|
OBJECTIVES
After studying this unit, the learner/learner will be able to:
• explain the operation of an instrument potential transformer.
• explain the operation of an instrument current transformer.
• diagram the connections for a potential transformer and a current transformer
in a single-phase circuit.
• state how the following quantities are determined for a single-phase circuit
containing instrument transformers: primary current, primary voltage, primary
power, apparent power, and power factor.
• describe the connection of instrument transformers in a three-phase, three-wire
circuit.
• describe the connection of instrument transformers to a three-phase, four-wire
system.
Instrument transformers are used in the measurement and control of alternating
cur rent circuits. Direct measurement of high voltage or heavy currents involves
large and expensive instruments, relays, and other circuit components of
many designs. The use of instrument transformers, however, makes it possible
to use relatively small and inexpensive instruments and control devices of
standardized designs. Instrument transformers also protect the operator,
the measuring devices, and the control equipment from the dangers of high
voltage. The use of instrument transformers results in increased safety,
accuracy, and convenience.
There are two distinct classes of instrument transformers: the instrument
potential transformer and the instrument current transformer. (The word “instrument”
is usually omitted for brevity.)
POTENTIAL TRANSFORMERS
The potential transformer operates on the same principle as a power or distribution
transformer. The main difference is that the capacity of a potential transformer
is small compared to that of power transformers. Potential transformers have
ratings from 100 to 500 volt-amperes (VA). The low-voltage side is usually
wound for 115 volts or 120 volts. The load on the low-voltage side usually
consists of the potential coils of various instruments, but may also include
the potential coils of relays and other control equipment. In general, the
load is relatively light and it is not necessary to have potential transformers
with a capacity greater than 100 to 500 volt-amperes.
The high-voltage primary winding of a potential transformer has the same
voltage rating as the primary circuit. When it is necessary to measure the
voltage of a 4,600-volt, single-phase line, the primary of the potential
transformer would be rated at 4,600 volts and the low-voltage secondary would
be rated at 115 volts. The ratio between the primary and secondary windings
is:
4,600/115 or 40/1
A voltmeter connected across the secondary of the potential transformer
indicates a value of 115 volts. To determine the actual voltage on the high-voltage
circuit, the instrument reading of 115 volts must be multiplied by 40. (115
x 40 = 4,600 volts). In most cases, the voltmeter is calibrated to indicate
the actual value of voltage on the primary side. As a result, the operator
is not required to apply the multiplier to the instrument reading, and the
possibility of errors is reduced.
Figure 22-1 illustrates the connections for a potential transformer with
a 4,600-volt primary input and a 115-volt output to the voltmeter. This potential
transformer has subtractive polarity. (All instrument potential transformers
now manufactured have subtractive polarity.) One of the secondary leads of
the transformer in figure 22-1 is grounded to eliminate high-voltage hazards.
Potential transformers have highly accurate ratios between the primary and
secondary voltage values; generally the error is less than 0.5 percent. Power
transformers are not designed for highly accurate voltage transformation.

Fig. 22-1 Connections for a potential transformer
CURRENT TRANSFORMERS
Current transformers are used so that ammeters and the current coils of
other instruments and relays need not be connected directly to high-current
lines. In other words, these instruments and relays are insulated from high
currents. Current transformers also step down the current to a known ratio.
The use of current transformers means that relatively small and accurate
instruments, relays, and control devices of standardized design can be used
in circuits.
The current transformer has separate primary and secondary windings. The
primary winding, which may consist of a few turns of heavy wire wound on
a laminated iron core, is connected in series with one of the line wires.
The secondary winding consists of a greater number of turns of a smaller
size of wire. The primary and secondary windings are wound on the same core.
The current rating of the primary winding of a current transformer is determined
by the maximum value of the load current. The secondary winding is rated
at 5 amperes regardless of the current rating of the primary windings.
For example, assume that the current rating of the primary winding of a
current transformer is 100 amperes. The primary winding has three turns and
the secondary winding has 60 turns. The secondary winding has the standard
current rating of 5 amperes; therefore, the ratio between the primary and
secondary currents is 100/5 or 20 to 1. The primary current is 20 times greater
than the secondary current. Since the secondary winding has 60 turns and
the primary winding has 3 turns, the secondary winding has 20 times as many
turns as the primary winding. For a current transformer, then, the ratio
of primary to secondary currents is inversely proportional to the ratio of
primary to secondary turns.
In figure 22-2, a current transformer is used to step down current in a
4,600-volt, single-phase circuit. The current transformer is rated at 100
to 5 amperes and the ratio of current step down is 20 to 1. In other words,
there are 20 amperes in the primary winding for each ampere in the secondary
winding. If the ammeter at the secondary indicates 4 amperes, the actual
current in the primary is 20 times this value or 80 amperes.
The current transformer in figure 22-2 has polarity markings in that the
two high-voltage primary leads are marked H1 and H2 and the secondary leads
are marked X1 and X2. When H1 is instantaneously positive, X1 is positive
at the same moment. Some current transformer manufacturers mark only the
H1 and X1 leads or use polarity marks. When connecting current transformers
in circuits, the H1 lead is connected to the line lead feeding from the source,
while the H2 lead is connected to the line lead feeding to the load.

