|
In all these examples the problem is caused
by the increase in normal operating current to the point where damage
can occur. Circuit breakers can sense either the heat or magnetic forces
as they increase beyond the maximum safe level, and fuses and overloads
can sense increased heat that the overload creates. Separation of these
devices will cause a set of contacts or a conducting element to open
anytime the current increases above the safe level. This presents a problem
with some loads, such as motors that have a very large inrush current
when they start.
Figure 1 shows a graph of the inrush current caused by a 208 volt,
5hp motor starting. Notice that the motor will draw 16.5 A at full load.
This motor will draw up to 99 A when it starts, which is six times the
amount of full-load current. This presents a problem in protecting against
overcurrents because a circuit breaker or fuse that is sized to protect
the motor during full-load current (16.5 A) would trip when the motor
is started, and if they are sized to allow the motor to start (99 A),
they won't provide adequate protection when the motor is running at full-load
current.

Above: Fig. 1 A graph of inrush current for a 208 volt, 5hp motor.
Several solutions to this problem are available. One of them is a motor
starter with heaters and overloads, and another is inverse-time circuit
breakers. Each of these devices provides several minutes of time delay
before they trip and take the motor off line. The theory of their operation
involves allowing small overcurrents to exist for up to 4 or 5 minutes,
and allowing larger overcurrents to exist for less than 10 seconds. These
times are based on the amount of time a specific overload condition can
exist before a motor begins to sustain damage. The devices must be sized
properly to provide adequate protection, and may be adjusted slightly
once they are installed. The only problem that remains with the inverse-time
circuit breaker and overloads is that they cannot sense a short circuit
and open the circuit fast enough to provide interruption capacity. |