|
OBJECTIVES
After studying this unit, the learner/learner will be able to…
• state the conditions which require that two alternators be paralleled.
• describe the use of synchronizing lamps in the three dark method and
the two bright, one dark method of synchronizing alternators.
• demonstrate the procedure for paralleling two three-phase alternators.
• state the effect of changes in field excitation and speed on the division
of load between paralleled alternators.
• describe “reverse power.”
WHEN TO PARALLEL ALTERNATORS
Alternators are paralleled for the same reasons that make it necessary
to parallel dc generators. Two alternators are paralleled whenever the
power demand of the load circuit is greater than the power output of a
single alternator.
When dc generators are paralleled, it is necessary to match the output
voltage and electrical polarity of the machines with the voltage and polarity
of the line. The same matching is required when alternators are paralleled.
However, the matching of alternator polarity to that of the line presents
problems not encountered when matching dc generator and line polarities.
The output voltage of an alternator is continuously changing in both magnitude
and polarity at a definite frequency. Thus, when two alternators are paralleled,
not only must the rate of the rise and fall of voltage in both alternators
be equal, but the rise and fall of voltage in one machine must be exactly
in step with the rise and fall of voltage in the other machine. When two
alternators are in step, they are said to be in synchronism. Alternators
cannot be paralleled until their voltages, frequencies, and instantaneous
polarities are exactly equal.
Fig. 13-1 shows a comparison of the voltage curves of one of the phases
of two three-phase generators operating independently but at different
speeds. The voltage curves must be in synchronism before paralleling machines.

Fig. 13-1 Periodic time relationship of the out-of-phase voltages
of two generators running at different speeds
The output voltage of an alternator can be controlled by varying the strength
of the direct current in the field circuit of the alternator. A field rheostat
can be used to vary the dc current. Since the frequency of an alternator
varies directly with speed changes, it is necessary to be able to control
the speed of at least one alternator in an installation containing two
machines.
ACHIEVING SYNCHRONIZATION
To synchronize AC generators, several important factors must be checked.
1. The phase rotation of both generator systems must be the same. Check
this with lights as described later or use a phase rotation meter to determine
ABC or ACB rotation.
2. The AC voltages of both generators should be equal. In practice the
voltage of the on-coming generator is usually 1-2 volts higher than that
of the other operating generator.
3. The frequencies of the on-coming generators must match when synchronized.
In practice the frequency of the on-coming generator is 1-2 hertz higher
than that of the on-line generator. This can be observed with lights or
by using a synchroscope.
The speed and output voltage of the on-coming generator are slightly higher
to pre vent it from becoming a load to the system when it is connected.
Two methods of synchronization using lights are described below.
Three Dark Method
The following describes the method of synchronizing two alternators using
the three-dark method.
Fig. 13-2 illustrates a circuit used to parallel two three-phase alternators.
Alternator G2 is connected to the load circuit. Alternator G1 is to be
paralleled with alternator G2 Three lamps rated at double the output voltage
to the load are connected between alternator G2 and the load circuit as
shown. When both machines are operating, one of two effects will be observed:
1. The three lamps will light and go out in unison at a rate which depends
on the difference in frequency between the two alternators.
2. The three lamps will light and go out at a rate which depends on the
difference in frequency between the two machines, but not in unison. In
this case, the machines are not connected in the proper phase sequence
and are said to be out of phase. To correct this, it is necessary to interchange
any two leads to alternator G1. The machines are not paralleled until all
lamps light and go out in unison. The lamp method is shown for greater
simplicity of operation.
By making slight adjustments in the speed of alternator G1 the frequency
of the machines can be equalized so that the synchronizing lamps will light
and go out at the lowest possible rate. When the three lamps are out, the
instantaneous electrical polarity of the three leads from G1 is the same
as that of G2 At this instant, the voltage of G1 is equal to and in phase
with that of G2 Now the paralleling switch can be closed so that both alternators
supply power to the load. The two alternators are in synchronism, according
to the three dark method.