Fig. 22-2 A current transformer used with an ammeter
The secondary leads are connected directly to the ammeter. Note that one
of the secondary leads is grounded as a safety precaution to eliminate high-voltage
hazards.
Caution: The secondary circuit of a transformer should never be opened when
there is current in the primary winding. If the secondary circuit is opened
when there is current in the primary winding, then the entire primary current
is an exciting current which induces a high voltage in the secondary winding.
This voltage can be high enough to endanger human life.
Individuals working with current transformers must check that the secondary
winding circuit path is closed. At times, it may be necessary to disconnect
the secondary instrument circuit when there is current in the primary winding.
For example, the metering circuit may require rewiring or other repairs may
be needed. To protect a worker, a small short-circuiting switch is connected
into the circuit at the secondary terminals of the cur rent transformer.
This switch is closed when the instrument circuit must be disconnected for
repairs or rewiring.
Current transformers have very accurate ratios between the primary and secondary
current values: the error of most modem current transformers is less than
0.5 percent.
When the primary winding has a large current rating it may consist of a
straight conductor passing through the center of a hollow metal core. The
secondary winding is wound on the core. This assembly is called a bar-type
current transformer. The name is derived from the construction of the primary
which actually is a straight copper bus bar. All standard current transformers
with ratings of 1,000 amperes or more are bar-type transformers. Some current
transformers with lower ratings may also be of the bar type. Figure 22-3
shows a bar type current transformer.
Figure 22-4 shows a clamp-on ammeter that uses the concept of a window-type
cur rent transformer. By opening the clamp and then closing it around the
current-carrying conductor, the current in the conductor is measured on the
meter.

Fig. 22-3 Bar type current transformer.
Fig. 22-4 Clamp on style ammeters/multimeters.
INSTRUMENT TRANSFORMERS IN A SINGLE-PHASE CIRCUIT

Fig. 22-5 Single-phase metering connections
Figure 22-5 illustrates an instrument load connected through instrument
transformers to a single-phase, high-voltage line. The instruments include
a voltmeter (figure 22-6), an ammeter, and a wattmeter. The potential transformer
is rated at 4,600 to 115 volts; the current transformer is rated at 50 to
5 amperes. The potential coils of the volt meter and the wattmeter are connected
in parallel across the low-voltage output of the potential transformer. Therefore,
the voltage across the potential coils of each of these instruments is the
same. The current coils of the ammeter and the watt meter are connected in
series across the secondary output of the current transformer. As a result,
the current in the current coils of both instruments is the same. Note that
the secondary of each instrument transformer is grounded to provide protection
from high-voltage hazards, as provided in Article 250 of the National Electrical
Code.
The voltmeter in figure 22-5 reads 112.5 volts, the ammeter reads 4 amperes,
and the wattmeter reads 450 watts. To find the primary voltage, primary current,
primary power, apparent power in the primary circuit and the power factor,
the following procedures are used:
Primary Voltage
Voltmeter multiplier = 4,600/115 = 40
Primary volts = 112.5 x 40
= 4,500 volts
Primary Current
Ammeter multiplier = 50/S = 10
Primary amperes =4 x 10
=40 amperes

Fig. 22-6 Panel mounted meters use transformers to monitor large values
Primary Power
Wattmeter multiplier = Voltmeter multiplier x ammeter multiplier
Wattmeter multiplier = 40 x 10
= 400
Primary watts = 450 x 400
= 180,000 watts or 180 kilowatts
Apparent Power
The apparent power of the primary circuit is found by multiplying the primary
volt age and current values.
Apparent power (volt-amperes) = volts x amperes
volt-amperes = 4,500 x 40
= 180,000 watts = 180,000/1,000 = 180 kilowatts
Power Factor
Power factor = Power in Kilowatts/Apparent power in kilovolt-amperes
= 180/180
= 1.00 or 100 percent
INSTRUMENT TRANSFORMERS ON THREE-PHASE SYSTEMS
Three-Phase, Three-Wire System
On a three-phase, three-wire system, two potential transformers of the same
rating and two current transformers of the same rating are necessary. It
is common practice in three-phase metering to interconnect the secondary
circuits. That is, the connections are made so that one wire or device conducts
the combined currents of two transformers in different phases.
The low-voltage instrument connections for a three-phase, three-wire system
are shown in figure 22-7. Note that the two potential transformers are connected
in open delta to the 4,600-volt, three-phase line. This results in three
secondary voltage values of 115 volts each. The two current transformers
are connected so that the primary of one transformer is in series with line
A and the primary winding of the second transformer is in series with line
C.

