|
OBJECTIVES
After studying this unit, the learner/learner will be able to use the National
Electrical Code to determine the requirements and limitations of transformer
installations.
The National Electrical Code (NEC) covers the minimum requirements of the
installation of electrical wiring and equipment within public or private
buildings and their premises.
TRANSFORMER LOCATION
The location of transformers is a prime Code ruling. Most electrical codes
and power companies state that transformers and transformer vaults must be
readily accessible to qualified personnel for inspection and maintenance.
The codes also contain specific sections covering oil-insulated, askarel-insulated,
other dielectric fluids, and dry-type transformers, as well as transformer
vaults. Dry-type transformers installed outdoors should have weather-proof
enclosures.
TRANSFORMER OVERCURRENT PROTECTION
The National Electrical Code gives information on the overcurrent protection
required for transformers and transformer banks, as well as the maximum overcurrent
protection allowed on the primary of a transformer.

Fig. 24-1 Transformer overcurrent protection
Figure 24-1 illustrates where transformer primary protection is located.
For a transformer 600 volts or less, overcurrent protection is permitted
in the secondary in place of primary protection provided that certain regulations
are followed.
1. The secondary overcurrent protection. Must not be greater than 125 percent
of the rated current of the secondary.
2. The primary feeder must not have overcurrent protection in excess of
six times the rated primary current of the transformer. This is allowable
only when the percentage impedance of the transformer is not in excess of
6 percent.
3. If the percentage impedance is greater than 6 percent but less than 10
percent, the primary feeder must not be rated in excess of four times the
rated primary current of the transformer.
About 90 percent of the transformers used within buildings are the dry type
and generally require lower values of overcurrent protection. Consult Section
450-3 of the National Electrical Code for specific information as to the
value of the protection.
Figure 24-2 illustrates a transformer connection where the overcurrent protection
is inserted in the secondary circuit. Note that the only primary protection
is the feeder over- current protection.
A transformer with integral thermal overload protection (the protection
is built into the transformer) does not need primary fuse protection. However,
there must be primary feeder protection. The feeder overcurrent rating requirements
are the same as given previously.
The Code requires that instrument potential transformers have primary fuses.
Fuses of different sizes are required for operation above and below 600 volts.

Fig. 24-2 Transformer and feeder overcurrent protection.
SECONDARY CONNECTIONS BETWEEN TRANSFORMERS
The Code defines a secondary tie as a circuit operating at 600 volts or
less between phases. This circuit connects two power sources or power supply
points such as the secondaries of two transformers.
A secondary tie circuit should have overcurrent protection at each end except
in situations as described in the Code. A tie connection between two transformer
secondaries is shown in figure 24-3. Note that the tie conductor circuit
has overcurrent protection at each end and that there are no load taps in
the tie connections.

Fig. 24-3 Tie connections between transformers
However, when load taps are made in the tie circuit between transformers,
the minimum size of conductor required is regulated by the Code. In this
case, the current-carrying capacity shall not be less than a stipulated percentage
of the rated secondary current of the largest capacity transformer connected
to the secondary tie.
A tie connection (with load taps) between two transformer secondaries is
shown in figure 24-4, Since there are load taps present, the size of the
tie conductors must be increased.

