|
OBJECTIVES:
After studying this unit, the learner/learner will be able to
• identify a self-excited shunt generator from a circuit diagram.
• describe the way in which the voltage buildup occurs for this type of
generator.
• list the causes for a failure of the voltage to build up.
• describe three methods which can be used to renew residual magnetism:
• define voltage control and voltage regulation.
• draw the basic circuit.
• connect the generator.
Most dc generators of the shunt type are self excited. A generator is
called a shunt generator when its field circuit is connected in parallel
with the armature and load. In the field circuit, itself, a four-pole winding
may be connected in series, parallel, or series-parallel. The circuit arrangement
of the field windings does not affect the classification of the generator
because the field windings, as a group, are connected in parallel with
the armature and load.

Ill. 3—1 Self-excited shunt generator
VOLTAGE BUILDUP
Figure 3—1 shows the schematic diagram of a self-excited shunt generator.
Voltage control is obtained with a field rheostat. Unlike the separately
excited generator, there is no current in the field circuit when the armature
is motionless. Since a small amount of residual magnetism is present in
the field poles, a weak residual voltage is induced in the armature as
soon as the armature is rotated. This residual voltage produces a weak
current in the field circuit. If this current is in the proper direction,
an increase in magnetic strength occurs with a corresponding increase in
voltage output. The increased voltage output, in turn, increases the field
current and the field flux which, again, increase the voltage output. As
a result of this action, the output voltage builds up until the increasing
field current saturates the field poles. Once the poles are saturated,
the voltage remains at a constant level, unless the speed of the armature
rotation is changed.
If the direction of armature rotation is reversed, the brush polarity
also is reversed. The residual voltage now produces a field current which
weakens the residual magnetism and the generator voltage fails to build
up. Therefore, a self-excited machine develops its operating voltage for
one direction of armature rotation only. The generator load switch may
be closed when the desired voltage is reached.
LOSS AND RENEWAL OF RESIDUAL MAGNETISM
A shunt generator may not develop its rated operating voltage due to a
loss of residual magnetism. The residual flux may be renewed by momentarily
connecting a low-volt age dc source across the field circuit. Several methods
can be used to renew the residual magnetism.
Method 1
a. Disconnect the field circuit leads from the brushes.
b. Momentarily connect a storage battery or low-voltage dc source to the
field circuit leads. To maintain the desired brush polarity, connect the
positive terminal of the battery to the field lead normally attached to
the positive generator brush.
Method 2
a. If it is inconvenient to detach the field leads and the brush assembly
can be reached, lift either the positive or the negative brush and insert
a piece of heavy, dry paper between the brush and the commutator segments.
b. Momentarily connect a battery to the output leads. With the brush lifted,
current passes through the field circuit only. (To maintain the original
brush polarity, connect the positive terminal of the battery to the positive
generator output terminal.)
c. Remove the paper under the brush before restarting the generator.
Method 3
a. If it can be done readily, disconnect the generator from its prime
mover.
b. Then, restore the residual field by momentarily connecting a battery
to the generator output leads. Since the field circuit is connected across
the output leads, the current renews the magnetic field.
Caution: If the armature is not free to rotate, damage to the armature
assembly may occur. When the battery voltage is high enough in Method 3,
the generator armature rotates as a motor. The rotation produced does not
contribute to restoring the residual flux. How ever, this effect, called
motorizing, is useful because it is a rough check of the overall generator
operation. That is, the armature should rotate freely if the voltage applied
is a sizable fraction of the rated output voltage, with the direction of
armature rotation opposite to the proper direction of rotation for a generator.
Use a reduced voltage for large motors.
Brush Polarity
To maintain the original brush polarity when renewing the residual magnetism,
the electrical polarities of the output leads and the exciting battery
must be matched. In other words, the positive terminal of the battery must
be connected to the positive output terminal of the generator and the negative
battery terminal must be connected to the negative generator terminal.
The motorizing test should never be used for restoring residual flux if
the generator armature is mechanically engaged to the prime mover and cannot
rotate freely. A strong current through the motionless armature sets up
a powerful magnetic field on the armature core. This magnetic field may
overpower and reverse the main field flux, causing a reversal of the brush
polarity when the generator is restarted. If there is any doubt as to whether
or not the armature can be disconnected completely from the prime mover,
it is preferable to isolate and energize the field circuit only, either
by lifting the brushes or disconnecting the field leads.
CRITICAL FIELD RESISTANCE
A shunt generator may fail to reach its operating voltage even though
its residual magnetic field is satisfactory. This failure may be due to
excessive resistance in the field circuit. Any generator has critical field
resistance. The presence of resistance in the field circuit in excess of
this critical value causes the generator to fail to build up to its rated
operating voltage.