Fig. 22-7 Metering connections for three-phase, three-wire system
Note that three ammeters are used in the low-voltage secondary circuit.
This wiring system is satisfactory on a three-phase, three-wire system and
all three ammeters give accurate readings. Other instruments which can be
used in this circuit include a three-phase wattmeter, a three-phase watt-hour
meter, and a three-phase power factor meter. When three-phase instruments
are connected in the secondary circuits, these instruments must be connected
correctly so that the proper phase relationships are maintained. If this
precaution is not observed, the instrument readings will be incorrect. In
checking the connections for this three-phase, three-wire metering system,
note that the interconnected potential and current secondaries are both grounded
to provide protection from high-voltage hazards.
Three-Phase, Four-Wire System

Fig. 22-8 Metering connections for three-phase, four-wire system
Figure 22-8 illustrates the secondary metering connections for a 2,400/4,152-volt,
three-phase, four-wire system. The three potential transformers are connected
in wye to give a three-phase output of three secondary voltages of 120 volts
to neutral. Three 50-to-5-ampere current transformers are used in the three
line conductors. Three ammeters are used in the interconnected secondary
circuit. Both the interconnected potential and the current secondaries are
grounded to protect against possible high-voltage hazards.
SUMMARY
Instrument transformers are specifically designed to transform voltage and
current in very precise ratios. Potential transformers are used to transform
high voltages to usable values of 115 or 120 volts for use by standard instruments.
Current transformers (CTs) are used to transform large values of ac current
down to a 5 amp level so that it can be used by standard instruments. DC
current levels are typically reduced to a usable level through the use of
shunts. The shunt has a primary-load current rating and the meter is then
connected across the shunt. The meter is designed to operate at 50 millivolts.
QUIZ
1. What are the two types of instrument transformers?
a.
b.
2. Why must the secondary circuit of a current transformer be closed when
there is current in the primary circuit? __________
3. A transformer is rated at 4,600/115 volts. A voltmeter connected across
the secondary reads 112 volts. What is the primary voltage?
4. A current transformer is rated at 150/5 amperes. An ammeter in the secondary
circuit reads 3.5 amperes. What is the primary current? _______
5. A 2,300/115-volt potential transformer and a 100/5-ampere current transformer
are connected on a single-phase line. A voltmeter, an ammeter, and a wattmeter
are connected in the secondaries of the instrument transformers. The voltmeter
reads 110 volts, the ammeter reads 4 amperes, and the wattmeter reads 352
watts. Draw the connections for this circuit. Mark leads H X and so forth.
Show all voltage, current, and wattage readings.
6. Complete a circuit using instrument transformers to measure voltage and
amperage. Include termninal markings.
FROM SOURCE TO LOAD
7. What is the primary voltage of the single-phase circuit given in question
5?
8. What is the primary current in amperes of the single-phase circuit given
in question 5?
9. What is the primary power in watts in the single-phase circuit given
in question 5?
10. What is the power factor of the single-phase circuit given in question
5?
Select the correct answer for each of the following statements.
11. The secondary for a potential transformer is usually wound for
a. 10 volts. c. 230 volts.
b. 115 volts. d. 500 volts.
12. Potential transformer secondaries are grounded to
a. stabilize meter readings.
b. insure readings with an accuracy of 0.5 percent.
c. complete a system with the primaries.
d. eliminate high-voltage hazards.
13. A transformer used to reduce current values to a size where small meters
can register them is a(n)
a. autotransformer. c. potential transformer.
b. distribution transformer. d. current transformer.
14. The primary of a large current transformer may consist of
a. many turns of fine wire.
b. few turns of fine wire.
c. many turns of heavy wire.
d. straight-through conductor.
15. The standard ampere rating of the secondary of a current transformer
is
a. 5 amperes. c. 15 amperes.
b. 50 amperes. d. 15 amperes.
16. The secondary circuit of a current transformer should never be opened
when current is present in the primary because
a. the meter will burn out.
b. the meter will not operate.
c. dangerous high voltage may develop.
d. primary values may be read on the meter. |