|
OBJECTIVES
After studying this unit, the learner will be able to:
• describe the operation of a dc series lockout relay.
• list the steps in the operating sequence of a series lockout relay acceleration
controller.

Fig. 10—1 Series lockout relay: Note: In another type of relay,
the magnetic gap is changed by shims located in back of the coil, rather
than by an adjusting screw.
A series lockout relay with its two coils is shown in figure 10—1. The
lockout coil prevents the relay contacts from closing during the period
of high motor starting current.
The pull-in coil closes the relay contacts when the motor has accelerated
and the starting current is reduced.
OPERATION OF THE SERIES LOCKOUT ACCELERATION CONTROLLER

Fig. 10—2 Elementary diagram for the series lockout acceleration
controller.
Figure 10—2 is the elementary diagram of a controller which uses series
lockout relays to produce the necessary time delay or step control in motor
acceleration.
Coils 1 A, 2A, and 3A are the pull-in coils of the three relays, while
coils 1 HA, 2HA, and 3HA are the lockout coils of the relays.
When the start button is pressed, coil M is energized, and the main contactor,
M, (1) seals the bypass auxiliary contact around the start button, and
(2) allows current to flow in the following sequence: from L1 through contact
M, the motor armature, the series field, coil 1A, coil 1HA, resistors R1,
R2 and R3 and coil 3HA to L2.
The large starting current through coil 1 HA produces a large magnetic
effect in this coil. Since this effect is larger than that of coil 1A,
the relay is held open due to the fact that the magnetic path of the pull-in
coil has a small amount of iron. As a result, this coil becomes saturated
at high values of current. The magnetic circuit of the lockout coil has
a larger amount of iron and, therefore, does not tend to become saturated
at a high current value.
As the motor accelerates and the starting current decreases, the pull
of the lockout coil becomes less than the pull of the pull-in coil and
contactor 1A closes. Resistor R1 and lockout coil 1HA are bypassed and
thus increased current is allowed through lockout relay coils 2A and 2HA.
A cycle of operation similar to that which occurred for relay 1A now takes
place for relay 2A. The current path is now from L1 through M, the armature
and series field, coil 1A, contact 1A, coils 2A and 2HA, resistors R2 and
R3 and coil 3HA to L2. The large current through lockout coil 2HA produces
more magnetic pull than is present at coil 2A with the result that contact
2A is held open.
Finally, as the motor accelerates, all resistors and relays are shunted
out. This should immediately cause all relay contacts to drop out, except
for the fact that coil 3AS is an auxiliary shunt coil which acts on contactor
3A. Coil 3AS is strong enough to hold contact 3A closed after it has been
pulled into contact, but is not strong enough to cause 3A to close its
contacts without the aid of coil 3A.
When there is a heavier load on the motor, acceleration takes place over
a longer period of time.
SUMMARY
The operation of the series lockout relay differs from the voltage drop
relay. The lockout relay coil is in series with the pull-in coil. The magnetic
fields are designed to pull the lockout coils first. As the current to
the armature decreases, the lockout coil field is weakened and the shunting
coils are allowed to pull the contacts shut, bypassing the armature resistors.
QUIZ
1. How is control relay M in the series lockout acceleration controller
held in when the start button is released?
2. How does the lockout relay short out a starting resistor when the motor
is accelerated?
3. What will happen if a break occurs in the coil of 3A?
4. A motor accelerates through two steps only. The speed is below normal
and the motor voltage is low at the armature terminals. What is the probable
cause of the problem?
5. What is the purpose of the 3AS coil of the lockout relay? |