OBJECTIVES
After studying this unit, the learner/learner will be able to
• diagram the simple wye connection of three transformers.
• list the steps in the procedure for the proper connection and checking
of the primary and secondary windings of three single-phase transformers
connected in a wye arrangement.
• state the voltage and current relationships for wye-connected, single-phase
transformers.
• describe how the grounded neutral of a three-phase, four-wire, wye-connected
transformer bank maintains a balanced voltage across the windings.
• state how the kVA capacity of a wye-wye-connected transformer bank is
obtained.
Voltage transformation on three-phase systems can also be accomplished using
wye-connected single-phase transformers (figure 20-1). To avoid errors when
wye connecting single-phase transformers, a systematic method of making the
connections should be used. The electrician should know the basic voltage
and current relation ships common to this type of connection.

Fig. 20-1: Single-phase, round coil transformer (Courtesy of McGraw-Edison
Company, Power Systems Division)
FUNDAMENTAL WYE CONNECTION
A simple wye system is formed by arranging three single-phase coils so that
one end of each coil is connected at a common point (figure 20-2). Note that
when these connections are shown in a schematic diagram, they resemble the
letter Y (written wye). This configuration is also known as a “star” connection.

Fig. 20-2: Simple wye connection
As an example, figure 20-3 shows the wye-wye connection of three single-phase
transformers to step down a three-phase input of 4,152 volts to a three-phase
output of 208 volts: Each transformer must be voltage rated for its applications.
The H leads or primary winding ends of the transformer are connected together.
The beginning or H lead of each transformer is connected to one of the three
line leads.

Fig. 20-3 Elementary diagram of wye-wye-connected transformer bank
Two of the primary windings are connected across each pair of line wires.
Each transformer primary winding is rated at 2,400 volts and the actual voltage
applied to each of these three windings is 2,400 volts. Note that the potential
across each pair of line leads is 4,152 volts and not the 2,400 + 2,400 =
4,800 volts which might be expected because of the connection of two coils.
The value of 4,152 volts arises from the fact that the voltage applied to
each of the primary windings is out of phase with the voltages applied to
the other primary windings. As a result, these winding voltages cannot be
added directly to obtain the line voltage. Rather, the line voltage is equal
to 1.73 x coil voltage. Therefore, for the input side of the transformer
bank in figure 20-3 where the voltage on the primary winding of each transformer
is 2,400 volts, the line voltage is
Line voltage = 1.73 x coil voltage
= 1.73 x 2,400
= 4,152 volts
If the coil voltage must be checked and the line voltage is known, the same
value of 1.73 can be used. For this situation, the coil voltage is obtained
by dividing the line volt age by 1.73.
Coil voltage = line voltage/1.73
= 4,152/1.73
= 2,400 volts
Thus, wye-connected transformer banks have only 58 percent (1/1.73 = 0.58)
of the line voltage applied to each of the three transformer windings. After
the high-voltage primary connections are completed, the three-phase, 4,152-volt
input may be energized. It is not necessary to make any polarity tests on
the input (primary) side.
POLARITY TEST FOR UNMARKED AND NEW TRANSFORMERS
The next step is to connect the low-voltage output (secondary) windings
in wye (figure 20-3). The following procedure must be followed when making
the secondary connections.
1. Check to see that the voltage output of each of the three transformers
is 120 volts. (for this example)
Caution: De-energize all circuits before making connections.
2. Connect the X ends of two low-voltage secondary windings.
Figure 20-4 illustrates two secondary coils with the X2 coil ends connected.
The voltage across the open ends should be 1.73 x 120 = 208 volts. However,
if the leads on one transformer are reversed, the voltage across the open
ends will be 120 volts.

Fig. 20-4 Two transformers correctly connected
Figure 20-5 illustrates two transformers connected incorrectly. The voltage
across the open ends is only 120 volts. If the leads of transformer 2 are
reversed, the connections will be correct and the voltage across the open
ends will be 208 volts.
Fig. 20-5 (above right) Two transformers incorrectly connected
3. Connect the X lead of the low-voltage secondary winding of transformer
3 with the X leads of the other two transformers.
The proper wye connection of the low-voltage secondary windings of the three
single-phase transformers is shown in figure 20-6. The voltage across each
pair of open ends should be 1,73 x 120 = 208 volts. If the voltage across
the open ends is correct, then the line leads feeding to the three-phase,
208-volt secondary system may be connected.