Fig. 13-2 Synchronization of alternators
The three dark method has certain disadvantages and is seldom used. A
large voltage may be present across an incandescent lamp even though it
is dark (burned out). As a result, it is possible to close the paralleling
connection while there is still a large voltage and phase difference between
the machines. For small capacity machines operating at low speed, the phase
difference may not affect the operation of the machines. However, when
large capacity units having low armature reactance operate at high speed,
a considerable amount of damage may result if there is a large phase difference
and an attempt is made to parallel the units.
Two Bright, One Dark Method
Another method of synchronizing alternators is the two bright, one dark
method. In this method, any two connections from the synchronizing lamps
are crossed after the alternators are connected and tested for the proper
phase rotation. (The alternators are tested by the three dark method.)
Fig. 13-3A shows the connections for establishing the proper phase rotation
by the three dark method. Fig. 13-3B shows the lamp connections required
to synchronize the alternator by the two bright, one dark method.
When the alternators are synchronized, lamps 1 and 2 are bright and lamp
3 is dark. Since two of the lamps are becoming brighter as one is dimming,
it is easier to determine the moment when the paralleling switch can be
closed. Furthermore, by observing the sequence of lamp brightness, it is
possible to tell whether the speed of the alternator being synchronized
is too slow or too fast.

Fig. 13-3 Methods of synchronizing alternators. (A) The Three-Dark
Method; (B) Two-Bright, One-Dark Method
Synchroscope
A synchroscope is recommended for synchronizing two alternators
since it shows very accurately the exact instant of synchronism (fig. 13-4).
The pointer rotates clock wise when an alternator is running fast and counterclockwise
when an alternator is running slow. When the pointer is stationary, pointing
upward, the alternators are synchronized. The synchroscope is connected
across one phase only. For this reason it cannot be used safely until the
alternators have been tested and connected together for the proper phase
rotation. Synchronizing lamps or other means must be used to determine
the phase rotation. In commercial applications, the alternator connections
to a three-phase bus through a paralleling switch are permanent. This means
that tests for phase rotation are not necessary. As a result, a synchroscope
is the only instrument required to bring the machines into synchronization
and thus parallel them; however, a set of lights is often used as a double-check
system.

Fig. 13-4 A) Diagram of synchroscope connection B) Photo of synchroscope
meter face and synchronizing lights
Prime Movers
In industrial applications, alternators are driven by various types of
prime movers such as steam turbines, water turbines, and internal combustion
engines. For applications on ships, alternators often are driven by dc
motors. Regardless of how alternators are driven, speed variation is a
factor in paralleling the machines. Thus, the electrician should have knowledge
of speed governors and other speed regulating devices. This text, how ever,
does not detail the operation of these mechanical devices.
PARALLELING ALTERNATORS
Since apprentices are likely to be required to parallel alternators driven
by dc motors sometime in their instruction, the following steps outline
the procedure for paralleling these machines. Fig. 13-5 illustrates a typical
circuit for paralleling two three-phase alternators.

Fig. 13-5 Parallel operation of alternators
Procedure
1. Set the field rheostat R2 of alternator G2 to the maximum resistance
position.
2. Knowing the number of field poles in alternator G2 determine the speed
required to generate the desired frequency.
3. Energize the prime mover to bring alternator G2 up to the required
speed.
4. Set Switch S to read the ac voltage across one phase of G2 Adjust field
rheostat R2 until the output voltage is equal to the rated voltage of the
load circuit.
5. Close the load switch and switch S4 to feed the load circuit. Readjust
the speed of the prime mover to maintain the predetermined speed required
for the desired frequency.
6. Readjust R2 to obtain the rated ac voltage of the load circuit.
7. Energize the prime mover to drive the second alternator, G1 Adjust
the speed of the alternator to the approximate value required to match
the frequencies of the alternators.
