OBJECTIVES
After studying this unit, the learner will be able to:
• explain how relays operate.
• list the principal uses of relays.
• describe different relay control and load conditions.
• tell how SCRs operate.
• identify relay component symbols.
• connect different relays in a circuit.
• identify and use various timers.
• use proper timer symbols in schematic diagrams.
RELAYS
Relays are devices used to relay or multiply electrical contact closures.
The relay concept is used where a small voltage at low current is used
to operate a set of electrical contacts to an open or closed position.
This contact operation in turn controls a larger electric load and so on,
as it relays the electrical operations.
Another common use of a relay is to multiply a single signal to open or
close multiple contacts for control of multiple electrical loads.
ELECTROMECHANICAL RELAYS
Electromechanical relays, contactors, and motor starters basically operate
by the same principles. These electrically-operated switches respond to
the electromagnetic attraction of an energized coil of wire in an iron
core. The devices differ in the amount of current that each must switch.
The relay—which can be compared to an amplifier—is used to switch small
amounts of currents (usually 0—15 amperes) in many control circuits (figure
13—1). Uses of relays include: switching (on and off) larger coils of motor
starters, contactors, solenoids, heating elements, and small motors. Other
uses are alarm systems and pilot light control. Relays have many industrial
and commercial applications, both ac and dc.

Fig. 13—1 Control relay and associated coil contact diagram.
A small current flow and/or low voltage applied to a relay coil can result
in a much larger current or voltage being switched. One input signal (voltage)
may control several output (switched) circuits (figure 13—2).

Fig. 13—2 Several electrical-mechanical relay uses and contact configurations:
SWITCHED CONTACT OUTPUT 230 VOLTS; COIL INPUT 24 VOLTS A; MULTIPLE CONTROLLED
OUTPUT NORMALLY OPEN (N/O); ONE INPUT SIGNAL (VOLTAGE). SWITCHED CONTACT
OUTPUT 15 AMPERES; COIL INPUT 0.25 AMPERE; MULTIPLE CONTROLLED OUTPUT NORMALLY
CLOSED (N/C) AND NORMALLY OPEN; ONE INPUT SIGNAL (VOLTAGE).
The coil voltages of the relay are separate or different from those at
the switched contacts; this is called separate control. However, the coil
voltage may be the same sys tem voltage as the switched voltage.
Relays are available in many shapes and sizes. Some are sealed in dustproof,
transparent plastic enclosures (figure 13—3 A). The general construction
of a typical relay is shown in figure 13—3B.
Note in figure 13—2 that relay contacts maybe normally-closed or normally-open.
The action of the contacts is to switch something on or off depending on
the configuration.

Fig. 13—3A “Ice cube relays” and plug in bases used for easy replacement
 Fig. 13—3B Construction of a typical electromagnetic control relay: ELECTROMAGNETIC
COIL OF MANY TURNS OF WIRE; TO CONTROL CIRCUIT VOLTAGE; MOVEABLE ARMATURE;
TO SWITCHED LOAD AND VOLTAGE; TO CONTROL CIRCUIT VOLTAGE

Fig. 13—4 Schematic symbol for an SCR which is the heart of the solid-state
relay: SWITCHED POWER TERMINALS; GATE (CONTROL), CATHODE, ANODE
SOLID STATE RELAY (SSR)
A solid state relay can be used to control most of the circuits that the
electromechanical relay controls. By comparison, the solid-state relay
has no coil or contacts. The semi conductor industry has developed solid-state
components with unusual applications to the industrial control processes.
These components are very compact and versatile. They are very reliable
if used in the proper application.
The silicon-controlled rectifier (SCR) is probably the most popular solid-state
device for controlling large and small electrical power loads. Basically,
the SCR is a rectifier which either conducts or does not conduct an electric
current. When it is not con ducting, the SCR offers almost a complete blockage
to the current. It passes only a few milli-amperes to the load. For this
reason, some manufacturers place contacts from electrically operated contactors
in the total circuit to disconnect the load completely.
The SCR will not conduct when the voltage across it is in the reverse
direction. It will conduct only in the forward direction when the proper
signal (voltage) is applied to the gate terminal (figure 13—4). Once it
is conducting, the SCR cannot be turned off immediately. It is necessary
only to provide a small signal to start the SCR conducting a current. It
will continue to conduct even without a signal from that point on as long
as the current is in the forward direction. The only way to stop the SCR
from conducting is to reduce the current flow below the holding current
level, or disconnect it from the system. On alternating current, of course,
this happens every half-cycle, so this characteristic is no problem (figure
13—5). For direct-current applications, the voltage is reduced to zero
by interrupting the circuit, generally with a contact on an electromagnetic
relay.
Figure 13—6 shows a typical solid-state relay. Note the input and switched
output terminal connections. Figure 13—7 shows these connections completed.
Terminal wiring is very simple and consists of two input control wires
and two output load wires. The connecting terminals are clearly identified
on solid-state relays (as they are on electromechanical relays). The relay
in figure 13—7 has a light-emitting diode (LED) connected to the input
or control voltage. When the input voltage turns the LED on, a photo-detector
connected to the gate of the triac turns the triac on and connects the
load to the line. This optical coupling is commonly used with solid-state
relays. These relays are referred to as being opto-isolated. This means
that the load side of the relay is optically isolated from the control
side of the relay. The control medium is a light beam. No voltage spikes
or electrical noise produced on the load side of the relay are therefore
transmitted to the control side.

