When a conductor from one potential comes
in contact with the system ground or a conductor from another potential,
a short circuit can occur. The short circuit provides little or no impedance
to the power source, so that the current can rise to 100 times the full-load
current levels in one or two cycles. That is, currents of 50,000 A or
larger are possible if the current is allowed to build.
Figure 1 shows a graph of the current developed by a short circuit.
Notice that the current continues to increase with each cycle of the
ac voltage. As this current increases, it will build up powerful magnetic
forces and tremendous amounts of heat energy that will cause the metal
conductors and terminals to melt and explode.

Above: Fig. 1 (a) Example graph of short-circuit current. (b) Example
of graph of current when a circuit breaker is used to protect against short-circuit current. (c) Example
graph of current when a fuse is used to protect against short-circuit current.
A circuit breaker is an electromechanical device that requires approximately
one-half of an AC cycle (positive or negative half of a sine wave) to
sense the short circuit and another half-cycle to trip its mechanical
contacts. The short-circuit current may still reach 40,000 - 45,000 A
during this period of time before the circuit breaker can open its contacts
fully. In some cases, the heat from this short-circuit current is so
intense that it will actually weld the contacts of the circuit breaker
together so that they cannot open even though the circuit breaker’s trip
mechanism has activated. When this occurs, the short-circuit current
continues to increase and eventually causes severe damage.
In comparison a fuse can sense the overcurrent as it begins to build
and its fusable link will melt before the current increases to a dangerous
level. A graph of the protection that a fuse can provide during a short
circuit is also shown in Figure 1. From this graph, notice that the
fuse element will open as soon as the current reaches the overcurrent
level. That is, the short-circuit fault will be sensed and opened in
less than a half-cycle. The only problem with the single- element fuse
is that it must be sized up to six times the full-load current level
to allow the motor to start. This leaves two alternatives when providing
short-circuit and overload current: fuses in combination with motor starters
or circuit breakers, or the use of a dual-element fuse. |