8. Set switch S3 to measure the ac voltage across one phase of G1. Adjust
field rheostat R1 until the ac voltage is equal at either position of switch
S3. The voltage output of both alternators is now equal.
9. Phase Rotation
With paralleling switch S2 open, close switch S1.
The three sets of lamps across the terminals of the open switch will respond
in one of two ways:
a. The three lamps will brighten and then dim in unison.
b. Two lamps will brighten in unison as the remaining lamp dims. Then
the two bright lamps will dim as the dark lamp brightens.
10. If the lamps respond as in 9a, the alternators are connected for the
proper phase rotation. The operator then may proceed to the next step in
synchronizing the alternators.
11. If the lamps respond as in 9b, the alternators are not in the proper
phase rotation. To correct the condition, interchange any two alternator
leads at the terminals of switch S2. All three lamps should dim together
and brighten together. No attempt to parallel the alternators should be
made until the lamps respond in this manner.
12. The three lamp sets will flicker (dim and brighten) at a rate equal
to the frequency difference between the two alternators. Adjust the speed
control of prime mover M1 to make the lamps flicker at the lowest possible
rate.
13. Interchange two lamp set leads (not alternator leads) at the terminals
of switch S2 so that the alternators can be synchronized using the two
bright, one dark method.
14. Again adjust the field rheostat of alternator G1 until both alternators
have the same output voltage as measured at either position of the voltmeter
switch S3.
15. With one hand on switch S2 watch the lamps. Close the switch at the
exact instant that two lamps are at their brightest and the other lamp
is out. This operation shunts out the synchronizing lamps and parallels
the alternators.
16. Ammeters I1 and I2 indicate the amount of load current carried by
each alternator. If the load circuit has a unity power factor, then the
sum of the ammeter readings should equal the reading of the ammeter in
the load circuit.
17. Note that a change in the field excitation of either alternator does
not appreciably change the amount of current supplied to the system. Such
a change in field excitation does, however, affect the power factor of
the specific alternator. The field rheostat of each machine should be adjusted
to the highest power factor as indicated by the lowest value of current
from the individual machine. Increasing or decreasing the mechanical power
to either alternator will increase or decrease the load current of that
machine. As a result, the division of the load between the alternators
can be changed by slight changes in the alternator speed.
Speed vs. Load Characteristics
Two alternators operating in parallel must have the same frequency and
the same terminal voltage. In addition, the prime movers of the parallel
alternators must have similar drooping speed load characteristics. For
steam-, diesel-, water-, or gas-driven prime movers, the speed load characteristic
depends on adjustments of a mechanical speed control governor. These adjustments
determine the division of load for two alternators operating in parallel.
For this reason, the kilowatt load delivered by two alternators in parallel
cannot be divided in any desired proportion by varying the dc field excitation
of either machine.
Two alternators properly connected in parallel will operate in stable
equilibrium. If one alternator attempts to pull out of synchronism, a current
is created which circulates between both alternators. This current increases
the speed of the lagging machine and retards the leading machine thus preventing
the machines from pulling out of synchronism.
REVERSE POWER
If, for any reason, one machine is allowed to slow to a point where the
other machine is taking all the electrical load, the zero load generator
then goes to a negative value or “reverse power.” This generator has now
become a motor. This situation is of particular concern where the machine’s
protective scheme has not been designed to operate properly in the motoring
situation. In such conditions reverse-current relays are usually employed
to trip the generator on detection of reverse power flow.
Results of Motorization of a Generator
If a generator loses prime mover power, it acts as a motor with a dc field
on the rotor. The dc field will cause the rotor to try and follow the ac
field in the same direction as before. If the mechanical drag on the rotor
is heavy, it will fall behind and “slip poles,” inducing a large voltage
into the rotor; this can cause insulation breakdown of the windings, flashover
at the brushes, and violent shaking of the generator mountings.
If a generator loses dc excitation to the rotor it will not generate,
but the prime mover power will still turn the rotor. Now the generator
acts as a motor running at no load.