Fig. 24-4 Tie connections between transformers with load taps
The overload protective devices used for the tie connection with load taps
must be approved by the Underwriters’ Laboratories, Inc. (UL). The following,
when approved, are acceptable for protection:
• limiting devices consisting of fusible-line cable connectors (limiter);
• automatic circuit breakers.
If the voltage exceeds a value specified in the Code, the tie conductors
must have a switch at each end of the tie circuit. When these switches are
open, the limiters and tie conductors are deenergized. These switches shall
be not less than the current rating of the tie conductors. Further, these
switches shall be capable of opening their rated current.
The Code gives further information on overcurrent protection where secondary
tie connections are used. It is acceptable practice to provide overcurrent
protection in the secondary connections of each transformer. The setting
of this overcurrent device is regulated by the Code.
An automatic circuit breaker must be installed in the secondary connection
of each transformer. This circuit breaker must have a reverse-current relay
set to open the circuit at not more than the rated secondary current of the
transformer.
PARALLEL OPERATION OF TRANSFORMERS
Transformers may be operated in parallel and protected as a unit if their
electrical characteristics are similar. These electrical characteristics
include the voltage ratio and the percentage impedance. When transformers
have similar electrical characteristics, they will divide the load in proportion
to their kVA rating.
GUARDING OF TRANSFORMERS
Appropriate provisions must be made to minimize the possibility of damage
to transformers from external causes. This is particularly important if the
transformers are located where they are exposed to mechanical injury.
Dry-type transformers must be provided with a noncombustible moisture-resistant
case or enclosure which will provide reasonable protection against the accidental
insertion of foreign objects. They also should have weatherproof enclosures
when installed outdoors. The transformer installation must conform with the
Code provisions for the guarding of live parts.
The operating voltage of exposed live parts of transformers must be marked
by warning signs or visible markings. These markings or signs are to be mounted
in unobstructed positions on the equipment and structure.
GROUNDING
The National Electrical Code requires that the metal cases and tanks of
transformers be grounded. Further, all noncurrent-carrying metal parts of
transformer installations and structures, including fences, are also to be
grounded. This grounding must be done in the manner prescribed by the Code
to minimize any voltage hazard that may be caused by insulation failures
or static conditions.
TRANSFORMER NAMEPLATE DATA
According to the Code, each transformer shall be provided with a nameplate
and the nameplate must include the following information:
a manufacturer’s name;
b. rated kVA capacity;
c. frequency in hertz;
d. primary and secondary voltages;
e. amount of insulating liquid and type used;
f. temperature class of insulation should be indicated on the nameplate
in dry-type transformers;
g. temperature rise for this insulation system;
h. impedance (25 kVA and greater);
i. required clearances for transformers with vented openings.
DRY-TYPE TRANSFORMERS INSTALLED INDOORS
Dry-type transformers are used extensively for indoor installations. These
transformers are insulated and cooled by air. They are not encased in the
steel tanks required for oil-filled transformers. For protection, dry-type
transformers are enclosed in sheet metal cases with openings to allow air
to circulate.

Fig. 24-5 Oil filled transformers with radiator cooling fins

Fig. 24-6 Oil insulated transformer used at a substation
The Code specifies that dry-type transformers of a 112 ‘/2-kVA rating or
less must have a separation of 12 inches from any combustible material. However,
there are Code conditions and exceptions.
Some transformers of more than a specific rating must be installed in a
transformer room with fire-resistant construction or must be installed in
a transformer vault. Transformers with Class B insulation (80°C temperature
rise) or Class H insulation (150°C temperature rise) need not be installed
in a transformer vault provided they are separated from combustible material
by the horizontal and vertical dimensions specified in the Code, or are separated
from combustible material by a fire-resistant barrier. Any dry-type transformer
rated at more than 35,000 volts must be installed in a transformer vault.
ASKAREL-INSULATED TRANSFORMERS INSTALLED INDOORS
The windings of some transformers are cooled and insulated by a synthetic,
non flammable liquid called as/care!. Askarel, when decomposed by an electric
arc, produces only nonexplosive gases.
The Code specifies that askarel-insulated transformers over 25 kVA must
be fur nished with a pressure-relief vent. If this type of transformer is
installed in a poorly ventilated area, it must be furnished with some method
of absorbing gases that may be generated by arcing inside the case.
Any askarel-insulated transformer rated over 35,000 volts must be installed
in a vault.
OIL-INSULATED TRANSFORMERS INSTALLED INDOORS
Many transformers are cooled and insulated with a special insulating oil.
The fire hazard potential due to oil-insulated transformers is greater than
that of askarel-insulated transformers therefore; the Code requirements are
more exacting for oil-insulated transformers.
OIL-INSULATED TRANSFORMERS INSTALLED OUTDOORS
The Code requires that combustible buildings, door and window openings,
and fire escapes must be safeguarded from fires originating in oil-insulated
transformers. Such protection may be provided by effective space separation
or by erecting a fire-resistant barrier between the transformer bank and
the areas requiring protection.
In addition, the Code requires that some means be installed to contain and
remove the transformer oil from a ruptured transformer tank. Such a precaution
applies to a transformer installation adjacent to a building where an oil
explosion can result in a fire hazard without this preventive measure.
PROVISIONS FOR TRANSFORMER VAULTS
The Code regulations cover all essential details for vaults used for transformer
installations, including the arrangement, construction, and ventilation of
the vaults.

