, refrigeration, data processing, or communication
systems where interruption of normal power would cause human discomfort
or damage to the product in manu facture, but where life safety does
not depend on the system. (Refer to Article 702 of the NEC.)
UNINTERRUPTIBLE POWER SYSTEMS
Uninterruptible power systems (UPS) are used as power systems to supply
critical electronic equipment that includes electronic computer and data
processing equipment as described in Article 645 of the National Electrical
Code.

Fig. 12-3 Control panels for uninterruptable power supplies

Fig. 12-4 1.8 million watt diesel-driven emergency power generating
system (Photo Courtesy of Onan Corporation, A Subsidiary of McGraw-Edison)
The basic system includes an electronic section that takes the normal
line power and converts it to dc power to act as a battery charger. The
system has a set of batteries that are constantly being charged. These
batteries are also connected to an electronic inverter system to change
the dc battery power back to normal ac power to supply an ac load. The
concept is to constantly have battery power connected and available to
provide a standard level of power to the electronic equipment at all times.
The battery system is sized to pro vide the needed volt-amp capacity to
the system for a specified period of time. The UPS system also provides
protection from low voltage conditions or brown-outs and protection from
momentary surges or power delivery failures. These systems can provide
continuous, filtered and regulated power to sensitive equipment. The systems
themselves can be sized to provide for a few computers or to supply hundreds
of computers or other essential equipment. Fig. 12-3 shows the variety
of sizes that may be used. If the UPS system is large and requires a bank
of batteries to supply the uninterruptible power, the batteries must be
installed according to the National Electrical Code.
Health Care Facilities
Health care facilities are governed by several National Electrical Code
rules concerning power sources, emergency systems, and essential electrical
systems. In particular, refer to NEC Article 517.
Fig. 12-4 shows a diesel-driven emergency power system consisting of four
450-kW electric generating sets. The system is electronically synchronized
to deliver 1.8 million watts of emergency power for a hospital. Each unit
can also be operated independently of the other units.
LEGALLY REQUIRED STANDBY SYSTEMS
NEC Article 701 states that legally required standby power systems are
those systems required by municipal, state, federal, or other codes or
a government agency having jurisdiction. In the event of failure of the
normal power source, these systems are intended to take over automatically.
Legally required standby power systems are installed to serve such loads
as communication systems, ventilation and smoke removal systems, sewage
disposal, rescue and fire fighting equipment, among others. These are installations
that must be installed within the guidelines of the authority having jurisdiction.
COGENERATING PLANTS
Cogeneration is being used to help reduce the cost of purchasing power
from a local utility. Many forms of cogeneration are available. Some use
the concept of recovering the energy from some manufacturing process to
drive electrical generators on site.
Some cogenerating plants are diesel-powered electric generators which
are designed to recapture and use the waste heat both from their exhaust
and cooling systems (fig. 12-5).
Although cogenerating plants are not a new concept, they are now being
used to combat the energy shortage and the rising prices charged by public
utility companies for power generation. About a dozen of the nation’s largest
manufacturers of diesel engines have set out to provide competition for
the foremost electric utility companies in the United States, As a result,
these manufacturers have been concentrating on selling cogenerating plants.
Equipped with cogenerating plants, energy users need no longer rely on
public utilities, due to the fact that not only can they make their own
electricity, at a lower cost, but provide heating and cooling for their
buildings, as well.
Various technical methods have been devised for using cogenerating plants.
How ever, all of them capitalize on the fact that the generation of electricity
wastes about twice as much energy in the form of heat as that amount of
energy which can be generated as electricity. Steam heat, as a waste by-product
of manufacturing processes, is now harnessed and used to turn steam turbine
electric alternators. This electricity, when not needed, is sold to the
public utility which services the plant.
The energy-saving application of cogeneration should result in greater
demands for electrical work and, thus, more jobs for electricians. It also
should create a particular need for power generator operators having the
skills to install, operate, and maintain cogenerating equipment.
SUMMARY
When the normal source of electrical power is interrupted, business and
industry may require immediate restoration of power to continue critical
operations or life support and safety. There are several methods used to
provide power, and different criteria are used to determine which system
is required or the best to use. Use the National Electrical Code to determine
which system is appropriate to install. In addition to required systems,
there is the potential for large power consumers to generate their own
power on-site as part of a money-saving feature. This cogeneration is often
used to reduce the amount of energy purchased from the utility or to supply
the high energy peaks in a facility to save on the demand charges from
the utility.

Fig. 12-5 A diesel-powered standby/peak-shaving plant (Photo
Courtesy of Cummins Engine Corp.)
REVIEW QUIZ:
Select the correct answer for each of the following statements.
1. Engine-driven generating sets are used for:
a. emergency systems.
b. standby power.
c. cogenerating plants.
d. all of these.
2. With an automatic transfer switch, as shown in fig. 12-1, how does
the emergency supply feed the load when power fails?
a. TD energizes R.
b. Normally open contact R opens.
c. Normally closed contact R closes.
d. Power contacts N close.
3, Generating capacities may be increased by using
a. parallel multiple units.
b. series multiple units.
c. turbines.
d. diesels.
4. Cogenerating sets are used
a. to supply emergency power.
b. to supply standby power.
c. to conserve energy.
d. in health care facilities.
5. Electrical capacity is gained with several small generating sets by
a. paralleling machines on the line.
b. reducing the load.
c. placing machines on the line in series.
d. none of these. |