|
OBJECTIVES
After studying this unit, the learner will be able to ...
describe the basic sequence of actions of the following types of controllers
when used to control three-phase ac induction motors: jogging-type controller,
quick-stop ac controller (plugging), dynamic braking controller, resistance
starter controller, automatic autotransformer compensator, automatic controller
for wound-rotor induction motors, wye-delta controller, and automatic controller
for synchronous motors.
• identify and use the various National Electrical Code sections pertaining
to controllers and remote control circuits for motors.
• state why ac adjustable speed drives are used.
• list the types of adjustable speed drives.
• describe the operating principles of different ac adjustable speed drives.
• list the advantages and disadvantages of some units.
The industrial electrician is required to install, maintain, and repair
automatic ac controllers which start up and provide speed control for squirrel-cage
induction motors, wound-rotor induction motors, and synchronous motors.
MOTOR CONTROLLERS WITH JOGGING CAPABILITY
Many industrial processes require that the driven machines involved in
the process be inched or moved small distances. Motor controllers designed
to provide control for this type of operation are called jogging controllers.
Jogging is defined as the quickly repeated closure of a controller circuit
to start a motor from rest for the purpose of accomplishing small movements
of the driven machine.
An across-the-line magnetic motor switch may be used to provide jogging
control if the proper type of pushbutton station is used in the control
circuit. Such a pushbutton station is called a start-jog-stop station.
Figure 16—1 A is a diagram of the connections for a three-phase, squirrel-cage
induction motor connected to a jogging-type, across-the-line motor starting
switch.
Figure 16—1 B shows the starter with the cover removed. Note in figure
16—1 that the connections and operation of the start and stop pushbuttons
are the same as those of a standard pushbutton station with start and stop
positions. The connections for the jog pushbutton, however, are more complex
and should be studied in detail. When the jog pushbutton is pressed, coil
M is energized, main contacts M close, and the motor starts turning. The
small auxiliary contacts M also close, but do not function as a sealing
circuit around the jog pushbutton because pushing the jog pushbutton also
opens the sealing circuit. As a result, as soon as the jog pushbutton is
released, coil M is deenergized and all M contacts open. Before the jog
pushbutton returns to its normal position, the sealing contacts M open
and thus the control circuit remains open. This control also can be used
for standard start-stop operations. In summary then, repeated closures
of the jog pushbutton start the motor momentarily so that the driven machine
can be inched or jogged to the desired position.
QUICK-STOP AC CONTROLLER (PLUGGING)
Some industrial applications require that three-phase motors be stopped
quickly. If any two of the line leads feeding a three-phase motor are reversed,
a counter torque is set up which brings the motor to a quick standstill
before it begins to rotate in the reverse direction. If the circuit is
interrupted at the instant the motor begins to turn in the opposite direction,
the rotor will just stop. This method of bringing a motor to a quick stop
is called plugging. The motor controller required to provide this type
of operation is an across-the-line magnetic motor starter with reversing
control and a special plugging relay. The plugging relay is belt-driven
from an auxiliary pulley on the motor shaft, or onto a through shaft motor.
The connections for a quick-stop ac controller are shown in figure 16—2A.
The controller itself is shown in figure 1 6—2B. When the start pushbutton
is pressed, relay coil F is energized. As a result, the small, normally
closed F contacts open. These contacts are connected in series with the
reverse coil, which locks out reverse operation. In addition, the other
small, normally open F contacts close and maintain the start pushbutton
circuit. When the start button is released, the circuit of coil F is maintained
through the sealing circuit, main contacts F close, and the rated three-phase
voltage is applied to the motor terminals. Then, the motor comes up to
speed and contacts PR of the plugging relay close.
When the stop pushbutton is pressed, the F relay coil is deenergized.
As a result of this action, the main F contacts for the motor circuit open
and disconnect the motor from the three-phase source. In addition, the
small F sealing contacts open, de-energizing the holding or sealing circuit
around the start pushbutton. Finally, the small F contacts in series with
the reverse relay close to their normal position and the reverse relay
coil is energized.

Fig. 16—1: A) Elementary diagram connections for a three-phase
motor with jogging B) Magnetic starter removed from enclosure.