Fig. 24-7 Approved use of an autotransformer
AUTOTRANSFORMERS
Code specifications are given for the use of autotransformers for lighting
circuits. Recall that an autotransformer does not have separate primary and
secondary windings. It consists of only one winding on an iron core. Part
of the single winding of the autotransformer is common to both the primary
and secondary circuits.
The Code limits the use of an autotransformer to feeding branch circuits
because of the interconnection of the primary and secondary windings. The
autotransformer may be used only where the identified ground wire of the
load circuit is connected solidly to the ground wire of the source (NEC Section
210-9).
Figure 24-7 illustrates an autotransformer connected to a lighting load.
Note that the ground wire is carried through the entire system.
An alternate use of an autotransformer for lighting circuits is shown in
figure 24-8. This circuit also follows Code regulations as the identified
ground wire is carried through the entire system.
Figure 24-9 illustrates an application for an autotransformer which is NOT
approved by the Code. Here, the single-phase, 230-volt input to the autotransformer
is obtained from a three-phase, 230-volt source. The use of a mid-tap on
the autotransformer makes available a single-phase, three-wire system for
a lighting load. However, if the ground wire is not solidly connected through
the entire system, this circuit will not meet Code regulations. The type
of installation shown in figure 24-9 is unsafe, particularly if an accidental
ground condition develops on the three-phase system.

Fig. 24-8 Approved use of an autotransformer

Fig. 24-9 Incorrect use of an autotransformer

Fig. 24-10 Voltage regulator transformer (Courtesy of Westinghouse Electric
and Manufacturing Company)
“Buck” and “Boost” Transformers

Fig. 24-11 Transformer used for buck or boost application
Autotransformers are also used where only a small voltage increase (boost)
or decrease (buck) is required, (figure 24-11). An example is to operate
a 230-volt appliance from a 208-volt feeder line. This is accomplished by
the use of an autotransformer which increases the 208-volt feeder line voltage
to the 230 volts required to operate the appliance. Voltage drops (losses)
in long or heavily loaded distribution systems may be increased in this manner
as an energy conservation measure. Many regular (isolating) transformer corrections
are used as autotransformers to decrease or increase a voltage.
Fig. 24-12 (above right) Four-wire delta secondary identification
IDENTIFIED FEEDER
On a four-wire, delta-connected secondary feeder conductor where the midpoint
of one phase is grounded to supply lighting and similar loads, the phase
conductor with the highest voltage to ground must be identified by an outer
finish that is orange in color, or by tagging, (figure 24-12). This identification
is to be placed at any point where a connection is made if the neutral conductor
is also present, such as in a distribution panel, junction box, or pull box.
SUMMARY
Transformers must be installed according to the provisions of the National
Electrical Code. There are many provisions that apply and each case must
be thoroughly researched. When using the Code criteria, be sure to consider
all the provisions of the Code. Overcurrent protection can be quite different
depending on the location and other protection avail able at the transformer
installation. Be sure to consider the nameplate information when locating
the transformer. Transformers can be quite dangerous and may cause severe
injury or property damage if not installed and protected properly.
QUIZ
1. The rated primary current of a transformer is 4 amperes at 480 volts.
How is the permissible maximum current setting determined for the overload
devices used on the primary side of the transformer when secondary overcurrent
protection is omitted?
2. The Code permits overcurrent protection in the secondary in place of
the primary protection if two requirements for transformers 600 volts or
less are observed. What are these requirements?
a.
b.
3. What items of data should appear on a transformer nameplate to comply
with Code requirements?
4. What is a secondary tie circuit?
5. What happens to the secondary tie conductor size if loads are connected
to the tie conductors?
6. What overload devices are acceptable to protect a secondary tie connection
with load taps?
7. What are the electrical characteristics that must be similar if transformers
are to be operated in parallel?
8. What are the Code requirements for the grounding of transformer installations?
9. How is the load divided when transformers are operated in parallel and
protected as one unit?
10. What precaution must be observed in using autotransformers to supply
lighting circuits which are grounded?
11. Give an example of how an autotransformer is used in a circuit to increase
the volt age.
12. Connect the following isolating transformer as an autotransformer to
“boost” the voltage from source to load.______________________________________________

|