|
OBJECTIVES
After studying this unit, the learner will be able to:
• explain the operation of the counter emf method of acceleration for
a direct-current motor.
• make use of elementary wiring diagrams, panel wiring diagrams, and external
wiring diagrams.
• explain the ratings of starting and running protection devices.
• describe the operating principles of dc variable speed motor drives.
• state how above and below dc motor speeds may be obtained.
• list the advantages of dc variable speed motor drives.
• describe how solid-state devices may replace rheostats.
• make simple drawings of dc motor drives.
• list the advantages of using thyristors.
Although manual starters are still used, most industrial applications
use automatic motor control equipment to minimize the possibility of errors
in human judgment. To install and maintain automatic motor control equipment
the electrician must be familiar with three kinds of electrical circuit
diagrams:
• elementary wiring diagram
• panel wiring diagram
• external wiring diagram
The elementary wiring diagram uses symbols and a simple plan of connections
to illustrate the scheme of control and the sequence of operations.
The panel wiring diagram shows the electrical connections throughout all
parts of the controller panel and indicates the external connections. All
of the control elements are represented by symbols but are located in the
same relative positions on the wiring diagram that they actually occupy
on the control panel. Because of the maze of wires shown on the panel wiring
diagram, it is difficult to use for troubleshooting or to obtain an under
standing of the operation of the controller. For this reason, the elementary
wiring diagram presents the sequence of operations of the controller and
the panel diagram is used to locate problems and failures in the operation
of the controller.
The external wiring diagram shows the wiring from the control panel to
the motor and to the pushbutton stations. This diagram is most useful to
the worker who installs the conduit and the wires between the starter panel
and the control panel and motor.
COUNTER-ELECTROMOTIVE FORCE METHOD OF MOTOR ACCELERATION CONTROL
The counter emf across the armature is low at the instant a motor starts.
As the motor accelerates, this counter emf increases. The voltage across
the motor armature can be used to activate relays which reduce the starting
resistance when the proper motor speed is reached.
Starting and Running Protection for a Counter Emf Controller
Starting protection for a counter emf controller is provided by fuses
in the motor feeder and branch-circuit line of the motor circuit. These
fuses are rated according to Article 430 of the NEC.
Running protection for a counter emf controller is provided by an overload
thermal element connected in series with the armature. The thermal element
is rated at 115 to 125 percent of the full-load armature current. As covered
in NEC Sections 430—32 and 430—34, if the current exceeds the percent of
the rated armature current value, heat produced in the thermal element
causes the bimetallic strip to open or trip the thermal contacts which
are connected in the control circuit. The value of current during the motor
startup period does not last long enough to heat the thermal element sufficiently
to cause it to open.
COUNTER EMF MOTOR CONTROL CIRCUIT
Starting the Motor (Refer to Figure 8—1A)
Close the main line switch before pressing the start button. After the
start button is pressed, control relay M becomes energized. The control
circuit is now complete from L1 through the thermal overload (OL) contacts
6—7, through the start button contacts 7—8, through the normally closed
stop button contacts 8—9 to L2. The lower auxiliary sealing contacts 7—8
of relay M also close and bypass the start button. As a result, the start
button may be released without disturbing the operation.
When the main contacts 2—3 of contactor M are closed, the motor armature
circuit is complete from L1 through overload thermal element contacts 1—2,
through contacts 2—3 of relay M, through the starting resistor, and through
armature leads 4—5 to L2. The shunt field circuit F1 — F2 is connected
in parallel with the armature circuit. Contacts 3-A of counter emf contactor
A remain open at startup because a high inrush current establishes a high
voltage drop across resistor 3—4. This leaves only a small voltage drop
across the armature and “A” contactor coil until acceleration is achieved.