Fig. 20-6: Three single-phase transformers properly connected in a wye
arrangement

Fig. 20-7: Three single-phase transformers properly connected to the
line
Figure 20-7 illustrates the secondary windings connected in wye with the
line leads properly connected. Since each of the line wires is connected
in series with one of the transformer windings, the current in each winding
is equal to its respective line current.
Whenever single-phase transformers are connected in wye, the following current
and voltage relationships are true.
1. The line voltage is equal to 1.73 x winding voltage.
2. The line current and the winding current are equal.
The wye-wye connection scheme is satisfactory as long as the load on the
secondary side is balanced. For example, this type of connection can be used
if the load consists only of a three-phase motor load where the load currents
are balanced. The wye-wye connection is unsatisfactory where the secondary
load becomes greatly unbalanced. An unbalanced load results in a serious
unbalance in the three output voltages of the transformer bank.
THREE-PHASE, FOUR-WIRE WYE CONNECTION
Voltage unbalancing in the secondary of the transformer bank can be nearly
eliminated if a fourth wire (neutral wire) is used. This neutral wire connects
between the source and the neutral point on the primary side of the transformer
bank.
In the connection diagram (figure 20-8) a three phase, four-wire system
is used to feed the three-phase, high-voltage input to the transformer bank.
The grounded neutral wire is connected to the common point where all three
high-voltage primary winding ends or H leads connect. The voltage from the
neutral to any one of the three line wires is 2,400 volts. Each high-voltage
winding is connected between the neutral and one of the three line loads.
Therefore, 2,400 volts is applied to each of the three high-voltage primary
windings. The voltage across the three line leads is 1.73 x 2,400 volts or
4,152 volts.
 Fig. 20-8.
The neutral wire maintains a relatively constant voltage across each of
the high-voltage primary windings even though the load is unbalanced. Because
the neutral wire is grounded, it helps protect the three high-voltage primary
windings from lightning surges.
A three-phase, four-wire system also feeds from the low-voltage secondary
side of the transformer bank to the load. Each low-voltage secondary winding
is connected between the secondary grounded neutral and one of the three
line leads. As on the primary side, the grounded neutral helps protect the
low-voltage secondary windings from lightning surges.
The voltage output of each secondary winding is 120 volts. The voltage between
the neutral and any one of the three line leads on the secondary side is
120 volts, as shown in figure 20-8. The voltage across the three line leads
is 1.73 x 120 = 208 volts. Thus, by using a three-phase, four-wire secondary,
two voltages are available for different types of loads: 208 volts, three
phase, for industrial power loads such as three-phase motors, and 120 volts,
single phase, for lighting loads.
Many single-phase transformers are designed so that the low-voltage side
consists of two 120-volt windings. These two windings can be connected in
series for 240 volts or in parallel for 120 volts.
Figure 20-9 shows three single-phase transformers connected as a wye-wye
bank. Each transformer has two 120-volt, low-voltage windings. For each single-phase
transformer, the low-voltage coils are connected in parallel to give a voltage
output of 120 volts. Note in figure 20-9 that the secondary output windings
of the three transformers are connected in wye. This three-phase, four-wire
secondary system provides two different types of service:
- three-phase, 208-volt service for motor loads Fig. 20-8 Wye-wye transformer
bank with neutral connection
- single-phase, 120-volt service for lighting loads

Fig. 20-9 Wye-wye transformer bank connections
The 120/208-volt wye system is commonly used in schools, stores, and offices.
Another popular system for large installations is the 480/277-volt wye system.
Some applications of this system include:
• motors connected to 480 volts (phase to phase);
• fluorescent lighting fixtures connected to 277 volts (phase to neutral);
• 120-volt outlets, incandescent lamps, and appliances connected to 120-volt
circuits supplied from single-phase, 480//120/240-volt transformers or three-phase,
480//208Y/120-volt transformers. These separate transformers are connected
to the 480-volt feeders for the primary source.
Three single-phase transformers of the same kilovolt-ampere capacity are
used in most wye-wye-connected transformer banks. The total kilovolt-ampere
capacity of a wye-wye-connected bank is found by adding the individual kVA
ratings of the transformer. If each transformer is rated at 25 kVA, then
the total kVA is 25 + 25 + 25 = 75 kVA.
If one transformer becomes defective, it must be replaced before the transformer
bank can be reenergized. A wye-wye-connected transformer bank cannot be reconnected
in an emergency situation using only two single-phase transformers, such
as in the open-delta system.
SUMMARY
Single-phase transformers can be connected in a wye or star pattern to achieve
the desired three-phase and single-phase voltages required by many commercial
customers. By connecting the single phases in a wye pattern, the line voltages
can be increased by a factor of 1.73 times the coil voltage. This increased
level of voltage is often desirable to reduce the line current drawn by a
load. By increasing the voltage, the current will be less for a specific
watt load. Be sure to check all transformer polarities and check the final
connections for a solid ground if using the three-phase, four-wire wye-connected
system.
QUIZ
1. Draw a connection diagram for three wye-wye-connected single-phase transformers.
This transformer bank is used to step down 2,400/4,152 volts on a three-phase,
four-wire primary to 120/208 volts on a three-phase, four-wire secondary.
Each transformer is rated at 20 kVA, with 2,400 volts on the high-voltage
winding and 120 volts on the low-voltage winding. Mark leads H X and so forth;
show all voltages.
2. What is the total kVA capacity of the wye-wye transformer bank in question
1?
3. A grounded neutral wire is used with a wye-wye-connected transformer
bank for what purpose?
4. The three-phase, four-wire secondary output of a wye-connected transformer
bank can be used for what two types of load?
a.
b.
5. List the steps that may be used in connecting three single-phase transformers
in wye.
a.
b.
c.
6. When single-phase transformers are connected in a three-phase Y,
a. what is the line current compared with the phase-winding current?
b. what is the line voltage compared with the phase-winding voltage? |