Since field rheostats are used to control the voltage output at rated
speed, it is important to reduce the resistance of the field rheostats
to a minimum value before investigating other possible faults in the event
of failure to develop rated voltage.
BRUSH CONTACT RESISTANCE
Contact resistance at the brushes is another reason for the failure of
the generator to develop its operating voltage. Since the field circuit
is completed through the armature, any resistance introduced at this point
is effectively in the field circuit. Additional pres sure applied to the
brushes may indicate trouble from this source.
Improper connection of the field circuit leads at the brushes is also
a cause of failure to build up rated voltage. An improper connection can
be discovered by reversing these leads.
ROTATION
When a dc shunt generator is used in special applications, it may be necessary
for the armature to rotate in a direction opposite to that specified by
the manufacturer. To develop voltage buildup in these instances, the field
circuit leads at the brushes must be reversed.
RATINGS
Shunt generators are rated for speed, voltage, and current. Generators
used in aircraft and automobiles operate through a wide range of speeds,
but must maintain a constant load voltage. Voltage regulators which automatically
change field resistance are used.
Generators designed for operation at a constant rated speed must not be
operated above this value, unless the field circuit is protected from the
effects of excessive current by current-limiting devices.
OUTPUT VOLTAGE CONTROL
Field rheostats are used to control the voltage output of shunt generators.
At a given speed, the rheostat can be used only to bring the output voltage
to values below the rated voltage obtainable without a field control. Values
above the normal rated voltage can be obtained only by operating the generator
above normal speed.
VOLTAGE REGULATION
The terms voltage regulation and voltage control are often confused. Voltage
control refers to intentional changes in the terminal voltage made by manual
or automatic regulating equipment, such as a field rheostat.
Voltage regulation refers to automatic changes in the terminal voltage
due to reactions within the generator as the load current changes.
Voltage regulation is defined as the percent difference between the voltage
output when there is no electrical load (EnL) and the terminal voltage
at full rated current capacity (EfL) . The formula used to determine
the percent of voltage regulation as follows:
[(EnL-EfL) / EfL] x 100 = % regulation
For example, it is inherent in the design of a shunt generator for the
output voltage to fall off as the load increases. If the drop is severe,
the generator is said to have poor voltage regulation.
SUMMARY
A self-excited shunt generator has the field coils and the field rheostat
shunted across the armature connections. If there is residual magnetism
left in the field iron, then spinning the armature will produce residual
voltage. This residual voltage is normally enough to begin the generation
process. If there is not enough residual voltage, then the residual magnetism
must be re-established. Self-excited generators must have the field polarity
correctly established and the armature spinning in the proper direction
to develop output voltage. The output voltage can be controlled by adding
or removing resistance to the shunt field circuit.
QUIZ
Select the correct answer for each of the following statements.
1. Most dc generators are _____
a. self-excited.
b. excited by storage batteries.
c. series wound.
d. excited separately.
2. The field coils of a shunt generator are always connected
a. in parallel with a rheostat.
b. in parallel with each other.
c. in series with each other.
d. across the line.
3. The voltage of a shunt generator is built up by:
a. permanent magnetism.
b. proper operation of the field rheostat.
c. residual magnetism.
d. increasing the speed.
4. The field windings of a shunt generator must have:
a. full line current applied.
b. comparatively low resistance.
c. one ohm resistance per volt.
d. comparatively high resistance.
5. Cutting resistance out of a shunt field circuit
a. cuts down the magnetic flux.
b. decreases the terminal voltage.
c. increases the load.
d. increases the terminal output voltage.
6. Failure of a dc shunt generator to build up to its rated voltage can
be due to:
a. loss of residual magnetism.
b. resistance greater than the critical field resistance.
c. rotation of the armature in the direction opposite to that known to
cause a voltage buildup.
d. brush contact resistance effectively increasing the field circuit resistance
above the critical point.
e. improper connection of the field circuit leads at the brushes.
f. all of these.
7. Voltage control refers to a change that takes place:
a. due to the, operation of auxiliary regulating equipment.
b. when the terminal voltage is increased.
c. when the speed is regulated.
d. automatically when the load is changed.
8. Voltage regulation refers to a change that takes place:
a. when speed is regulated.
b. when the terminal voltage is increased.
c. automatically when the load is changed.
d. when auxiliary equipment is used.
9. When the load is raised from minimum to maximum there is:
a. no change in terminal voltage.
b. an increase in terminal voltage.
c. a decrease in terminal voltage.
d. less change than in other generators.
10. Connect the following self-excited generator by drawing the proper
connections in the terminal boxes.
11. Write the formula for percent voltage regulation.
|