Fig. 16—2 A) Elementary circuit with a plugging relay B) Ac full
voltage reversing starter, size 1.
The main R contacts now close to reconnect the three-phase line voltage
to the motor terminals. The connections of two line leads are interchanged.
The resulting reversing counter-torque developed in the motor brings it
to a quick stop. At the moment the motor begins to turn in the reverse
direction, contacts PR open due to the mechanical action of the PR relay
unit. Coil R is deenergized and the R contacts open and interrupt the power
supply to the motor. Since the motor is just beginning to turn in the opposite
direction, it comes to a standstill. The motor supplies the mechanical
power to drive a disk which causes contacts PR to close when the motor
is in operation.
DYNAMIC BRAKING WITH INDUCTION MOTORS
It should be recalled from the study of dc controllers that dynamic braking
is a method used to help bring a motor to a quicker stop without the extensive
use of friction brakes. In this application, dynamic braking means that
the motor involved is used as a generator. An energy dissipating resistance
is connected across the terminals of the motor after it is disconnected
from the line.
Dynamic braking also can be applied to induction motors. When the stop
pushbutton is pressed, the motor is disconnected from the three-phase source
and the stator windings are excited by a dc source. A stationary magnetic
field is developed by the direct current in the stator windings. As the
squirrel-cage rotor revolves through this stationary field, a high rotor
current is created. This rotor current reacts with the stationary field
of the stator to produce a countertorque that slows and stops the motor.
Figure 16—3 is a diagram of an ac motor installation with an across-the-line
magnetic motor starter and dynamic braking capability.

Fig. 16—3: diagram of an ac motor installation.
When the start pushbutton is pressed, coil M is energized. At this instant,
the main M contacts close and connect the motor terminals to the three-phase
source, and the auxiliary, normally open M contacts close and provide a
maintaining circuit around the start pushbutton. When relay coil M is energized,
the normally closed contacts M in the dc control circuit open, with the
result that both the main dc relay coil N and the time-delay relay coil
TR are deenergized and interlocks in the dc circuit open. The three-phase
volt age applied to the motor terminals causes the motor to accelerate
to the rated speed.
When the stop pushbutton is pressed, coil M is deenergized. At this moment,
a number of actions occur: 1) the main contacts M open and disconnect the
motor from the three-phase source; 2) the auxiliary M contacts open (these
contacts act as a maintaining circuit); 3) protective interlocks M in the
dc circuit close; and 4) the auxiliary, normally closed contacts M in the
dc control circuit close and energize the time-delay relay and the main
relay coil N. Energizing relay coil N causes the closing of contacts N
so that dc volt age is connected on the ac windings through a current-limiting
resistance. As a result, the motor comes to a quick stop. Following a definite
period after the motor has stopped, measured in seconds, relay coil TR
operates and opens contacts TR to cause coil N to become deenergized. Thus,
contacts N open and disconnect the motor windings from the dc source. The
controller now is ready for the next starting cycle.
Timing contacts are shown in their deenergized condition. Timers are either
on-delay or off-delay and are used in motor control work. The actual timer
mechanism varies depending on the vintage of the controller and the manufacturer.
See unit 13 for complete description of the timer symbols and operations.
RESISTANCE STARTER CONTROLLER
When a squirrel-cage induction motor is connected directly across the
rated line voltage, the starting current may be 300 percent to 600 percent
of the rated current of the motor. In large motors, this high current may
cause serious voltage regulation problems and overloading of industrial
power feeders.
The starting current of a squirrel-cage induction motor can be reduced
by using a resistance starter controller. This type of controller inserts
equal resistance values in each line wire at the instant the motor is started.
After the motor accelerates to a value near its rated speed, the resistance
is cut out of the circuit and full line voltage is applied to the motor
terminals.

Fig. 16—4 A) Definite lime acceleration with resistance starting
B) Two-point primary resistance starter rated at 25 hp, 600 V.
Figure 16—4A is a diagram of the circuit connections for a resistance
starter. A photo of this starter is figure 1 6—4B. When the start button
is pressed, main relay coil M is energized. The main contacts close and
connect the motor to the three-phase source through the three resistors
(R). The circuit for coil M is maintained through the small auxiliary contacts
(3 and 4) which act as a sealing circuit around the normally open start
push-button. When the main contacts of relay coil M are closed, a mechanical
device, called a definite time relay, is started. After a predetermined
time elapses, the definite time contacts close and energize coil R. Coil
R causes three sets of contacts to close and shunt out the three resistors.
Thus, the motor is connected directly across the rated line voltage with
no interruption of the power line (closed transition).
When the stop button is pressed, the circuits of both coil M and coil
R are opened. This causes the opening of the main contacts, the sealing
contacts, and the contacts which shunt the series resistors. As a result,
the motor is disconnected from the three-phase source.
The starting current in the resistance starter causes a relatively high
voltage drop in the three resistors. Because of this, the voltage across
the motor terminals at start is low. As the motor accelerates, the current
decreases, the voltage drop across the three resistors decreases, and the
terminal voltage of the motor increases gradually. A smooth acceleration
is obtained because of this gradual increase in the terminal voltage. However,
it may be unwise to select resistance starting for many starting tasks
because of the energy dissipated in the starting resistors.
The National Electrical Code provides guidelines on the selection of the
correct fuse sizes for starting protection on a branch motor circuit containing
a squirrel-cage induction motor with a resistance starter. In addition,
the Code specifies the running overload protection required, and the wire
sizes required on the branch motor circuit.
AUTOMATIC AUTOTRANSFORMER COMPENSATOR
The automatic autotransformer (figure 16—5A) compensator basically operates
in the same manner as a manual starting compensator. A manual compensator
is used to manually connect an autotransformer in series with the motor
during the starting cycle. A compensator is another name for an autotransformer
starter. By inserting an autotransformer, the voltage to the motor is reduced
and therefore the starting current is reduced. The starting current drawn
from the line is reduced. Because the autotransformer steps down the voltage
to the motor, the secondary (motor) current is higher than the primary
current. The result is that the current drawn from the line is much less
than if the motor were started with a reduced voltage through a resistor.
The automatic compensator has the advantage in that it can be pushbutton-controlled
from a convenient location. Figure 16—5B is a typical schematic wiring
diagram for an automatic autotransformer compensator.

