The two-wire control circuit is commonly
used in applications where the operation of a system is automatic and
basically two wires are used to provide voltage to the load. This may
include such applications as sump pumps, tank pumps, electric heating,
and air compressors. In these systems one typically closes a disconnect
switch or circuit breaker to energize the circuit, and the actual energizing
of the motor in the system is controlled by the operation of the pilot
device.
The circuit is called a two-wire control because only two wires are
needed to energize the motor starter coil. The circuit controls that
are located prior to the coil will provide the operational and safety
features, and the overload contacts that are located after the coil are
used to protect the circuit against over-currents.
Figure 1 (above) shows a ladder diagram of the two-wire control circuit
for a pumping station and Figure 2 (above) shows the control circuit
as a wiring diagram. Note that it's difficult to see the sequence of
operation in the wiring diagram, so you generally use the ladder diagram
to determine the sequence of operation. The wiring diagram shows the
location of all wires and components.
Voltage to the pumping station is provided through a fused disconnect.
After the disconnect is closed, the float switch in the diagram is in
complete control of the motor starter. Notice that the float control
is identified as a float switch. When the level of the sump rises past
the setpoint on the control, its contacts will energize and the motor
starter coil will become energized. The coil of the motor starter will
energize and pull in the motor starter contacts, which will energize
the motor. As the motor operates, it will pump the liquid to reduce the
level in the sump. When the level of the sump is lowered, the level switch
will sense the change in level and switch its contacts off, which will
de-energize the motor starter coil. When the motor starter coil is de-energized,
the motor starter contacts are opened, and the motor is turned off.
This on/off sequence will continue automatically until the disconnect
is switched off or unless the motor starter overloads are tripped. If
the motor draws too much current when it's pumping, the heaters will
trip the overload contacts and open the control circuit, which will interrupt
current flow to the motor starter coil. Since the overloads must be reset
manually, the circuit won't become ener gized automatically when the
overload is cleared. In this case, someone must physically come to the
motor starter and press the reset button. At this time, the system should
be thoroughly inspected for the cause of the overload. It would also
be important to use a clamp-on ammeter to determine the full-load amperage
(FLA) of the motor and cross-reference this to the size of the heaters
in the motor starter to see that they match. The FLA should be checked
against the motor’s data plate. You should also take into account the
service factor listed on the data plate when you are trying to determine
if the pump motor is operating correctly.
Figure 3 (right) shows
a more complex two-wire control circuit that is used to control an air
compressor. Notice that the wiring diagram for the control and load circuit
is shown in Figure 3a and the ladder diagram of the control circuit
is shown in Figure 3b. This circuit is still a two-wire control circuit
andit's used to turn the air compressor on automatically when the pressure
drops below 30 psi and to turn off the compressor when the pressure reaches
90 psi. Pressure switch A in this circuit controls the operation of the
control at these pressures. Its high and low pressures are adjustable
so that the system could be energized and de-energized at other pressures
if the need arises. A hand switch is provided in this circuit that allows
the system to be pumped to a predetermined pressure. The hand switch
is intended to be used when the auto switch is not functioning properly
or if you need to test the system.
Right: Fig. 3 (a) A wiring diagram of a two-wire
control circuit for a compressor motor. The compressor motor is controlled
by a motor starter that is energized by one of two pressure switches.
(b) A ladder diagram of the same circuit shown in the wiring diagram.
In this circuit notice a selector switch pro vides “hand” or “auto” control.
Pressure switch A is in the circuit when the selector switch is in auto,
and pressure switch B is in the circuit when the selector switch is in
manual.
Pressure switch B in this diagram acts as a safety for this circuit.
This pressure switch is set at 120 psi and is not adjustable. It's in
the circuit to prevent the tank pressure from rising too high. This could
occur if the operational pressure switch became faulty and would not
open when the pressure reached 90 psi. It could also be used to protect
the system against overpressure when the switch is in the hand position.
Generally, the safety switch is meant to protect the system against component
failure or control failure.
If a pressure control would fail, the compressor would continue pumping
air into the tank, which would allow its pressure to rise to an unsafe
level. Since the operational switch is still closed, the air pressure
in the tank could be increased to a level where the pump would cause
the motor to stall if the safety switch were not in the circuit. This
could build up pressure to several hundred pounds, which could cause
lines and fittings in the air system to explode.
The nonadjustable pressure switch would act as a backup to the operational
switch and trip off anytime the pressure reaches 120 psi. This switch
is also different in thatit's interlocked when it trips, so that it must
be reset manually by having someone press the reset button. If you find
the reset button activated on the safety switch, you must test the system
thoroughly to determine why the operational switch did not control the
circuit.
In normal operation, the motor starter would cycle the air compressor
on and off to keep the pressure in the tank between the high and low
setpoint that is set on the operational control. The motor starter overloads
could also trip this circuit and require manual reset. This could occur
if the motor was incurring overcurrent problems. The overcurrent could
occur due to bad bearings or if someone physically depresses the switch.
When this push button is released, the NO contacts return to their NO
state.
The NO auxiliary contacts from the motor starter will close when the
motor starter coil is energized. When they close they will provide an
alternate path around the push-button contacts for current to get to
the coil. These contacts are called seal or seal-in contacts when they
are used in this manner. Sometimes the seal contacts are said to have
memory, since they will maintain the last state of the push buttons in
the circuit. |