SUMMARY
In many cases the parallel operation of alternators is essential to provide
needed power and to maintain electrical power during peak loads or when
removing an alternator from service for maintenance. The requirements for
paralleling are: (1) the phase rotation of the generated voltage must be
the same, (2) the voltage at the paralleling point must be the same, and
(3) the frequencies of the generators must match. Lamps and synchroscopes
are often used to aid in the paralleling procedure. If a generator loses
output power, it must be removed from the electrical power system or serious
consequences could result.
REVIEW QUIZ
A. Select the correct answer for each of the following statements.
1. Two alternators are paralleled___
a. so that one is not overworked.
b. because of a rising load demand.
c. to ease the workload.
d. because of the declining load demand.
2. To parallel alternators, it is necessary to match___
a. voltages.
b. frequencies.
c. voltages and frequencies.
d. voltages, frequencies, and instantaneous polarities.
3. The output voltage of an alternator is controlled by___
a. adjusting the prime mover.
b. adjusting the direct current of the field circuit.
c. synchronizing lamps.
d. a synchroscope.
4. Alternators should not be paralleled unless the synchronizing lamps
are lighting and dimming ___
a. in rotation.
b. in reverse rotation.
c. in unison.
d. alternately.
5. Three lights flashing rapidly in unison while paralleling alternators
means that ____
a. the machines are not polarized.
b. the phase sequences are wrong.
c. the paralleling switch should be closed.
d. the frequencies differ by a large amount.
6. The three dark method of synchronizing alternators has the disadvantage
that _________
a. the lamps may burn out.
b. an undetected voltage may be present at the lamps.
c. the light is more difficult to see.
d. an undetected current may be present through the lamps.
7. The most reliable method of synchronizing alternators is to use __________
a. a synchroscope.
b. the three dark method.
c. the three light method.
d. the two bright, one dark method.
8. If a synchroscope is rotating clockwise, the ___
a. alternators are ready to parallel.
b. alternator being synchronized is too slow.
c. alternator being synchronized is too fast.
d. machines have not been polarized.
9. When the pointer of a synchroscope is stationary and points upward
during the paralleling operation, the ____
a. alternators are in synchronism.
b. alternators are not in synchronism.
c. incoming alternator frequency is too slow.
d. incoming alternator frequency is too fast.
10. The division of load between alternators operating in parallel is
accomplished by changing the
a. field excitation.
b. speed of the prime movers.
c. power factor of the load.
d. machine characteristics.
B. Insert the word or phrase to complete each of the following statements.
1. To operate satisfactorily in parallel, two alternators must have the
same___, the same frequency, and the same___.
2. Two alternators are to be connected in parallel. The best instrument
to use for synchronizing them is a(an)_____.
3. An alternator is connected to a live three-phase bus. Using the three
dark method, a lamp is connected in series with each lead. The lamps brighten
and dim in unison. This proves that the alternators have the proper _______________________
rotation.
4. In question 3, the switch shorting the three series lamps should be
closed at the instant the lamps are____________________________
5. Two 208-volt alternators are to be paralleled. The synchronizing lamps
should be rated at ______________________________
6. The output voltage of alternators operating in parallel is equalized
by adjusting their___________.
7. The load on an alternator operating in parallel with another alternator
may be increased by decreasing the spring tension of its speed ___________.
8. The division of load between two alternators operating in parallel
can be changed by adjusting the____________.
9. Two alternators, A and B, are being synchronized for parallel operation.
Alternator A is operating at a frequency of 60 hertz. The synchronizing
lamps are flickering twice a second. The frequency of alternator B is________
hertz or _________ hertz.
10. Synchronizing lamps and a synchroscope are being used to parallel
two alternators. Just before the moment the alternators are paralleled,
there is no visible light from the lamps but the synchroscope is rotating
slowly. In this case, the _________ method should be used to indicate when
the paralleling switches should be thrown because_______. |