Fig. 16—5: A) Reduced voltage starter, autotransformer type, with
a pneumatic timer. Elementary diagram of an autotransformer compensator
for starting an induction motor
If the start button is pressed, a circuit is established from line 1 through
the following devices to line 2: the normally closed stop button, the start
button, contacts TR (timing relay) to relay coil S (start coil), and the
normally closed overload contacts. Coil M is energized, closing the normally
open small contacts M to provide the maintaining circuit.
When coil S is energized, all contacts marked S close. The three autotransformers
are connected in wye across the three-phase line and supply reduced voltage
to the motor. The motor begins to accelerate to a value near the rated
speed.
As shown in figure 16—5B, a second circuit is established through the
timer relay by contacts TR. The timer relay begins operating as soon as
it is energized. After a definited timed period (figure 16—6) the timer
relay mechanically actuates all TR contacts. Coil S is deenergized as a
result. This coil was used to start the three-phase motor on reduced voltages.
At the same time, coil R (run coil) is energized and closes the running
contacts to apply the rated three-phase voltage to the motor terminals.
At this time, the motor is operating on full voltage. If the stop button
is pressed, the holding coil circuit for coils M and R opens. As a result,
the R contacts to the motor open and the motor stops. When coil R is deenergized,
the normally closed R contacts close the pilot motor circuit. The pilot
motor runs to set all TR contacts for the next starting cycle.
The National Electrical Code rulings for starting and running protection
also apply to motors operated with either a manually operated starting
compensator or an automatic autotransforrner compensator.

Fig. 16—6 Cross section of an ac on-delay timer, which provides
time delay after the coil is energized. It is shown with the coil energized
and the timer timed out. Schematic wiring symbols are shown (de-energized
positions) for various portions of the timer.
AUTOMATIC CONTROLLER FOR WOUND-ROTOR INDUCTION MOTORS
Manual speed controllers, such as the faceplate type or the drum type,
may be used to provide speed control for wound-rotor induction motors in
industrial applications. If the resistance in the rotor circuit of a wound-rotor
induction motor is to be used only on starting, then an automatic controller
may be used, figure 16—7. In this case, resistors in the rotor circuit
are automatically removed by contactors arranged to operate in sequence
at definite time intervals.

Fig. 16—7: Elementary diagram of an automobile controller for
a wound-rotor induction motor
As shown in figure 16—7, when the start button is pressed, the main relay
coil M is energized. The main contacts are closed to connect the stator
circuit of the motor directly across the three-phase line voltage. All
of the resistance of the controller is inserted in the secondary circuit
of the motor as it begins to accelerate.
After the start button is released to its normally open position, the
small auxiliary contacts M act as a maintaining circuit to keep the circuit
of coil M closed. Contacts A are held open for a timed period (seconds)
by a mechanical or electronic device (figure 16—8A, B, and C). When the
A contacts close, coil N is energized through the normally closed contacts
C, and all N contacts close to shunt out the R resistors in the rotor circuit.
Contacts B also are held open for a definite number of seconds by a mechanical
or electronic device. When B contacts close, coil 0 is energized, all 0
contacts close, and all resistance is cut out of the rotor circuit. At
the same time, the C contacts open and deenergize coil N which then opens
contacts N. The D contacts then close and maintain a closed circuit through
coil 0.
When the stop pushbutton is pressed, relay coil M is deenergized, and
contacts M open to disconnect the motor from the line. Coil 0 also is deenergized
and contacts 0 open, with the result that all of the resistance is inserted
in the rotor circuit for the next starting cycle.
The National Electrical Code regulations for wire size, starting overload
protection, and running overload protection also apply to both manual speed
controllers and automatic controllers used with wound-rotor induction motors.

