OBJECTIVES
After studying this unit, the learner/learner will be able to:
• state the differences between a shunt generator and a compound-wound
generator.
• define what is meant by a cumulative compound-wound generator and a
differential compound-wound generator.
• describe how the voltage regulation of a generator is improved by compound
windings.
• list changes in output voltage at full load due to the effects of over-compounding,
flat compounding, under-compounding, and differential compounding.
• draw the basic generator circuit.
• connect the generator.
The voltage regulation of a generator is an important factor in deciding
the type of load to which the generator should be connected. For lighting
loads, a constant terminal voltage should be maintained when the load current
increases. A simple shunt generator can only do this if expensive regulating
equipment is also used.
Generators designed to maintain a constant voltage within reasonable load
limits may have a double winding in the field circuit (figure 4—1). The
second winding is wound on top of, or adjacent to, the main winding. This
second winding is called the series winding to distinguish it from the
main shunt winding. The series winding has fewer turns than the shunt winding.
Since the series winding is connected in series with the armature and load,
it carries the full-load current, and is heavier gauge wire than the shunt
field. A generator with such a double-field winding is called a compound-wound
generator.
Figure 4 shows the basic circuits of two ways to connect a compound-wound
generator: the long shunt and the short shunt. In the short shunt circuit
(A), the main shunt field is connected directly across the brushes; in
the long shunt circuit (B), the shunt field is connected across the combination
of the armature and the series field. The operating characteristics of
these circuits are quite similar, but the short shunt is preferred because
the shunt field remains more constant and is not affected by changes caused
by the series field.

Ill. 4—1A Short shunt compound generator connection. A. SHORT
SHUNT CONNECTION; SHUNT FIELD; SERIES FIELD; FIELD RHEOSTAT. Ill. 4—1B
Long shunt compound generator connection: B. LONG SHUNT CONNECTION
COMPOUND FIELD WINDINGS
Two important details of the compound-wound generator must be considered:
(1) the relative direction of the currents through both windings of a particular
field pole, and (2) the magnetic effects which these currents can produce.
The series and shunt windings of a single pole of a compound-wound generator
are shown in, figure 4—2. Winding (A) is the series winding through which
the load current passes; winding (B) is the normal shunt winding. If the
load current is in the direction shown in figure 4—2, the magnetizing force
of the series winding (A) will aid the shunt winding (B) and increase the
strength of the magnetic field. The current in the shunt winding is not
normally strong enough to saturate the core. If the load current through
the series winding is in the direction opposite to that shown in figure
4—2, its effect will be to weaken the magnetic field.

Ill. 4—2 Compound field windings: GENERATOR FIELD POLE.
When the series winding is connected to aid the shunt winding, the generator
is called a cumulative compound-wound generator; if the series winding
is connected to oppose the magnetic field, it is called a differential
compound-wound generator.
The action of two fields in changing the flux density can be used to improve
the volt age regulation of a normal shunt generator. As you recall, as
a load is applied in the shunt generator, the output voltage falls because
of internal resistance, armature reaction, and the reduction of voltage
applied to the field circuit. If the field strength can be automatically
increased in proportion to load current as it increases, the output voltage
can be maintained at a constant level, increased, or decreased. This is
the objective in adding the series winding to the compound generator. As
the load current increases in a cumulative-compound connected generator,
it passes through the series winding and increases the flux. The additional
voltage induced by cutting this flux compensates for the voltage loss due
to armature resistance, armature reaction, and lower shunt field voltage.
The number of turns in the series field helps determine the degree of
compounding which is achieved. A large number of turns in the series winding
produces over-compounding (a voltage increase at full load as compared
to the output voltage at no load). A small number of series turns produces
a reduced voltage at full load. This effect is called under-compounding.
Flat compound generators have the same voltage output at no load and full
load. In industry, this type of generator is used where the distance between
the generator and the load is short and line resistance is minimal. Over-compounding
generators are used when the transmission distance is long, as in traction
service, and the voltage at the end of the line must remain fairly constant.
A comparison of the voltage regulation of a shunt generator and a compound
generator for both cumulative and differential connections is shown in
figure 4—3.

Ill. 4—3 Compound generator load characteristics.
OUTPUT VOLTAGE CONTROL
The rated voltage of a compound generator operating at rated speed is
set by adjusting the field rheostat. Since the compounding effect of the
series field changes with speed, it is important to operate a compound
generator at its rated speed.
Variation of Compounding
In general, compound-wound generators are designed by the manufacturer
to have an over-compounding effect. The amount of compounding can be changed
to any desired value by using a diverter rheostat across the series field.
In figure 4—4, a diverter rheostat (R) is connected in shunt (parallel)
with the series winding. If the resistance of the diverter is set at a
high value, the load current passes through the series winding to produce
a maximum compounding effect. If the diverter is set at its minimum value,
no load current passes through the series winding and the generator acts
like a normal shunt generator. By adjusting the rheostat to intermediate
values, any degree of compounding within these limits can be obtained.
Flat compounding results when “no load” voltage is equal to “full load”
voltage.

Ill. 4—4 Diverter circuit: diverter rheostat, shunt
field rheostat
SUMMARY
Compound-wound generators use a series field, connected in series with
the load, to react to current load changes. It is connected to aid the
shunt field or to oppose the shunt field. In most dc generators the series
field will be connected so that the magnetic field produced, aids the shunt
field flux. This connection is called a cumulative connection. The degree
of compounding can be controlled by a diverter rheostat. If the series
field is connected so that the resultant flux opposes the shunt field flux,
then the output voltage drops with an increase in current-draw and the
generator is differentially connected.
QUIZ
A. Select the correct answer for each of the following
statements.
1. A compound-wound generator terminal connection box contains terminal
leads
a. F1, F2, and A1, A2
b. S1, S2, and F1, F2
c. S1, S2, and A1, A2
d. S1, S2, F1, F2, and A1, A2
2. The series winding must be large enough to carry:
a. the total magnetic flux.
b. a 300% overload.
c. full line current.
d. full line voltage.
3. Select the type of generator that may be used for loads quite distant
from the generator.
a. Over-compounded c. under-compounded
b. flat compounded d. differential compounded
4. The normal voltage of a compound generator is changed by adjusting
the ____
a. series field shunt. c. shunt field rheostat.
b. brush setting. d. equalizer.
5. The resistance of a series field diverter should be:
a. comparatively high.
b. equal to the resistance of the series field.
c. a variable resistor.
d. comparatively low.
6. To achieve a maximum compounding effect, the diverter rheostat should
be:
a. set at its minimum value.
b. set at a high value.
c. set at a value midway between its minimum and maximum values.
d. removed from the series field circuit.
B. Select the correct answer to questions 7 to 12 from the following list
and place it in the space provided.
a. field poles g. increase
b. diverter rheostat h. flat compounding
c. compound-wound generator i. shunt field rheostat
d. saturate j. over-compounding
e. decrease k. remain constant
f. shunt generator l. under-compounding
7. When it is necessary to provide automatic control of the voltage output
at constant speed, the generator selected is a ______
8. The current through the shunt winding of a compound generator is not
sufficient to _____________ the field poles.
9. The terminal voltage output of a cumulative compound-wound generator
should ________________ as the load current is increased.
10. When the output voltage of a generator is the same at both no load
and full load, the generator is called a ________ type.
11. Compound-wound generators are generally designed to be of the type.
12. The amount of compounding which can be obtained from a generator is
controlled by the ________.
|