Fig. 8—1A. Elementary diagram of a dc counter emf controller
Connecting the Motor across the Line
The counter emf generated in the armature is directly proportional to
the speed of the motor. As the motor accelerates, the speed approaches
the normal full speed and the counter emf increases to a maximum value.
Relay A is calibrated to operate at approximately 80 percent of the rated
voltage. When contacts 3—4 of relay A close, the starting resistance 3-4
is bypassed and the armature is connected across the line.
Running Overload Protection
A thermal overload relay contains two circuits. One circuit is in series
with the armature and has the armature current flowing through its thermal
sensor or heating element. The second circuit of the overload relay is
the control circuit with a control contact. If the contact opens, because
of excessive heat in the thermal heater, the control circuit will be interrupted,
and stop the motor. A thermal overload relay unit is shown in figure 8—1B.
The schematic diagram is shown in figure 8—1A.
When the load current of the armature exceeds the rated allowable percent
of the full load current, the overload thermal element (points 1—2) heats
up and opens contacts 6—7 in the control circuit. Control relay M is deenergized
and main contacts 2—3 of M open and disconnect the motor from the line.

Fig. 8—1B. Bi-metal disk flexes as it is heated and opens motor
control circuit. Photo of bimetal disk, solder-pot type melting alloy,
bi-metal strip. heater: bimetal disk, heater: melting alloy, heater: bimetal
strip
Stopping the Motor
When the stop button is pressed the control circuit is broken at points
8-9. The same shutdown sequence occurs as in the case of the overload condition
discussed previously. The sealing circuit 7—8 is broken in each case.
The advantage of this type of automatic starter is that it does not supply
full voltage across the armature until the speed of the motor is correct.
The starter eliminates human error which may result from the use of a manual
starter.
PANEL WIRING DIAGRAM
Figure 8—2 shows the same counter emf control circuit presented in figure
8-1A However, the panel wiring diagram locates the wiring on the panel
in relationship to the actual location of the equipment terminals on the
rear of the control panel. Troubleshooting or checking of original installations
requires an accurate comparison of the elementary and panel diagrams. It
is recommended that the electrician use a system of checking connections
on the diagram with the actual panel connections. For example, a colored
pencil may be used to make check marks on the diagram as each connection
is properly traced on the panel and compared to the diagram.

Fig. 8—2 Panel wiring diagram for a dc counter emf motor controller
CONDUIT OR EXTERNAL WIRING PLAN
All necessary external wiring between isolated panels and equipment is
shown in the conduit plan (figure 8—3). The proper size of conduit, size
and number of wires, and destination of each wire is indicated on this
plan. An electrician refers to this plan when completing the actual installation
of the counter emf controller.

Fig. 8—3 Conduit or external wiring plan for a counter emf
controller: for internal connections see panel wiring diagram; pushbutton
station; size of conduit no. of wires, size of wires; power supply; shunt
motor.