Fig. 16—8 A) Solid-state timing relays with different plug-in
program keys.

Fig. 16—8 B-C) Solid-state timing relays with different plug-in
program keys:
1. STANDARD INDUSTRIAL CONTROL RELAY MOUNTING
2. REMOVABLE TIMER COVER PROTECTS TIME DELAY AND MODE SETTING
3. LED (LIGHT EMITTING DIODE) TIMING INDICATOR
4. CONVERTIBLE TIME DELAY MODE SHOWS THROUGH COVER
5. ONE N.O. AND ONE N.C. TIMED NEMA B150 HARD OUTPUT CONTACTS (10 AMPERE
CONTINUOUS)
6. TERMINALS CLEARLY MARKED
7. FIVE TIMING RANGES FROM 0.05 SECONDS TO 10 HOURS
8. MARKING AREA
9. SELF-LIFTING PRESSURE WIRE CONNECTORS
10. OPTIONAL INSTANTANEOUS NEMA B150 HARD OUTPUT CONTACTS (10 AMPERE CONTINUOUS)
WYE-DELTA CONTROLLER
Figure 16—9A shows a simple method by which a three-phase, delta-connected
motor can be started on reduced voltage by connecting the stator windings
of the motor in wye during the starting period. Figure 16—9B shows the
actual starter. After the motor accelerates, the windings are reconnected
in delta and placed directly across the rated three-phase voltage.

Fig. 16—9 A) Elementary diagram of wye-delta motor starting B)
Photo of wye delta, 200 hp, closed transition.
When the start button is pressed, the main M contacts close, and relay
coil Y and time-delay relay TR are energized. Coil Y causes contacts Y
to close and the windings of the motor are connected in wye. If the line
voltage is 230 volts, the voltage across each winding is:
230/1.73 = 133 volts
The voltage across each winding is only 58 percent of the line voltage
when the windings are connected in wye at the start position. (See 3-phase
Voltage)
After a definite period of time, the time-delay relay TR opens the circuit
of relay coil Y and the Y. contacts open.
Then, the time-delay relay TR closes the circuit of relay coil D. All
D contacts are closed and the motor winding connections are changed from
wye to delta. Full line volt age is applied to the motor windings and the
motor operates at its rated speed.
Motors started by a wye-delta controller must have the leads of each phase
winding brought out to the terminal connection box of the motor. In addition,
the phase windings must be connected in delta for the normal running position.
NOTE: The electrician should never attempt to operate a three-phase, wye-connected
motor with this type of controller. This is due to the fact that there
will be an excessive voltage applied to the motor windings in the run position
when the windings are connected in delta by the controller.
AUTOMATIC CONTROLLER FOR SYNCHRONOUS MOTORS
Synchronous motors may be started by means of an across-the-line magnetic
motor starting switch, a manual starting compensator, or an automatic starting
compensator. Dynamic braking may be provided by the controller.
Figure 16—10 is a diagram of the connections for a synchronous motor controller
with dynamic braking. When the start button is pressed, main relay coil
M is energized. The four normally open M contacts close and the two normally
closed M contacts open. Three-phase voltage is applied to the motor terminals.
When the motor accelerates to a speed near the synchronous speed, the dc
field circuit is energized by secondary controls.
When the stop button is pressed, main relay coil M is deenergized. The
M contacts open and disconnect the motor terminals from the three-phase
line. The two normally closed M contacts reconnect the motor windings through
the resistors and the dc field remains energized. As a result, the synchronous
motor acts as an ac generator and delivers electrical energy to the two
R resistors. The use of this type of controller results in a more rapid
slowing of a synchronous motor.
The National Electrical Code provides guidelines for branch-circuit fuse
protection and running overload protection for branch circuits feeding
three-phase synchronous motors, and for allowable conductor sizes for branch
circuits feeding synchronous motors. Local building and electrical code
authorities should be consulted before installations are made with motors
and controllers which do not comply with National Electrical Code rulings.

