|
OBJECTIVES
After studying this unit, the learner will be able to:
• list several factors to be considered when selecting and installing
electric motor control equipment.
• explain the purpose of a contactor.
• describe the basic operation of a contactor and relay.
• list the steps in the operation of a control circuit using start and
stop pushbuttons.
• interpret simple automatic control diagrams.
• draw a simple magnetic control circuit.
Motor control was a simple problem when motors were used to drive a common
line shaft to which several machines were connected. In this arrangement,
it was necessary to start and stop only a few times daily.
With individual drive, however, the motor is an integral part of the machine
and the motor controller must be designed to meet the needs of the machine
to which it is connected.
As a result, the modem motor controller does not just start, stop, and
control the speed of a motor. The controller may also be required to sense
a number of conditions, including changes in temperature, open circuits,
current limitations, overload, smoke density, level of liquids, or the
position of devices. Manual control is limited to pressing a button to
start or stop the entire sequence of operations at the machine or from
a remote position.
The electrician must know the symbols and terms used in automatic control
diagrams to be able to wire, install, troubleshoot, and maintain automatic
control equipment.
CLASSIFICATION OF AUTOMATIC CONTROLLERS
Purpose
Factors to be considered in selecting motor controllers include what types
of starting, stopping, reversing, running, speed and sequence control,
and protection are required.
Operation
The motor may be controlled directly or manually by an operator using
a switch or a drum controller. Remote control uses contactors, relays,
and pushbuttons, sensors and possibly electronics.
CONTACTORS

Fig. 7-1a DC magnetic relay; Fig. 7-1b DC operated relay.
Contactors, or relays (figure 7-1) are required in automatic controls
to transmit varying conditions in one circuit to influence the operation
of other devices in the same or another electrical circuit. Relays have
been designed to respond to one or more of the following conditions:
voltage
current
current direction
power direction
phase angle
phase failure |
over-voltage
overcurrent
differential current
volt-amperes
power factor
impedance
temperature |
under-voltage
undercurrent power (watts)
frequency
phase
rotation
speed |
Magnetic switches are widely used in controllers because they can be used
with remote control, and are economical and safe.
A relay or contactor usually has a coil which can be energized to close
or open contacts in an electrical circuit. The coil and contacts of a relay
are represented by symbols on the circuit diagram or schematic of a controller.
Symbols commonly used to represent contactor elements are shown in figure
7-2.

Fig. 7-2 Schematic symbols for contactor elements.
If the control coil is connected in series in the motor power circuit,
the heavy line symbol shown at the left of figure 7-2 is used. If the coil
is connected in parallel (shunt), the light line symbol is used.
A series coil has a large current carrying conductor with few turns designed
to carry large currents. A shunt coil has a small wire size with many turns;
it carries small currents. It is possible for a series coil and a shunt
coil to have the same ampere turns, resulting in similar magnetic results.
Contacts which are open when the coil is deenergized are known as normally
open contacts and are indicated by two short parallel lines. Contacts which
are closed when the coil is deenergized are called normally closed contacts
and are indicated by a slant line drawn across the parallel lines.
To minimize heavy arcing which burns the contacts, a dc contactor usually
is equipped with a blowout coil and an arc chute. Figure 7-3 shows a magnetic
contactor which is provided with a blowout coil and an arc chute.

Fig. 7-3 Magnetic blow out coils magnetically move the
arc away from the contacts: arc barriers; power contacts.
When a heavy current is broken by the contacts of the contactor, an arc
occurs. Figure 7-4 illustrates the behavior of the arc as it is quickly
extinguished by the electromagnetic and thermal action of the magnetic
blowout coil and arc chute.

Fig. 7-4 Behavior of arc with correctly designed blowout: ARCING
HORN; ARC CHUTE; STATIONARY TIP
PUSHBUTTONS
Pushbutton stations (figures 7-5A and B), are spring-controlled switches
and, when pushed, are used to complete motor or motor control circuits.
Figure 7-5B shows multiple control stations, with pushbuttons, selector
switches, and pilot indicating lights. Note the “mushroom” stop button
for easy access. This is for convenience and safety.