Fig. 8—4 (A) Basic electrical theory of a dc motor-generator
variable speed control system. (B) Packaged motor-generator with dc variable
speed control system supplied from ac.
DC ADJUSTABLE SPEED DRIVES
DC adjustable speed drives are available in convenient units that include
all necessary control and power circuits.
Some machinery requirements are so precise that the ac variable frequency
drives may not be suitable (See unit 16). In such cases dc motors provide
characteristics that are not available on ac motors. A dc motor with adjustable
voltage control is very versatile. and can be adapted to a large variety
of applications.
In the larger horsepower range, the motor-generator set used to be one
of the most widely used methods of obtaining variable speed control. The
set consists of an ac motor driving a dc generator to supply power to a
dc motor. Such motor-generator set drives, called Ward-Leonard Systems,
control the speed of the motor by adjusting the power sup plied to the
field of the generator, and, as a result, the output voltage to the motor
(figure 8—4). The generator field current can be varied with rheostats,
as shown, or by variable transformers supplying a dc rectifier, or automatically
with the use of solid-state controls. When it is desirable to control the
motor field as well, similar means are used.
The speed and torque of the system shown in figure 8—4 can be controlled
by adjusting the voltage to the field, or to the armature, or both. Speeds
above the motor base speed (nameplate speed) are obtained by weakening
the motor shunt field. Speeds below the motor base speed are obtained by
weakening the generator field. As a result, there is a decrease in the
generator voltage supplying the dc motor armature. The motor should have
a full shunt field for speeds lower than the base speed to give the effect
of continuous control, rather than step control of the motor speed.
The motor used to furnish the driving power may be a three-phase induction
motor, as shown in figure 8—4. After the driving motor is started, it runs
continuously at a constant speed to drive the dc generator.
The armature of the generator is coupled electrically to the motor armature
as shown. If the field strength of the generator is varied, the voltage
from the dc generator can be controlled to send any amount of current to
the dc motor. As a result, the motor can be made to turn at many different
speeds. Because of the inductance of the dc fields and the time required
by the generator to build up voltage, extremely smooth acceleration is
obtained from zero r/min to speeds greater than the base speed.
The field of the dc generator can be reversed automatically, or manually,
with a resulting reversal of the motor rotation.
The generator field resistance can be changed automatically by the use
of SCRs (or thyristors) or time-delay relays operated by a counter EMF
across the motor armature. The generator field resistance can also be changed
manually.
Electrically controlled variable speed motor drives offer a wide choice
of speed ranges, torque, and horsepower characteristics. They provide a
means for controlling acceleration and deceleration, and methods of automatic
or manual operation. A control ling tachometer feedback signal may be driven
by the dc motor shaft. This is a system refinement to obtain a preset constant
speed. This method depends upon the type of application, the speed, and
the degree of response desired. In addition to speed, the controlling feedback
signal may be set to respond to pressure, tension, shock, or some other
transducer function.
One of the most advantageous characteristics of the motor-generator set
drive is its inherent ability to regenerate. In other words, when a high
inertia load overdrives the motor, the dc motor becomes a generator and
delivers reverse power. For example, assume the dc motor is running at
base speed. If the generator voltage is decreased by adjusting the rheostat
to slow the motor, the motor counter voltage will be higher than the generator
voltage and the current reverses. This action results in reverse torque
in the motor and the motor slows down. This process is called dynamic braking.
This dynamic feature is very desirable when used on hoists for lowering
heavy loads, metal working machines, textile and paper processing machines,
and for general industry for the con trolled stopping of high inertia loads.
Multiple motor drives are also accomplished with this type of motor-generator
drive.
Motor-generator set drives using automatic regulators have been used for
years for nearly every type of application. A higher degree of sophistication
in controls has been developed, making it possible to meet almost any desired
level of precision or response.

Fig. 8—5 Control panel for SCR controlled DC motor drive.

Fig. 8—6 Silicon Controlled Rectifier (SCR) of various sizes.
STATIC MOTOR CONTROL DRIVES
Despite the widespread acceptance and use of the motor-generator drives,
rotating machines were required to convert ac to mechanical power. As a
result, the combined efficiency of the set is rather low; it requires the
usual rotating machine maintenance, and it is noisy. Static dc drives now
being used have no moving parts in the power conversion equipment that
converts (rectifies) and controls the ac power (figures 8—5 and 8—6). The
solid-state devices are used for controlled conversion of ac line power
to dc.
The basic theory for obtaining dc motor speeds below and above base speed
are the same as with a motor-generator set. It is only the method of controlling
the voltages and field strengths that differs. For example, in Figure 8—7,
the armature is supplied with dc rectified from an ac source. The ac is
rectified by the use of the S.C.R. in the controlled circuit to obtain
dc. The gate of the thyristor will turn on the S.C.R. at the proper portion
of the half wave, thereby controlling the motor below base speed. Figure
8—7 is a simplified circuit for the purpose of illustration. The field
strength would be held at its fullest strength in a similar manner. For
above motor base speed, the field control can weaken field strength with
full armature voltage. The feedback tachometer will maintain a preset speed.