Fig. 16-10 Synchronous motor controller with dynamic braking
SOLID-STATE REDUCED VOLTAGE STARTERS
Solid-state devices and equipment are used for reduced voltage motor starting,
electrical energy saving control circuits, variable speed drives, motor
protection and other applications. A motor starter consists of a control
circuit, a motor power circuit, and protective devices for the wiring and
the motor. The functions of a starter are performed by contactors and overload
relays in electromechanical motor starters. In solid-state starters, the
control functions are performed by semiconductors. They are controlled
by integrated circuits and microprocessors to provide the protective functions,
operating instructions, and control.
Construction and Operation
The solid-state reduced-voltage starter provides a smooth, stepless acceleration
of a three-phase induction motor. This is accomplished by gradually turning
on six power SCRS (silicon controlled rectifiers). Two SCRs per phase are
connected in a back-to-back or reverse parallel arrangement, figure 16—11.
The SCRs are mounted on a heat (dissipating) sink to make up a power pole
(phase). Each power pole contains the gate firing circuits as discussed
in unit 13. An integrated thermal sensor is also provided to deenergize
the starter if an over-temperature condition exists.
The firing circuitry on each power pole is controlled by a logic module.
These modules monitor the starter for correct start up and operating conditions.
Some motor starters provide a visual indicator of the starting condition
through the use of light-emitting diodes (LEDs).
The SCRs are connected back to back so that they may pass ac and control
the amount of voltage. The current-limiting starter is a common type; it
is designed to maintain the motor current at a constant level throughout
the acceleration period. A cur rent-limit potentiometer adjustment is provided
to preset this current. A starter with current ramp acceleration is designed
to begin acceleration at a low current level and then increase the current
during the acceleration period.
As indicated in figure 16—11, this starter includes both start and run
contactors. The start contacts are in series with the SCRs; the run contacts
are in parallel with the combi nation of SCRs and start contacts. When
the starter is energized, the start contacts close. The motor acceleration
is then controlled by phasing-on the SCRs, When the motor reaches full
speed, the run contacts close and the motor is connected directly across
the lines (closed transition). At this point, the SCRs are turned off and
the start contacts open. Under full speed running conditions, the SCRs
are out of the circuit, eliminating SCR power losses during the run cycle.
This feature saves energy; it also guards against possible damage due to
overvoltage transients. With the starter in the deenergized position, all
contacts are open, isolating the motor from the line. This open circuit
condition protects against accidental motor rotation as a result of SCR
misfiring and/or SCR damage caused by overvoltage transients. A solid-state
reduced-voltage starter is shown in figure 16—12. Field connections are
very similar to those for electromechanical starters.

Fig. 16—11 Solid-state reduced voltage starter power circuit.
Reduced Voltage Operation To reduce the voltage applied to the motor in
a solid-state starter, the SCRs can be turned on by the “gate” electrode
for any desired part of each half cycle. Usually the SCRs turn off as the
current wave reaches zero. They stay off until gated on again in the next
half cycle. Some devices can vary the switching and timing. By switching
the controlled current gating, the effective ac voltage can be varied to
the motor. This voltage can be varied from zero to full voltage as required.
The voltage is applied at some preset minimum value that can start the
motor rotating. As the motor speed builds up, the SCR “on” time is gradually
increased. The voltage is increased until the motor is placed across the
line at full voltage. Mechanical shock is reduced and the current inrush
can be regulated and controlled as desired (figure 16—13). The solid-state
reduced-voltage starter can replace any of the electromechanical starters
already described for reduced voltage starting.

Fig. 16—12 Solid-state reduced voltage starter power circuit.