Fig. 7-5 Pushbutton stations

Fig. 7-6 Symbols for pushbutton contacts: NORMALLY OPEN; NORMALLY
CLOSED; OPEN AND CLOSED
The symbols used in schematic, drawings to represent momentary pushbutton
contacts are given in figure 7-6. Contacts can either be normally-open
or normally-closed. This is the normal condition when there is no mechanical
actuation of the contacts. In the pushbuttons shown in figure 7-6, the
contacts are referred to as momentary contacts. This simply means that
the contacts change from their normal condition to the opposite condition
momentarily when mechanical actuation is applied, and then change back
to the normal condition when the actuator is removed. Some contacts are
designated as maintained contacts. This means that the contacts will stay
as activated (held mechanically) until returned to their original position.
See the glossary for the complete set of symbols.
TYPICAL CONTROL CIRCUIT
Figure 7 - 7 is an elementary control circuit with start and stop buttons
and a sealing circuit. The following sequence describes the operation of
the circuit. The typical control circuit uses an electromagnetic coil to
move sets of contacts. The contacts move to open and close the power circuit
to the motor, and also open and close contacts in the control circuit.
The control contacts provide a sealing circuit in parallel to the start
momentary contacts. This parallel circuit is referred to as the sealing
circuit. It seals a current path around the normally open start button
contacts. The circuit operation is as follows:
1. When the start button is pressed to close contacts 2-3, current flows
from L1 through normally closed contacts 1 - 2 of the stop button, through
the closed contacts 2 - 3 of the start button, and through coil M to Line
L2.

Fig. 7-7 A control circuit with start and stop buttons and
sealing circuit
2. The current in coil M causes the contact M to close. Thus, the sealing
circuit around contacts 2-3 of the start button closes. The start button
may now be released, and even though the spring of the pushbutton opens
contacts 2-3, coil M remains energized and holds contacts M closed to maintain
a sealing circuit around the normally open contacts 2-3 of the start button.
Coil M, being energized, also closes M contacts in the power circuit to
the motor (not shown).
3. If the stop button is momentarily pressed, the circuit is interrupted
at contacts 1 - 2 and coil M is deenergized. Contacts M then open and coil
M cannot be energized until the start button again closes contacts 2 -
3.
SUMMARY
The basic automatic control circuit is used to control larger motors and
to control them through electromagnetic relays. This allows the operation
to be remotely located and the contactor to be located near the motor.
The basic principle uses a momentary-contact switch to close a circuit
to a magnetically-operated relay.
QUIZ
Select the correct answer for each of the following statements.
1. Early motor installations consisted of:
a. individual drives.
b. a common line shaft drive.
c. automatically controlled motor drives.
d. remotely controlled motors.
2. Individual motor drives require:
a. single-phase motors.
b. automatic controllers.
c. speed rheostats.
d. gear heads.
3. Automatic dc motor controllers are designed to respond to changes in
temperature, open circuits, current limitations, and:
a. wire size. c. speed acceleration.
b. fuse rating. d. brush assembly.
4. Interpretation of automatic control circuits requires the recognition
of:
a. color. c. ratings
b. electrical circuit symbols. d. parallel circuits
5. A relay symbol shows the:
a. number of turns in a coil.
b. relay current rating.
c. relative position of the component parts.
d. size of the contacts.
6. A relay is classified as a piece of electrical equipment with at least
one:
a. coil.
b. resistor.
c. coil operating one contact.
d. coil operating two contacts.
7. Normally open contacts are
a. open at all times.
b. open when the relay coil is deenergized.
c. open when the relay coil is energized.
d. contacts that open a circuit.
8. Normally closed relay contacts are represented by the symbol:

9. A sealing circuit bypasses:
a. the armature circuit.
b. the field circuit.
c. the ON pushbutton contacts.
d. the relay coil.
10. Elementary control diagrams are read from:
a. top to bottom. c. right to left.
b. bottom to top. d. field to armature circuit. |