Fig. 8—7 Single-phase, half-wave armature controlling a small
motor. feedback tachometer; field.
In figure 8—7, the SCR is controlled by the setting of the potentiometer,
speed control. This varies the “on” time of the thyristor per ac cycle,
and thus varies the amount of average current flow to the armature. When
speed control above the base speed is required, the rectifier circuit in
the field is controlled by SCRs, rather than diodes.
The SCR, or thyristor, can control all of the positive waveform or voltage
through the use of a method called phase shifting. It is not the
intent of this text to cover the theory of the method.
The SCR is probably the most popular solid-state device for controlling
large and small electrical power loads. The SCR is a controlled rectifier
which controls an electric current. It will not conduct when the voltage
across it is in the wrong direction. It will con duct only in the forward
direction when the proper signal (voltage) is applied to the gate terminal.
The gate is normally controlled by electronic pulses from a control circuit.
The gate will turn the SCR on but will not turn it off in a dc circuit.
To turn the anode-cathode section of the SCR on (close the switch), the
gate must be the same polarity as the anode with respect to the cathode.
Once the gate has turned the SCR on, it will remain on until the current
flowing through the power circuit (anode-cathode section) is either interrupted
or drops to a low enough level to permit the device to turn off. The anode
to cathode current must fall below the holding current level. The holding
current, or maintaining current, is the amount of current required to keep
the SCR turned on. The SCR performs the same function as a rheostat would
in controlling motor field strengths or voltage to an armature. It is similar
to a variable resistance, since it can be adjusted throughout its power
range. The SCR control has replaced the rheostat since it is smaller in
size for the same current rating, is more energy efficient, and is cheaper.
Figure 8—8 illustrates two sophisticated, single-phase, packaged, static
control ac motor drive controls. They are shown with their wiring exposed
and in their boxes. More elaborate units are available for three-phase
ac power supplies.

Fig. 8—8 AC motor drive control
SUMMARY
DC motors need controls to start, stop, protect, and adjust the speed
and torque of the motor. The systems used must comply with the NEC and
also have approval from testing firms such as UL. The motors must be protected
from overheating and causing damage to the motor and the surrounding area.
This unit introduced the two general styles of wiring diagrams: the schematic,
which shows the electrical location of the components, and the wiring diagram
which shows the physical relationship of the equipment. Motor generator
sets were presented to familiarize you with the possible sources of dc
control. Now much of the control is done by solid state dc electronic drives.
QUIZ
Select the correct answer for each of the following statements.
1. The least important plan or diagram in troubleshooting motor controls
is probably the
a. elementary plan.
b. panel diagram.
c. external conduit plan.
d. layout of the area in which the controllers are installed.
2. The best diagram to use to determine how a controller operates is the:
a. elementary plan.
b. panel plan.
c. external plan.
d. architectural plan.
3. The physical location of control wires is shown on the:
a. elementary plan.
b. architectural plan.
c. conduit plan.
d. panel wiring diagram.
4. The dc counter emf controller results from the automatic actions of
the:
a. applied voltage.
b. changing voltage across the armature.
c. changing voltage across the field.
d. starting current.
5. Overload protection is the same as
a. starting protection. c. electrical protection.
b. mechanical protection. d. running protection.
6. Overload contacts open the circuit when the motor current reaches:
a. 85 percent of full load.
b. 100 percent of full load.
c. 125 percent of full load.
d. 150 percent of full load.
7. In the event a motor is allowed to exceed the permissible current value,
it is protected by:
a. starting protection.
b. fuses.
c. an overload thermal element.
d. the stop button.
8. With the disconnect switch closed, the shunt field in figure 8-1 is
placed across the line when the:
a. A contact closes.
b. disconnect switch is closed.
c. M contact closes.
d. start button closes.
9. In figure 8—1, contact A is closed when the:
a. start button is closed.
b. stop button is opened.
c. A coil is deenergized.
d. A coil is energized.
10. The motor in figure 8—1 is placed across the line when:
a. the start button is closed.
b. the disconnect switch is closed.
c. contact A is closed.
d. contact M is closed.
11. What is the dc motor base speed?
12. How is the speed of a dc motor controlled above the base speed?
13. How is the speed of a dc motor controlled below the base speed?
14. How may an SCR replace a rheostat?
15. List the advantages of using thyristors in the motor drive control? |