Fig. 16—13 SCR controller section, the regulating part of the
starter. The controller determines to what degree the SCR’s should be phased
on, thereby controlling the voltage applied to the motor.
CODE REFERENCES FOR MOTOR CONTROLLERS
The following sections of the National Electrical Code are concerned with
motor controllers and remote control circuits.
1. Sections 430-8 and 430-9 refer to the identification of motors and
controllers with respect to controller nameplate ratings and terminal markings.
2. Section 430-C is concerned with overload protection.
3. Section 430-37 gives the number of running overcurrent relays required
for different electrical systems.
4. Section 430-D is concerned with branch-circuit protection.
5. Sections 430-71 to 430-74 are concerned with the control circuits of
controllers.
6. Sections 430-81 to 430-90 are concerned with controller installations.
7. Sections 430-101 to 430-113 cover motor disconnecting means.
AC ADJUSTABLE SPEED DRIVES
Adjustable speed drives have a flexibility that is particularly useful
in specialized applications. For this reason, these drives are widely used
throughout industry for convey ors used to move materials, hoists, grinders,
mixers, pumps, variable speed fans, saws, and crushers. The advantages
of ac drives include the maximum utilization of the driven equipment, better
coordination of production processes, and reduced wear on mechanical equipment.
The ac induction motor is the major converter of electrical energy into
another usable form. About two-thirds of the electrical energy produced
in the United States is delivered to motors.
Much of the power that is consumed by ac motors goes into the operation
of fans, blowers, and pumps. It has been estimated that approximately 50%
of the motors in use are for these types of loads. Such loads are particularly
appropriate to look at for energy savings. Several alternate methods of
control for fans and pumps have been developed and show energy savings
over traditional methods of control.
Fans and pumps are designed to meet the maximum demand of the system in
which they are installed. Often, however, the actual demand varies and
may be much less than the design capacity. Such conditions are accommodated
by adding outlet dampers to fans or throttling valves to pumps. These controls
are effective and simple, but affect the efficiency of the system. Other
forms of control have been developed to adapt machinery to varying demands.
These controls do not decrease the efficiency of the system as much as
the traditional methods of control. One of the newer methods is the direct
variable speed control of the fan or pump. This method produces a more
efficient means of flow control compared to the other existing methods.
In addition to a tangible reduction in the power required to operate equipment
and machinery resulting from the use of adjustable speed drives, other
benefits include extended bearing life and pump seal life.
WOUND ROTOR AC MOTORS
Wound rotor motor drives use a specially constructed ac motor to accomplish
speed control. The windings of the motor rotor are brought out of the motor
through slip rings on the rotor shaft. Figure 16—14 shows an elementary
diagram of a wound rotor motor with an adjustable speed drive. These windings
are connected to a controller which places variable resistors in series
with the windings. The torque performance of the motor can be controlled
using these variable resistors.
Wound rotor motors are more common in the larger sizes, in the range of
300 horse power and above.

Fig. 16—14 Elementary diagram of an adjustable speed drive wound
rotor motor
Features of Wound Rotor Motors
Wound rotor motors have the following advantages which make them suitable
for a variety of applications:
• Cost — the initial cost is moderate for the high horsepower units.
• Control — not all the power need be controlled, resulting in a moderate
size and simple controller.
• Construction — the simple construction of the motor and control lends
itself to maintenance without the need for a high level of training.
• High inertia loads — the drive works well on high inertia loads.
Disadvantages of Wound Rotor Motors
• Custom motor-. the motor has a rotor wound with wire, slip rings, and
is not readily available.
• Efficiency — the drive does not maintain a high efficiency at low speeds.
• Speed range — the drive usually is limited to a speed range of two to
one.

Fig. 16—15 Spider rotor coil magnet rotated within a steel drum
TYPES OF ADJUSTABLE SPEED DRIVES
Several types of variable speed drives can be used with wound rotor induction
motors. These drives are eddy current (magnetic) drives, variable pitch
drives, and adjust able frequency drives.
Eddy Current (Magnet) Drives
The eddy current drive couples the motor to the load magnetically (figure
16—15). The electromagnetic coupling is a simple way to obtain an adjustable
output speed from the constant input speed of squirrel cage motors. There
is no mechanical contact between the rotating members of the eddy current
drive; thus, there is no wear. Torque is transmitted between the two rotating
units by in electromagnetic reaction created by an energized rotating coil
winding. The rotation of the ring with relation to the electromagnet generates
eddy currents and magnetic fields in the ring. Magnetic interaction between
the two units transmits torque from the motor to the load. The slip between
the motor and the load can be controlled continuously with great precision.
Torque can be controlled using a thyristor in an ac or dc circuit, or
by using a rheostat to control the field through slip rings. When the eddy
current drive responds to an input or command voltage, the speed of the
driven machine changes. A further refinement can be obtained in automatic
control to regulate and maintain the output speed. The magnetic drive can
be used with nearly any type of actuating device or transducer that can
pro vide an electrical signal. For example, the input can be provided by
static controls and sensors which detect liquid level, air and fluid pressures,
temperature, and frequency.
Magnetic eddy current drives are used for applications requiring an adjustable
speed such as cranes, hoists, fans, compressors, and pumps (figure 16—16).
Variable Pitch Drives
The speed of an ac squirrel cage induction motor depends upon the frequency
(hertz) of the supply current and the number of poles of the motor. The
equation expressing this relationship is:
RPM = 60xHertz/Pairs of Poles

Fig. 16—16 Two magnetic drives driven by 100-hp Induction motors
mounted on top.