Fig. 13—5 An SCR will contact current in the forward direction until
the voltage is reduced to zero.

Fig. 13—6 Solid state relay has no moving parts.
Solid state relays have a wide range of input or control voltage designs.
The solid state relays may operate at TTL (transistor logic levels) + 5
volts dc. They may operate at levels between 3—30V dc or other relays at
90—120V ac. Considerations as to what style of relay include the way that
the SSR turn on. A zero switch relay turns on as the load volt age crosses
zero. This is often used for resistive type loads.
Instant-on relays turn on anytime during the ac waveform to the load.
A third style is the universal switch. This turn-on occurs after the load
voltage has reached peak and is moving toward zero. The universal switch
is used for combination loads of inductive and resistive loads.
TIMERS
Timers come in many different styles and with different operating characteristics.
The mechanical timers use either clock motors to operate a mechanical trip
mechanism or solenoids to create timing operations. Pneumatic timers use
air, a diaphragm, and an operating solenoid to cause a time delay. Figure
13—8 shows a mechanical time-clock-type timer. This type of timer is used
for rough time-of-day timing to turn lights or equipment on or off at an
approximate time of day. Tabs on the face of the clock are moved to create
different on and off periods.

Fig. 13—7 Solid state relay used to control an ac load

Fig. 13—8 Synchronous clock timer
Pneumatic timers such as those in figure 13—9 are typically used for on
or off delay operations. The symbols shown in figure 13—10 depict the type
of timer operation and the operation of the contacts. In ON-delay timers
(TDE, Time-Delay-on-Energization) the contacts stay in their original position
until a solenoid plunger has moved through its entire travel distance.
The travel time is controlled by adjusting a needle valve to allow the
air to escape in front of the solenoid diaphragm. The timer solenoid has
power applied to pull the plunger into its timed-out position. The contacts
can start as either normally-open or normally-closed and will change to
the opposite position at the end of the time, if power is still applied
to the solenoid coil.
The OFF-delay timer (TDD, Time-Delay-on-De-energization) acts in the opposite
mode. In other words, the timing change to the contacts takes place when
the power is removed from the timer coil and the solenoid plunge is allowed
to go back to it de-energized position. The time that it takes the solenoid
to return to it original position is con trolled by the needle valve allowing
air to return to the vacuum side of the air diaphragm. Figure 13—10 shows
the TDD contacts in their normal, timed-out state. When power is applied
to the timing coil in this type timer, the contacts change to the opposite
state and will time out to return to the original designation.

Fig. 13—9 Time delay relay symbols used with timers:.
Fig. 13—10 Time delay on de-energization contact symbols: NORMALLY CLOSED/OPEN,
TIME OPENING

Fig. 13—11 Electronic timers with side range of functions and time delays
Solid state timers are now commonly used to provide highly accurate and
an extremely wide range of timing operations. Many of the timers, such
as the one in figure 13—11, can be used as ON-delays or OFF-delays and
have several different trigger modes.
They can also provide a wide range of timing, from milliseconds to hundreds
of hours.
The timing is accomplished with electronics, which makes them very accurate
and precise.
SUMMARY
Relays are used to control various loads from other electrical circuits.
They may be used to operate large values of dc or ac power or simply multiply
the electrical circuit function. Contacts can be normally-open (NO) or
normally-closed (NC) or convertible from one form to another.
Things to consider when ordering:
Control voltage and value;
Contact ratings in current and voltage, number of contacts, NO, NC, or
SPDT, etc.
Are open contacts, enclosed contacts, or solid-state no-contact movement
important?
Does the relay need very fast speed as in SSR or is physical isolation
more important as in electromechanical relays?
QUIZ
1. A mouse trap may be compared with the gate trigger action of an SCR.
Indicate whether this statement is true or false and explain your reasoning.
2. What is the major difference between an electromechanical relay and
a solid-state relay?
3. Describe different relay control and load conditions.
4. How are relays used in industrial controls?.
5. Basically, what is an SCR? |