Fig. 16—17 Variable pitch pulley method of obtaining continuously
adjustable speed from constant speed shaft.
A frequency changer may be used to vary the speed of this type of motor.
A possible method is to drive an alternator through an adjustable mechanical
speed drive.
The voltage is regulated automatically during frequency changes. An ac
motor drives a variable cone pulley or sheave, which is belted to another
variable pulley on the output shaft (figure 16—17). When the relative diameters
of the two pulleys are changed, the speed between the input and the output
can be controlled. As the alternator speed is varied, the output frequency
varies, thereby varying the speed of the motor, or motors, connected electrically
to the alternator supply.
Adjustable Frequency AC Drives
Adjustable frequency (static solid-state) drives are also commonly called
inverters. The power conversion losses are greatly reduced when using these
transistor controllers for adjustable speed drives. They are available
in a range of horsepowers from fractional to 1,000 hp. Adjustable frequency
drives are designed to operate standard ac induction motors. This allows
them to be added easily to an existing system. (Figure 16-18).
Where energy saving is a major concern the drives are ideal for pumping
and fan applications. They are also used for many process control or machine
applications where performance is a major concern. Many adjustable speed
precision applications were limited to the use of dc motors. By using adjustable
frequency controllers with optional dynamic braking, standard squirrel
cage motors can now be used in these applications. Municipal, industrial,
commercial and mining applications include: sewage, waste water, slurry
and booster pumps, ventilation and variable air volume fans; conveyors;
production machines and compressors.

Fig. 16—18 Controller operation
AC VARIABLE SPEED/VARIABLE FREQUENCY CONTROLS
AC motors are designed to run at a specific full load speed. This design
speed takes into account various losses in the motor including copper losses
of the stator and the rotor and other losses such as iron losses, friction,
and windage. The end result is some speed less than synchronous speed,
which is calculated by the following formula:
Synchronous RPM = 120 Freq/ # poles
Use this formula to determine the synchronous speed of a motor if the
number of poles and the applied frequency are known. The number of poles
is usually fixed and the frequency of a normal power feed in the U.S.A.
is 60 Hz. Therefore, to operate an ac motor at other than its design speed,
either the number of poles or the frequency must be altered. Some adjustable
speed motors are able to reconnect the poles or connect a separate winding
of poles to establish other set speeds. To vary the speed of an ac motor
over a wide range of speeds, the applied frequency is altered.
There are two basic techniques for altering the frequency of the applied
power through electronic means. Both techniques use the principle of rectifying
the three-phase ac 60 Hz input power to a dc supply (see figure 16—19).
Then filter the dc to provide smooth dc to the inverter section of the
electronic controller. The amplitude of the output voltage must change
with the frequency, because at low frequency the impedance of the motor
is low and the voltage must also be reduced to prevent overheating of the
motor. Conversely, as the frequency is raised above 60 Hz, the motor’s
impedance is increased and voltage must also increase to maintain motor
torque.
One method of speed control is the variable voltage inverter. The dc voltage
applied to the inverter is adjusted, then the pulse is modified to create
various frequencies (see figure 16—18).
The other and more common method is known as pulse width modulation, or
PWM. The voltage output of the dc-to-ac inverter is really a series of
pulses of DC that is stepped to produce a “staircase” approximation of
the sine wave at the frequency desired, to control the motor speed. The
controller uses a sensor and a set point to determine output frequency
and the desired set speed.
The control modules adjust the output of a dc voltage control module as
it adjusts the output of the frequency control module. The frequency control
module typically drives the output power controller, there are two of these
for each of the three phases; one controls the positive half cycles of
one phase and one controls the negative half cycles of the same phase.
Six output modules are required for three phases.
When connected to a motor the stepped output wave form appears close to
a sine wave because of the motor’s inductance. Frequency then determines
the speed of the motor in conjunction with the set number of poles.

Fig. 16—19 Three-phase, full-wave rectifier with connected load.
INTRODUCTION TO PROGRAMMABLE CONTROLLERS
Modern motor control requires more exact timing and faster, more consistent
operations than those provided by the older electromechanical relays and
timers. Because modern manufacturing requirements also rely on flexibility
of systems, a fast change sys tem was needed that didn’t require extensive
redesign, building, hand wiring, and testing to create a new motor control
scheme.

Fig. 16—20 Adjustable frequency motor drive controller.
Along with this change in needs, the microprocessor was improved to make
it more reliable in industrial environments and more trouble-free in operation.
The combination of these events produced the Programmable Controller, or
PC.
Various versions of the PC are made by different manufacturers and have
various capabilities. However, all programmable controllers have at least
three basic components:
The first is a processor, which is a microprocessor that contains the
instructions and makes the decisions; the second component is an input/output
section, which receives input information from the process it is controlling,
and connects it to the controller in the proper format. It also takes the
output from the controller and interfaces to the real world of control
devices; the third main component is the programmer. This is the operator’s
access to the controller. The programs are written in ladder logic style,
which is familiar to most electricians. This familiarity was the factor
that allowed the programmable controller to be so widely accepted as a
control system. Controls were easily converted and adapted by current electricians
without having to learn extensive new microprocessor programming language.
PCs are used where the control system is likely to be changed frequently
and usually where there are multiple functions for the controller to monitor,
compare, count, time, or operate. These conditions make the use of a PC
economical and practical.
Large control systems may have various input/output cards that must be
coordinated according to the “field wiring.” For example: ac and dc voltage
at various levels, Transistor-Transistor Logic (TTL), Input/Output (10),
Analog I/O, Thermocouple or Binary Coded Decimal (BCD). Figure 16—21 is
a programmable controller.
The intent of this guide is not to teach programming of the PC, but to
familiarize the electrician with the possibility of motor control using
the PC. A Technician ‘s Guide to Programmable Controllers, by Richard A.
Cox, Delmar Publishers Inc., is an excellent reference to gain further
“generic” information.

Fig. 16—21 Programmable controller, with one input/output card
removed
SUMMARY
There are many methods used to start, stop, jog, and reverse three-phase
motors. The basic operations generally use a magnetic controller to supply
power to the motor. The reversing controller is used in the plugging operation
to momentarily reverse the power and therefore bring the motor to a quick
stop. Dynamic braking can also be used to stop an ac motor by applying
dc to the motor field. Various methods of reducing the starting current
to the motor employ the application of reduced voltage at the motor terminals
during the starting period. Resistance or reactance can be inserted in
series with the motor to reduce the voltage. An autotransformer may be
used to reduce the applied voltage. Wound-rotor motors use secondary resistors
to keep the starting current to a minimum. Wye-delta starters can be used
to reduce the starting current to the motor by changing the configuration
of the connections. Solid state starters are now being installed to reduce
the inrush current and to control the speed and the stopping characteristics.
Variable-frequency drives use electronics to control the frequency to
the motor and therefore control the speed of the motor. Many motor-control
schemes can be developed with the use of a programmable controller. This
electronic equivalent of a relay system is used to provide exact timing
and complex, but changeable, control through the use of a microprocessor-based
system.
REVIEW / QUIZ:
1. What is meant by the term jogging?
2. What is meant by the term plugging?
3. How is dynamic braking applied to an ac induction motor? ___
4. How is dynamic braking applied to a synchronous motor? ___
5. Draw a schematic diagram of the connections for the control circuit
of an across-the line magnetic motor switch with jogging capability. Include
the main relay coil, the pushbutton station with start, jog, and stop pushbuttons,
and the sealing contactor.
6. What identifying information should appear on a motor controller so
that the controller complies with the requirements of the National Electrical
Code?
7. Draw a schematic diagram of an automatic controller used for a three-phase,
wound-rotor induction motor.
8. A three-phase, squirrel-cage induction motor has the following ratings:
15 horse power, 230 volts, 42 amperes per terminal, 40 degrees Celsius,
and code classification F. In the spaces in the following table, insert
the correct values for fuse protection and running overcurrent protection
for this motor when used with each of the types of controllers listed.
Type of Controller |
Fuse Protection: Nontime-delay
|
Fuse Protection: Time-delay |
Running Overcurrent Protection |
a. Resistance starter |
|
|
|
b. Automatic autotransformer compensator |
|
|
|
c. Across-the-line magnetic motor starting
switch with jogging capability |
|
|
|
d. Across-the-line magnetic motor starting
switch with plugging capability |
|
|
|
9. What is the purpose of an automatic autotransformer starting compensator?
10. What is the purpose of an automatic controller used with wound-rotor
induction motors?
11. A wye-delta controller starts the motor at …
a. 173 percent of the line voltage.
b. 58 percent of the line voltage.
c. full line voltage.
d. 25 percent of the line voltage.
12. A three-phase, wye-connected motor
a. should never be started by a wye-delta controller.
b. should always be started by a wye-delta controller.
c. can be started by a wye-delta controller if proper timers are used.
d. can be started by a wye-delta controller if proper pushbuttons are
used.
13. How are SCRs connected to pass and control ac?___
14. If a solid-state controller has contactors in the power circuit, in
what position are the contacts of start and run in the off position? Why?
15. Why are adjustable speed drives used? _______
16. List the types of ac adjustable speed drives. ______
17. How is the speed of the wound rotor motor adjusted?
18. How is the eddy current drive coupled to the load? ____
19. How is the ac frequency varied in the mechanical method drive? ____
20. What is the formula for calculating ac motor speed?
21. What basic devices are provided in the adjustable frequency drive?
____
22. With an apparent high degree of skill required to maintain an adjustable
frequency drive control, how does the plant electrician repair one? ___ |